1. Introduction
The Eastron ESP-E11 is a DIN rail mountable RS485 to Ethernet protocol converter designed for IoT solutions. This device facilitates data transfer from RS485 interfaces to TCP/IP networks. It integrates a TCP/IP controller, memory, and a 10/100M Ethernet transceiver. The ESP-E11 utilizes a fully developed TCP/IP network stack and FreeRTOS operating system, and includes an embedded web server for device configuration. Its highly integrated hardware and software platform make it suitable for industrial control, smart grid, personal medical applications, and remote control scenarios requiring low data rates and infrequent data transmission/reception.

2. Key Features
- Small Size
- DIN Rail Mounting
- Modbus RTU to Modbus TCP/IP converter
- Support for 10/100M Ethernet Auto-Negotiation
- Webpage Easy Configuration or PC IoT Service Tool for setup

3. Setup and Installation
3.1 Physical Installation
The ESP-E11 is designed for DIN rail mounting. Securely attach the device to a standard DIN rail in your control cabinet or enclosure.
3.2 Wiring Diagram
Follow the wiring diagram below for proper connection of power, RS485, and Ethernet.

- Power Input: Connect L (Live), N (Neutral), and GND (Ground) to the 100~240VAC@50~60Hz power supply.
- RS485 Interface: Connect the RS485 A, B, and GND terminals. Ensure correct polarity for communication.
- Ethernet Port: Connect a standard RJ45 Ethernet cable to the device for network connectivity.
3.3 Initial Configuration
The ESP-E11 can be configured via its embedded web server or a PC IoT Service Tool. Refer to the device's datasheet for detailed instructions on accessing and using the configuration interface.
- Web Configuration: Access the device's IP address through a web browser to configure network settings, Modbus parameters, and other operational modes.
- PC IoT Service Tool: Utilize the dedicated PC software for UART fast configuration or other service tool functionalities.
4. Operation
Once installed and configured, the ESP-E11 operates as a transparent gateway between RS485 devices and an Ethernet network, converting Modbus RTU to Modbus TCP/IP.
4.1 LED Indicators
The device features several LED indicators to show its status:
- Power: Indicates power supply status.
- Link: Indicates Ethernet link status.
- Active: Indicates data activity on the Ethernet port.
- Net: Indicates network connection status.

4.2 Network Protocols
The ESP-E11 supports a wide range of network protocols for versatile integration:
- IP, TCP, UDP, DHCP, DNS, HTTP Server/Client, ARP, AutoIP, ICMP, Telnet, NTP, Modbus TCP.
4.3 Modbus Conversion
The primary function of the ESP-E11 is to convert Modbus RTU commands from the Ethernet network to RS485 and vice-versa, allowing Modbus RTU devices to communicate over TCP/IP.
5. Maintenance
The ESP-E11 is designed for reliable operation with minimal maintenance. However, periodic checks are recommended:
- Ensure all wiring connections are secure and free from corrosion.
- Keep the device clean and free from dust and debris to ensure proper heat dissipation.
- Verify LED indicators for normal operation.
- Periodically check for firmware updates on the manufacturer's website to ensure optimal performance and security.
6. Troubleshooting
If you encounter issues with your ESP-E11, consider the following:
- No Power LED: Check the power supply connections and ensure the input voltage is within the specified range (100~240VAC).
- No Link LED: Verify the Ethernet cable connection to both the ESP-E11 and the network switch/router. Ensure the network device is powered on.
- No Net LED: Check network configuration (IP address, subnet mask, gateway, DNS). Ensure the device can reach the network.
- RS485 Communication Issues:
- Verify RS485 wiring polarity (A/B).
- Check baud rate, data bits, stop bits, and parity settings in the device configuration to match your RS485 devices.
- Ensure proper termination resistors are used on the RS485 bus if required by your setup.
- Configuration Access Issues: If you cannot access the web interface, ensure your PC is on the same network segment as the ESP-E11 and that its IP address is correctly configured. Try resetting the device to factory defaults if configuration is lost (refer to datasheet for reset procedure).
7. Specifications
The following table details the technical specifications of the ESP-E11 RS485-Ethernet Converter:
| Parameter | Value |
|---|---|
| Processor/Frequency | Cortex-M3/96MHz |
| Flash/SDRAM | 2MB/128KB |
| Operating System | FreeRTOS |
| Port Number | 1 |
| Interface Standard | 10/100 Base-T Auto-Negotiation |
| Transformer | Integrated |
| Network Protocol | IP,TCP,UDP,DHCP,DNS,HTTP Server/Client,ARP, AutoIP, ICMP,Telnet, NTP, Modbus TCP |
| Security Protocol | AES 128Bit DES3 |
| RS485 Port Number | 1 RS485 |
| Data Bits | 5, 6, 7, 8 |
| Stop Bit | 1, 2 |
| Check Bit | None, Even, Odd |
| Baud Rate | TTL: 600bps~460800bps |
| Flow Control | No Flow Control, Software Xon/Xoff flow control |
| Web Pages | Http Web Configuration Customization of HTTP Web Pages |
| Configuration | Web CLI/XML import, Telnet/IOT Service PC Software UART Fast Config |
| Firmware Upgrade | Webpage, IoT Service Tools |
| Size | 97.60mm x 64.95mm x 27.50mm |
| Operating Temp. | -40 ~ 85°C |
| Storage Temp. | -45 ~ 105°C, 5 ~ 95% RH(no condensation) |
| Input Voltage | ESP-E11: 100~240VAC@50~60Hz |
| Working Current | ~100mA |
| Power | <400mW |

8. Warranty and Support
8.1 Warranty
The ESP-E11 comes with an 18-month warranty. For warranty claims or service, please contact Eastron customer support.
8.2 Technical Support
For technical assistance, datasheets, Modbus protocol instructions, or Modbus register maps, please visit the official Eastron website at www.eastrongroup.com or contact their customer support directly.
9. User Tips
- Always ensure proper grounding to prevent electrical interference and ensure stable operation.
- When configuring, double-check all network and serial communication parameters to avoid connectivity issues.
- For complex Modbus implementations, refer to the official Modbus protocol documentation in conjunction with the device's specific register map.
10. Frequently Asked Questions (FAQ)
- Q: Where can I get a Datasheet?
- A: Datasheets can be downloaded from the official Eastron website: www.eastrongroup.com.
- Q: What is the warranty of your products?
- A: The warranty period for this product is 18 months.
- Q: Can you offer Modbus protocol instruction/Modbus register map?
- A: Yes, Eastron can provide Modbus protocol instructions and register maps. Please contact them for this information.