GEYA GYR10N-50

Contents

GEYA GYR10N-50 Electronic Type RCBO Instruction Manual

Residual Current Circuit Breaker with Over-Current Protection

1. Introduction

The GEYA GYR10N-50 Series Residual Current Circuit Breaker with Over-Current Protection (RCBO) is designed for use in electrical lines with AC 50Hz or 60Hz, a rated voltage of 230V/240V, and a rated current up to 50A. This electronic type RCBO provides essential protection against earth fault/leakage current, short-circuit, and overload conditions, while also functioning as an isolation device. It offers complementary protection against direct contact by the human body and effectively safeguards electrical equipment from insulation failure.

The GYR10N-50 is a compact device, taking up only 18mm of space, similar to a standard single-pole switch, making it suitable for both household and commercial distribution systems.

Front view of GEYA GYR10N-50 RCBO with pre-wired connections
Figure 1: GEYA GYR10N-50 RCBO (Front View with Wires)

2. Safety Information

WARNING: Installation and maintenance of this device must be performed by a qualified electrician in accordance with all local and national electrical codes and regulations. Failure to follow these instructions may result in serious injury or death.

  • Always disconnect power at the main service panel before working on electrical circuits.
  • Verify that the power is off using a voltage tester before touching any wires.
  • Do not use this device if it appears damaged.
  • Ensure proper grounding connections.
  • The device is designed for specific voltage and current ratings. Do not exceed these ratings.

3. Product Overview

The GYR10N-50 RCBO features a compact design for DIN rail mounting. Key components include:

  • Operating Lever: Used to manually switch the RCBO ON or OFF.
  • Indicator Window: Provides a visual indication of the breaker's ON (green) or OFF (red) status.
  • Test Button: Used to periodically test the residual current protection function.
  • Terminals: Clearly marked for Line Input (LIN), Line Output (LOUT), Neutral Input (N INOUT), and Neutral Output (N LOUT).
Side view of GEYA GYR10N-50 RCBO
Figure 2: GEYA GYR10N-50 RCBO (Side View)
Front view of GEYA GYR10N-50 RCBO without pre-wired connections
Figure 3: GEYA GYR10N-50 RCBO (Front View without Wires)

4. Specifications

FeatureSpecification
Model NumberGYR10N-50 RCBO
Product NameRCBO Electronic Type
TypeResidual Current (RCD), Type A or Type AC
Poles1P+N
Rated Voltage220V, AC230/240V
Rated Current16A, 25A, 32A, 40A, 50A
Rated Sensitivity10mA, 30mA, 100mA, 300mA
Breaking Capacity6000A (6kA)
Rated Frequency50/60Hz
StandardIEC61009-1
Mounting35mm Din Rail
Optimum Operating Temperature-25℃ to 40℃
Electro-mechanical Endurance4000 cycles
Terminal Tightening Torque1.2N
Suitable BusbarPIN Busbar
Is Smart DeviceNo
Wireless FunctionalityNo
Includes BatteryNo
EU LVD VoltageBelow 50Vac or 75Vdc
CertificationCE

5. Setup and Installation

The GEYA GYR10N-50 RCBO is designed for 35mm DIN rail mounting. Follow these steps for safe and correct installation:

  1. Mounting: Securely attach the RCBO to a 35mm DIN rail within your electrical distribution board.
  2. Wiring: Refer to the wiring diagram below for correct connections. Ensure all connections are tight and secure with a terminal tightening torque of 1.2N.
    • Connect the incoming Line (Phase) wire to the terminal marked 'LIN'.
    • Connect the outgoing Line (Phase) wire to the terminal marked 'LOUT'.
    • Connect the incoming Neutral wire to the terminal marked 'N INOUT'.
    • Connect the outgoing Neutral wire to the terminal marked 'N LOUT'.
    • Ensure proper grounding of the entire electrical system.
  3. Verification: Double-check all wiring connections before restoring power.
Dimensions and wiring diagram for GEYA GYR10N-50 RCBO
Figure 4: GEYA GYR10N-50 RCBO Dimensions and Wiring Diagram

Note: The wiring diagram shows the internal connections and terminal designations. Ensure the incoming power (LINE 1, LINE N) is connected to the top terminals (LIN, N INOUT) and the load (LOAD 2, LOAD N) is connected to the bottom terminals (LOUT, N LOUT). This device is not bi-directional; power must flow from the designated input to the output.

6. Operating Instructions

  1. Switching ON: Push the operating lever upwards to the 'ON' position. The indicator window should show green.
  2. Switching OFF: Push the operating lever downwards to the 'OFF' position. The indicator window should show red.
  3. Tripping: In case of an earth fault, short-circuit, or overload, the RCBO will automatically trip, moving the operating lever to the 'OFF' position and showing red in the indicator window.
  4. Resetting: After a trip, identify and rectify the cause of the fault. Then, push the operating lever fully downwards to reset the internal mechanism, and then push it upwards to the 'ON' position. If the RCBO immediately trips again, a fault still exists.

7. Maintenance

Regular maintenance ensures the continued reliable operation of your GEYA GYR10N-50 RCBO.

  • Monthly Test: Press the 'Test' button (usually marked 'T' or 'Test') at least once a month. The RCBO should trip immediately. If it does not trip, the device may be faulty and should be replaced by a qualified electrician.
  • Visual Inspection: Periodically inspect the RCBO for any signs of physical damage, discoloration, or loose connections.
  • Cleaning: Keep the device clean and free from dust and debris. Use a dry, soft cloth for cleaning. Do not use liquids or abrasive cleaners.

8. Troubleshooting

If your GEYA GYR10N-50 RCBO is not functioning as expected, consider the following:

  • RCBO Trips Frequently: This indicates a persistent fault in the circuit it protects. Common causes include:
    • Overload: Too many appliances connected to the circuit.
    • Short-circuit: Faulty wiring or appliance.
    • Earth leakage: Damaged insulation, faulty appliance, or moisture.
  • RCBO Does Not Reset: If the RCBO trips and cannot be reset, there is likely a severe or persistent fault in the circuit. Do not force the lever.
  • RCBO Does Not Trip During Test: If pressing the test button does not cause the RCBO to trip, the device itself may be faulty and requires immediate replacement.

Always consult a qualified electrician for any persistent issues or if you are unsure about diagnosing or resolving an electrical fault.

9. User Tips

  • The compact 18mm width of the GYR10N-50 makes it an excellent choice for installations where space is limited, fitting into the same slot as a single-pole switch.
  • Users have noted the high quality of materials and workmanship, contributing to stable operation without false tripping.
  • This RCBO is a reliable option for enhancing electrical safety in both residential and commercial settings.

10. Frequently Asked Questions (FAQ)

Q: Is the GEYA GYR10N-50 RCBO bi-directional?
A: No, the GYR10N-50 RCBO is not bi-directional. It has designated input (LINE) and output (LOAD) terminals, as indicated in the wiring diagram. Ensure power flows from the incoming terminals (LIN, N INOUT) to the outgoing terminals (LOUT, N LOUT).

11. Warranty and Support

For warranty information, technical support, or service inquiries, please contact GEYA directly. Ensure you have your product model number and purchase details available.

Manufacturer: YUEQING GEYA ELECTRICAL CO., LTD.

GEYA contact information business card
Figure 5: GEYA Contact Information

Website: www.geya.net

Email: cassie@cngeya.com

Phone: +86 13968799499

Address: Wenzhou Bridge Industrial Zone, Beibaixiang Town, Wenzhou City, Zhejiang Province

12. About GEYA

GEYA Electric, established in 2007, is a private-owned enterprise specializing in the research, manufacturing, and sales of low-voltage electrical and automatic controlling products. The company is committed to top quality and constant innovation, utilizing top-level numerical control machines and fully automated process lines to ensure steady and stable production quality. GEYA products are certified to required industry standards, including CCC, CE, CB, SAA, SEMKO, TUV, and RoHS.