SUSWE SU-300 Series

Contents

SUSWE SU-300 Series Frequency Converter User Manual

Model: SU-300 Series | Brand: SUSWE

1. Introduction

Thank you for selecting the SUSWE SU-300 series vector frequency converter. This manual provides essential information for the correct and safe use of your frequency converter, also known as an Adjustable Speed Drive or VFD. The SU-300 series is designed for high-performance motor control, offering stable quality, reduced energy loss, and high torque even at low frequencies. It supports various power configurations from 0.75KW to 5.5KW, with both single-phase 220V and three-phase 380V input options.

This manual is intended for system design and model selection staff, installation and wiring personnel, debugging technicians, and maintenance staff.

2. Safety Information and Precautions

To ensure safe operation and prevent injury or damage, please adhere to the following safety guidelines:

2.1. Danger

  • Power Disconnection: Always confirm that the input power has been cut off before wiring to avoid electric shock and fire.
  • Professional Wiring: All wiring operations must be performed by qualified electrical engineering professionals.
  • Grounding: The grounding terminal must be reliably grounded. For 380V systems, ensure special Type 3 grounding.
  • Emergency Stop: After connecting the emergency stop terminal, verify its effective operation.
  • Output Terminals: Do not touch the output terminals directly. The frequency converter's output terminals are directly connected to the motor; avoid short-circuiting them.
  • Terminal Cover: Ensure the terminal cover is properly installed before powering on. When disassembling, disconnect the power supply first.
  • Power Discharge: After cutting off power, wait 5 to 8 minutes for residual power to discharge completely before inspection or maintenance.
  • Qualified Personnel: Only professional technical personnel are permitted to perform inspection and maintenance.

2.2. Attention

  • Voltage Matching: Verify that the input power supply voltage matches the rated input voltage of the frequency converter.
  • Braking Resistor/Unit: Connect the braking resistor or braking unit according to the provided wiring diagram.
  • Terminal Tightening: Use a screwdriver and wrench with the specified torque to tighten terminals.
  • Incorrect Wiring: Do not connect the input power cord to the output U/V/W terminals, as this can cause internal damage.
  • Panel Removal: Only remove the terminal cover for wiring; do not remove the front panel cover.

3. Product Overview

The SUSWE SU-300 series frequency converter is a high-performance vector control device designed for precise motor speed regulation. It features a compact design, robust protection functions, and an intuitive control panel.

3.1. Key Features

  • High Performance: Utilizes advanced vector control for stable and efficient operation.
  • Energy Saving: Optimized design to reduce energy loss.
  • Robust Protection: Includes six protection functions: overcurrent, overvoltage, undervoltage, overload, power module protection, and overtemperature protection.
  • User-Friendly Interface: Classic control panel with quick keys and a smart display for easy operation and monitoring.
  • Wide Application: Suitable for various industrial applications including motors, blenders, water pumps, cranes, and CNC lathes.

3.2. Dimensions

The SU-300 series frequency converter is designed with a compact footprint for easy installation.

Dimensions of the SU-300 Frequency Converter
Figure 3.2.1: Approximate dimensions of the SU-300 Frequency Converter (9.5 cm width, 18.0 cm height, 11.3 cm depth).

For detailed dimensions and installation hole sizes, refer to the table below:

Table 3.2.1: SU-300 Series Exterior and Installation Dimensions
PowerH1 (mm)H2 (mm)W1 (mm)D1 (mm)H (mm)W (mm)D (mm)Mounting Hole (mm)
0.75KW-2.2KW130/73/142851094
4KW-5.5KW168/83/18095.5113.64
7.5KW-11KW230/96/2401071544.3

3.3. Control Panel

The control panel provides an intuitive interface for operating and monitoring the frequency converter.

Control Panel Layout
Figure 3.3.1: Classic control panel layout with labeled buttons and display.

Control Panel Elements:

  • Display: 5-digit LED display showing frequency (Hz), current (A), voltage (V), and various parameters.
  • RUN Indicator: Lit when running, off when stopped.
  • F/R Indicator: Lit for forward rotation.
  • TC (Fault) Indicator: Flashing indicates a fault state.
  • PRG (Programming Key): Enters/exits Level 1 menu.
  • M-FUN (Multifunction Selection Key): Used for function shift selection.
  • Up/Increment Key: Increases data or function code.
  • Down/Decrement Key: Decreases data or function code.
  • SHIFT Key: Cycles display parameters, selects parameter modification bit.
  • ENTER (Confirm Key): Enters sub-menus, confirms settings.
  • RUN Key: Starts operation in keyboard control mode.
  • STOP/REST Key: Stops operation, resets fault alarms.
  • Speed Control Knob: Adjusts speed.

4. Specifications

The following tables detail the technical specifications and inverter series indicators for the SU-300 series frequency converter.

4.1. Technical Specifications

Table 4.1.1: General Technical Specifications
CategoryParameterSpecification
InputRated Voltage, FrequencyThree-phase (G3 series) 380V; 50/60HZ; Three-phase (G2 series) 220V: 50/60HZ
Allowable Voltage VariationThree-phase (G3 series) 320V~460V; Three-phase (G2 series) 190V~250V
Output VoltageG3 series: 0~380V; G2 series: 0~220V
OutputFrequencyV/F control, simple vector control: 0.0~999.9HZ; Advanced vector control and torque control: 0.5-300.0HZ
Overload Capacity110% long-term; 150% 1 minute; 180% 5 seconds
Control CharacteristicsControl MethodV/F control, simple vector control, advanced vector control, torque control
Frequency Setting ResolutionAnalog input: 0.1% of maximum output frequency; Digital setting: 0.1HZ
Frequency AccuracyWithin 0.2% of maximum output frequency; Digital input: 0.01% of set output frequency
V/F Curve (Voltage Frequency Characteristics)Linear torque, square torque, user-defined V/F curve
V/F ControlTorque IncreaseManual setting: 0.0-30.0% of rated output; Automatic lifting based on output current and motor parameters
Automatic Current and Voltage LimitingAutomatically detects and suppresses motor current and voltage during operation
Non-Inductive Vector ControlStarting Torque100% rated torque at 5.0Hz (V/F control); 150% rated torque at 1.0Hz (vector control)
Current and Voltage SuppressionFull process current closed-loop control, avoiding current surge
Under Voltage SuppressionMaintains operation during low grid voltage and fluctuations
Other FunctionsMulti-speed operation (7-segment programmable), PID control, RS485 communication
EnvironmentAmbient Temperature-10°C~+40°C (derate for 40°C~50°C)
Humidity5%~95%RH, no condensation
StructureProtection LevelIP20
Installation MethodWall mounted, cabinet mounted

4.2. Inverter Series Indicators

Product Parameters Table
Figure 4.2.1: Product parameters for various SU-300 models.
Table 4.2.1: SU-300 Series Inverter Indicators
Converter ModelPower Supply Capacity (KVA)Input Voltage (V)Rated Output Current (A)Adapted Motor kWAdapted Motor HP
SU300-0R75G21.5Single-phase 200V-240V 50Hz/60Hz40.751
SU300-1R5G23Single-phase 200V-240V 50Hz/60Hz71.52
SU300-2R2G24Single-phase 200V-240V 50Hz/60Hz9.62.23
SU300-4R0G25.5Single-phase 200V-240V 50Hz/60Hz1744
SU300-5R5G28.9Single-phase 200V-240V 50Hz/60Hz255.55
SU300-0R75G31.5Three-phase 340V-440V 50Hz/60Hz2.50.751
SU300-1R5G33Three-phase 340V-440V 50Hz/60Hz4.11.52
SU300-2R2G34Three-phase 340V-440V 50Hz/60Hz5.82.23
SU300-4R0G36.1Three-phase 340V-440V 50Hz/60Hz9.045
SU300-5R5G38.9Three-phase 340V-440V 50Hz/60Hz135.57.5

5. Installation and Wiring

Proper installation and wiring are crucial for the safe and effective operation of the frequency converter. The wiring is divided into the main circuit and the control circuit.

5.1. Mounting

The SU-300 series supports guide rail one-button installation for convenience.

Guide rail one-button installation, top view
Figure 5.1.1: Guide rail installation mechanism (top view).
Guide rail one-button installation, side view
Figure 5.1.2: Guide rail installation mechanism (side view).

5.2. Main Circuit Wiring

The main circuit connects the power supply to the frequency converter and the frequency converter to the motor. Ensure all connections are secure and follow local electrical regulations for wire diameter specifications.

Single-phase Power Supply Wiring Diagram
Figure 5.2.1: Single-phase power supply wiring diagram. Connect L1, L2 from power supply, and U, V, W to motor.
Three-phase Power Supply Wiring Diagram
Figure 5.2.2: Three-phase power supply wiring diagram. Connect R, S, T from power supply, and U, V, W to motor.
Main Line Terminal Connection Diagram
Figure 5.2.3: Main line terminal connection diagram showing input three-phase 380V connected to R/S/T.

Wiring Precautions for Main Circuit:

  • Do not connect AC input power to the output terminals U, V, W of the frequency converter.
  • When the carrier frequency is less than 4KHz, the maximum distance between the frequency converter and the motor should be within 50 meters. For higher frequencies, reduce this distance and consider laying wiring in a metal tube.
  • If installing peripheral devices (filters, reactors), measure insulation resistance to ground (should not be lower than 4 megohms).
  • Do not install phase capacitors or resistance-capacitance absorption devices at the output terminals U, V, and W.
  • If frequent starting is required, use the COM/RUN control terminal for start/stop operation instead of cycling power to avoid damaging the rectifier bridge.

5.3. Control Circuit Wiring

The control circuit handles signals for operation, display, and communication. Use shielded wires and isolation devices for external control lines.

Control Circuit Terminal Connections
Figure 5.3.1: Terminal connections for S5/Y, AO, AI, and 485.
Control Wiring Diagram with Start/Stop Buttons
Figure 5.3.2: Example control wiring diagram showing connections for start (启动) and stop (停止) buttons to DI1 and DI2.

Wiring Precautions for Control Circuit:

  • External control lines should be shielded and routed separately from main circuit wiring to minimize electromagnetic interference.
  • Ensure proper connection of control circuit terminals as per the diagrams.

6. Operation and Display

The frequency converter's operation is managed through its control panel, allowing for parameter modification, status monitoring, and start/stop control.

6.1. Basic Operation

  • Power On: After ensuring all wiring is correct and safe, apply power to the unit.
  • Display Monitoring: The LED display will show real-time operating parameters such as output frequency, current, and voltage. Use the SHIFT key to cycle through different display parameters.
  • Start/Stop: In keyboard operation mode, press the RUN key to start the motor and the STOP/REST key to stop it.
  • Speed Adjustment: Use the speed control knob to adjust the output frequency and motor speed.

6.2. Parameter Settings

The frequency converter's behavior can be customized by adjusting various function parameters. These are organized into groups (F0, F1, F2, etc.).

  • Entering Parameter Menu: Press the PRG key to enter the Level 1 parameter menu.
  • Navigating Parameters: Use the Up/Down keys to scroll through parameter groups and individual parameters.
  • Modifying Parameters: Press ENTER to select a parameter. Use the SHIFT key to select the digit to modify, and the Up/Down keys to change the value. Press ENTER again to confirm the new value.
  • Exiting Menu: Press PRG repeatedly to exit the parameter menu and return to the main display.

For a complete list and detailed descriptions of all function parameters, please refer to the comprehensive PDF manual.

7. Maintenance

Regular maintenance ensures the longevity and optimal performance of your frequency converter.

  • Cleaning: Keep the unit clean and free from dust and debris. Use a soft, dry cloth for cleaning.
  • Inspection: Periodically inspect all wiring connections for tightness and signs of wear or damage.
  • Cooling Fan: Ensure the cooling fan is free from obstructions and operating correctly. A faulty fan can lead to overheating.
  • Environmental Conditions: Operate the frequency converter within specified temperature and humidity ranges. Avoid direct sunlight, corrosive gases, oil mist, and excessive dust.
  • Professional Service: Any complex maintenance or repair should only be performed by qualified technical personnel.

8. Troubleshooting

This section provides common issues, their possible causes, and corrective actions. For detailed fault codes and advanced troubleshooting, refer to the full PDF manual.

8.1. Common Faults and Solutions

Table 8.1.1: Common Abnormalities and Countermeasures
Fault PhenomenonPossible CausesCorrective Actions
No Display on KeypadPower failure, missing phase in input power, incorrect wiring.Check power supply and wiring.
No Display, but Internal Charge Indicator is LitKeypad-related wiring issues, faulty switching power supply, damaged starting resistor, faulty voltage regulator.Check keypad wiring, internal power supply, starting resistor, and voltage regulator.
Motor HummingMotor load is too heavy.Reduce the load.
Motor Doesn't Accelerate/Decelerate SmoothlyInappropriate acceleration/deceleration time setting, current limit value too low, overvoltage protection during deceleration, inappropriate carrier frequency setting, heavy load, oscillation.Increase acceleration/deceleration time, increase current limit, increase deceleration time, adjust carrier frequency, reduce load, adjust V/F control parameters.
Motor can rotate but speed cannot be adjustedFrequency setting too low, frequency gain too small, incorrect speed control method.Adjust frequency settings, check speed control method.
Motor speed fluctuates during operationFrequent load fluctuations, inverter and motor ratings mismatch, poor contact of frequency setting potentiometer, fluctuating frequency reference signal.Minimize load variation, set motor parameters to actual values, switch to digital frequency setting, increase filter time constant.
Motor rotation direction is oppositeIncorrect phase sequence of output terminals U, V, W; incorrect operation direction setting; output phase loss.Adjust phase sequence, set operation direction (F0-12=1) to reverse, check motor wiring.

8.2. Fault Codes (E Group)

The frequency converter may display specific fault codes to indicate issues. Below are some common E-group fault codes:

Table 8.2.1: Common E-Group Fault Codes
CodeNamePossible CausesCorrective Actions
E0C1Overcurrent during AccelerationShort acceleration time, inverter power too small, improper V/F curve or torque boost setting.Increase acceleration time, use higher power inverter, adjust V/F curve or torque boost.
E0C2Overcurrent during DecelerationShort deceleration time, inverter power too small.Increase deceleration time, use higher power inverter.
E0C3Overcurrent during Constant SpeedSudden load change or abnormality, inverter power too small.Check load or reduce load variations, use higher power inverter.
EHU1Overvoltage during AccelerationAbnormal input voltage, restarting a rotating motor.Check input power, set to start after DC braking.
ELUOUndervoltage during OperationAbnormal input voltage or relay not pulled in.Check power supply voltage or contact manufacturer.
EPLIOutput Phase Loss ProtectionOutput phase loss on U, V, W.Check output wiring.
EPAOPipe Burst FaultFeedback pressure less than low pressure detection threshold or greater than/equal to high pressure detection threshold.Check feedback wiring or adjust high/low pressure detection thresholds.

9. User Tips

Based on common user inquiries, here are some helpful tips for operating your SU-300 series frequency converter:

  • Adjusting Frequency Limit: To increase the Hz limit up to 400Hz, refer to parameters F0-04 (Max Output Frequency) and F0-05 (Upper Frequency Limit) in the function parameter table.
  • Changing Motor Direction: The motor's direction of rotation can be changed by adjusting parameter F0-12 (Rotation Direction Setting) or by modifying the wiring connections to the motor (U, V, W terminals).
  • Voltage Compatibility: The 380V 3-phase input models are designed to withstand voltage variations between 320V and 460V. Always ensure your input voltage is within the specified range for your model.
  • Varying Motor Speed: This frequency converter is specifically designed to vary the speed of AC motors. For detailed instructions on how to connect and operate it for speed variation, refer to the 'Installation and Wiring' and 'Operation and Display' sections.
  • Connecting a Selector for Forward/Reverse: To connect a selector switch for forward and reverse motor operation, refer to the 'Control Circuit Wiring' section and diagrams. Digital input terminals (DI1, DI2, etc.) are typically used for such control signals.

10. Warranty and Support

Your SUSWE SU-300 series frequency converter comes with a 1-year warranty, ensuring quality and reliability.

10.1. Technical Support

Should you have any questions or require technical assistance, please contact our customer service staff. Our professionals are dedicated to providing comprehensive support.

10.2. User Manual (PDF)

For a more detailed and comprehensive guide, including in-depth parameter descriptions and advanced troubleshooting, please refer to the official PDF user manual. You can view or download it from the following link: SUSWE SU-300 Series Operating Specification Manual V2.0 (PDF).