ZILMET 11A HYDRO-PRO Series, ULTRA-PRO Series

Contents

ZILMET Expansion Tank User Manual

Models: 11A HYDRO-PRO Series, ULTRA-PRO Series (various capacities)

Introduction

This manual provides essential information for the safe and efficient installation, operation, and maintenance of your ZILMET expansion tank. ZILMET expansion tanks are designed for use in various hydraulic systems, including ground heating, water pump systems, and as pressure stabilizing or make-up water tanks. They play a crucial role in maintaining system pressure and absorbing volume changes caused by temperature fluctuations, thereby protecting system components and improving efficiency.

Assortment of ZILMET expansion tanks in various sizes
Figure 1: ZILMET expansion tanks of different capacities.

Specifications

ZILMET expansion tanks are available in various models and capacities, each designed for specific system requirements. Key specifications include maximum working pressure, operating temperature range, and pre-charge pressure. All ZILMET tanks are manufactured in Italy.

General Product Attributes

  • DIY Supplies: Electrical
  • Material: Carbon steel (tank body)
  • Driving Method: Power-driven (refers to the system the tank integrates with, e.g., a pump-driven system)
  • Certification: None (as listed in product attributes)

HYDRO-PRO Series Technical Specifications

Table of specifications for ZILMET HYDRO-PRO series expansion tanks
Figure 2: HYDRO-PRO Series Technical Specifications Table.

The HYDRO-PRO series offers tanks with a maximum working pressure of 10 bar and an operating temperature range of -10°C to +99°C. Pre-charge pressure varies by model.

ModelCapacity (L)Max Working Pressure (bar)Outer Dimensions D (mm)Outer Dimensions H (mm)Outer Dimensions h (mm)InterfacePre-pressure (bar)Gross Weight (KG)
11A0000200210123220241/2"G31.04
11A0000500510160298283/4"G31.7
11A0000800810200308283/4"G32.35
11A00012001210270292283/4"G23.28
11A00018001810270377283/4"G23.85
11A00024002410300420281"G25.75
11A00035003510380565281"G29.55

ULTRA-PRO Series Technical Specifications

Table of specifications for ZILMET ULTRA-PRO series expansion tanks
Figure 3: ULTRA-PRO Series Technical Specifications Table.

The ULTRA-PRO series includes models with varying maximum working pressures (8 bar, 10 bar, 16 bar, 20 bar) and capacities, primarily focusing on 19L and 24L options. Operating temperature range is -10°C to +99°C.

ModelCapacity (L)Max Working Pressure (bar)Outer Dimensions D (mm)Outer Dimensions Dtot (mm)Outer Dimensions H (mm)Outer Dimensions h (mm)InterfacePre-pressure (bar)Gross Weight (KG)
11000019111910270411--1"G1.54.4
1100002452248362-355-1"G1.55.75
11000024182410270-485-1"G1.54.9
11000024232416270-485-1"G29.5
11000024G92420270-485-1"G214.7
1100002430 (Horizontal)2410270290485-1"G1.5-

Note: Some models may have specific flange plate configurations as indicated in the product options.

Dimension Diagrams

Diagram showing vertical expansion tank dimensions D, H, and h
Figure 4: Vertical Tank Dimension Diagram (D=Diameter, H=Total Height, h=Connection Height).
Diagram showing horizontal expansion tank dimensions D, Dtot, H, and h
Figure 5: Horizontal Tank Dimension Diagram (D=Diameter, Dtot=Total Diameter, H=Length, h=Connection Height).

Setup and Installation

Proper installation is crucial for the safe and effective operation of your ZILMET expansion tank. It is highly recommended that installation be performed by a qualified professional in accordance with local codes and regulations.

  1. **Location Selection**: Choose a suitable location for the tank, considering its dimensions and weight when filled. Ensure adequate space for maintenance and inspection. The tank should be protected from freezing and excessive heat.
  2. **Pre-charge Pressure Check**: Before installation, verify the tank's pre-charge pressure using a reliable pressure gauge. Adjust the pressure if necessary to match the system's requirements, typically 0.2-0.3 bar below the system's minimum operating pressure. Refer to the specifications table for the factory pre-charge.
  3. **Mounting**: Securely mount the tank in its designated position. Vertical tanks should be installed upright, and horizontal tanks should be supported appropriately to prevent strain on connections. Some models may include a flange plate for specific mounting needs.
  4. **Connection**: Connect the expansion tank to the hydraulic system using appropriate fittings and piping. Ensure all connections are tight and leak-free. The interface size is specified in the tables (e.g., 1/2"G, 3/4"G, 1"G).
  5. **System Fill and Test**: After installation, slowly fill the system with water and carefully check for any leaks at all connection points. Monitor the system pressure to ensure it operates within the recommended range and that the expansion tank is functioning correctly.
Close-up of the bottom connection of an expansion tank, showing the threaded inlet
Figure 6: Tank bottom connection detail.

Important Safety Note: The tank is designed for operating temperatures between -10°C and +99°C. Do not expose the tank to temperatures outside this range, as it can lead to damage or system failure.

Operating Instructions

ZILMET expansion tanks are passive components designed to absorb volume changes in a closed hydraulic system. Once correctly installed and pre-charged, they operate automatically without requiring manual intervention during normal system operation.

  • Ensure the system pressure remains within the safe operating limits specified for your tank model and the overall hydraulic system.
  • The tank's internal diaphragm separates the system fluid from the pre-charged air, preventing waterlogging and maintaining efficiency.
  • No user interaction is typically required during normal operation, provided the system is properly maintained.

Maintenance

Regular maintenance helps ensure the longevity and optimal performance of your expansion tank and the overall hydraulic system. Adhere to the following guidelines:

  1. **Annual Pre-charge Check**: At least once a year, check the pre-charge pressure of the expansion tank. This should be done when the system is depressurized and cold. If the pressure is low, recharge it using an air pump to the recommended level.
  2. **Visual Inspection**: Periodically inspect the tank for any signs of corrosion, leaks, or physical damage. Pay attention to the connections and the tank body.
  3. **System Pressure Monitoring**: Regularly monitor the system pressure. Significant fluctuations or consistent low pressure might indicate an issue with the expansion tank or the system itself.
  4. **Cleaning**: Keep the exterior of the tank clean and free from debris to prevent corrosion and allow for easy inspection.

Troubleshooting

While expansion tanks are generally reliable, issues in the hydraulic system can sometimes be attributed to or affect the tank. Consult a qualified technician for complex issues or if you are unsure about any troubleshooting steps.

  • **Frequent Pressure Drops/Rises**: This could indicate a loss of pre-charge pressure in the tank. Check and recharge the pre-charge as per maintenance instructions. It could also signal a leak in the system or a faulty pressure relief valve.
  • **Water in Air Valve**: If water comes out when checking the air valve, the internal diaphragm may be ruptured. In this case, the tank will need to be replaced.
  • **Visible Leaks**: Any visible leaks from the tank body or connections require immediate attention. Depressurize the system and repair or replace the affected components.
  • **System Overheating/Underheating**: While not directly a tank issue, an improperly functioning expansion tank can contribute to system inefficiencies. Ensure the tank's pre-charge is correct and it is adequately sized for the system.

User Tips

No specific user tips were available from provided reviews or Q&A. However, general best practices for expansion tanks include:

  • Always ensure the pre-charge pressure is set correctly for your specific system to optimize performance and prevent premature wear.
  • Consider installing a service valve between the system and the expansion tank to facilitate easier maintenance and replacement without draining the entire system.
  • Regularly check the system's pressure gauge to catch potential issues early.

Warranty and Support