Eastron ESP-E11

Contents

ESP-E11 RS485-Ethernet Converter User Manual

Model: ESP-E11 | Brand: Eastron

1. Introduction

The Eastron ESP-E11 is a DIN rail mountable RS485 to Ethernet protocol converter designed for IoT solutions. This device facilitates data transfer from RS485 interfaces to TCP/IP networks. It integrates a TCP/IP controller, memory, and a 10/100M Ethernet transceiver. The ESP-E11 utilizes a fully developed TCP/IP network stack and FreeRTOS operating system, and includes an embedded web server for device configuration. Its highly integrated hardware and software platform make it suitable for industrial control, smart grid, personal medical applications, and remote control scenarios requiring low data rates and infrequent data transmission/reception.

Eastron ESP-E11 RS485 to Ethernet Converter
Figure 1: Eastron ESP-E11 RS485 to Ethernet Protocol Converter for IoT Solutions.

2. Key Features

  • Small Size
  • DIN Rail Mounting
  • Modbus RTU to Modbus TCP/IP converter
  • Support for 10/100M Ethernet Auto-Negotiation
  • Webpage Easy Configuration or PC IoT Service Tool for setup
Product Features and Overview of ESP-E11
Figure 2: Overview of ESP-E11 features and design.

3. Setup and Installation

3.1 Physical Installation

The ESP-E11 is designed for DIN rail mounting. Securely attach the device to a standard DIN rail in your control cabinet or enclosure.

3.2 Wiring Diagram

Follow the wiring diagram below for proper connection of power, RS485, and Ethernet.

ESP-E11 Wiring Diagram and Dimensions
Figure 3: Wiring Diagram and Physical Dimensions of the ESP-E11.
  • Power Input: Connect L (Live), N (Neutral), and GND (Ground) to the 100~240VAC@50~60Hz power supply.
  • RS485 Interface: Connect the RS485 A, B, and GND terminals. Ensure correct polarity for communication.
  • Ethernet Port: Connect a standard RJ45 Ethernet cable to the device for network connectivity.

3.3 Initial Configuration

The ESP-E11 can be configured via its embedded web server or a PC IoT Service Tool. Refer to the device's datasheet for detailed instructions on accessing and using the configuration interface.

  • Web Configuration: Access the device's IP address through a web browser to configure network settings, Modbus parameters, and other operational modes.
  • PC IoT Service Tool: Utilize the dedicated PC software for UART fast configuration or other service tool functionalities.

4. Operation

Once installed and configured, the ESP-E11 operates as a transparent gateway between RS485 devices and an Ethernet network, converting Modbus RTU to Modbus TCP/IP.

4.1 LED Indicators

The device features several LED indicators to show its status:

  • Power: Indicates power supply status.
  • Link: Indicates Ethernet link status.
  • Active: Indicates data activity on the Ethernet port.
  • Net: Indicates network connection status.
ESP-E11 Product Display and Detail Views
Figure 4: Detailed views of the ESP-E11, showing LED indicators and ports.

4.2 Network Protocols

The ESP-E11 supports a wide range of network protocols for versatile integration:

  • IP, TCP, UDP, DHCP, DNS, HTTP Server/Client, ARP, AutoIP, ICMP, Telnet, NTP, Modbus TCP.

4.3 Modbus Conversion

The primary function of the ESP-E11 is to convert Modbus RTU commands from the Ethernet network to RS485 and vice-versa, allowing Modbus RTU devices to communicate over TCP/IP.

5. Maintenance

The ESP-E11 is designed for reliable operation with minimal maintenance. However, periodic checks are recommended:

  • Ensure all wiring connections are secure and free from corrosion.
  • Keep the device clean and free from dust and debris to ensure proper heat dissipation.
  • Verify LED indicators for normal operation.
  • Periodically check for firmware updates on the manufacturer's website to ensure optimal performance and security.

6. Troubleshooting

If you encounter issues with your ESP-E11, consider the following:

  • No Power LED: Check the power supply connections and ensure the input voltage is within the specified range (100~240VAC).
  • No Link LED: Verify the Ethernet cable connection to both the ESP-E11 and the network switch/router. Ensure the network device is powered on.
  • No Net LED: Check network configuration (IP address, subnet mask, gateway, DNS). Ensure the device can reach the network.
  • RS485 Communication Issues:
    • Verify RS485 wiring polarity (A/B).
    • Check baud rate, data bits, stop bits, and parity settings in the device configuration to match your RS485 devices.
    • Ensure proper termination resistors are used on the RS485 bus if required by your setup.
  • Configuration Access Issues: If you cannot access the web interface, ensure your PC is on the same network segment as the ESP-E11 and that its IP address is correctly configured. Try resetting the device to factory defaults if configuration is lost (refer to datasheet for reset procedure).

7. Specifications

The following table details the technical specifications of the ESP-E11 RS485-Ethernet Converter:

ParameterValue
Processor/FrequencyCortex-M3/96MHz
Flash/SDRAM2MB/128KB
Operating SystemFreeRTOS
Port Number1
Interface Standard10/100 Base-T Auto-Negotiation
TransformerIntegrated
Network ProtocolIP,TCP,UDP,DHCP,DNS,HTTP Server/Client,ARP, AutoIP, ICMP,Telnet, NTP, Modbus TCP
Security ProtocolAES 128Bit DES3
RS485 Port Number1 RS485
Data Bits5, 6, 7, 8
Stop Bit1, 2
Check BitNone, Even, Odd
Baud RateTTL: 600bps~460800bps
Flow ControlNo Flow Control, Software Xon/Xoff flow control
Web PagesHttp Web Configuration Customization of HTTP Web Pages
ConfigurationWeb CLI/XML import, Telnet/IOT Service PC Software UART Fast Config
Firmware UpgradeWebpage, IoT Service Tools
Size97.60mm x 64.95mm x 27.50mm
Operating Temp.-40 ~ 85°C
Storage Temp.-45 ~ 105°C, 5 ~ 95% RH(no condensation)
Input VoltageESP-E11: 100~240VAC@50~60Hz
Working Current~100mA
Power<400mW
ESP-E11 Product Parameters Table
Figure 5: Detailed product parameters for the ESP-E11.

8. Warranty and Support

8.1 Warranty

The ESP-E11 comes with an 18-month warranty. For warranty claims or service, please contact Eastron customer support.

8.2 Technical Support

For technical assistance, datasheets, Modbus protocol instructions, or Modbus register maps, please visit the official Eastron website at www.eastrongroup.com or contact their customer support directly.

9. User Tips

  • Always ensure proper grounding to prevent electrical interference and ensure stable operation.
  • When configuring, double-check all network and serial communication parameters to avoid connectivity issues.
  • For complex Modbus implementations, refer to the official Modbus protocol documentation in conjunction with the device's specific register map.

10. Frequently Asked Questions (FAQ)

Q: Where can I get a Datasheet?
A: Datasheets can be downloaded from the official Eastron website: www.eastrongroup.com.
Q: What is the warranty of your products?
A: The warranty period for this product is 18 months.
Q: Can you offer Modbus protocol instruction/Modbus register map?
A: Yes, Eastron can provide Modbus protocol instructions and register maps. Please contact them for this information.
FAQ section with common questions and answers
Figure 6: Frequently Asked Questions.
Documents and downloads

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.