PowMr POW-HVM10.2M

Contents

PowMr 10.2KW/10200W Hybrid Solar Inverter User Manual

Model: POW-HVM10.2M

1. About This Manual

1.1 Purpose

This manual describes the assembly, installation, operation, and troubleshooting of the PowMr POW-HVM10.2M Hybrid Solar Inverter. Please read this manual carefully before installations and operations. Keep this manual for future reference.

1.2 Scope

This manual provides safety and installation guidelines as well as information on tools and wiring.

2. Safety Instructions

WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.

  1. Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
  2. CAUTION --To reduce risk of injury, charge only deep-cycle lead acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
  3. Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
  4. To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
  5. CAUTION – Only qualified personnel can install this device with battery.
  6. NEVER charge a frozen battery.
  7. For optimum operation of this inverter/charger, please follow required spec to select appropriate cable size. It's very important to correctly operate this inverter/charger.
  8. Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
  9. Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please refer to INSTALLATION section of this manual for the details.
  10. One piece of 150A fuse is provided as over-current protection for the battery supply.
  11. GROUNDING INSTRUCTIONS -This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulation to install this inverter.
  12. NEVER cause AC output and DC input short circuited. Do NOT connect to the mains when DC input short circuits.
  13. Warning!! Only qualified service persons are able to service this device. If errors still persist after following troubleshooting table, please send this inverter/charger back to local dealer or service center for maintenance.

3. Product Overview

3.1 Features

  • Pure sine wave inverter
  • Configurable input voltage range for home appliances and personal computers via LCD setting
  • Configurable battery charging current based on applications via LCD setting
  • Configurable AC/Solar Charger priority via LCD setting
  • Compatible to mains voltage or generator power
  • Auto restart while AC is recovering
  • Overload/ Over temperature/ short circuit protection
  • Smart battery charger design for optimized battery performance
  • Cold start function
  • Inverter running without battery
  • Output power factor 1.0
  • High PV input voltage range (90~500VDC)
  • WIFI & GPRS available for iOS and Android (optional module)
  • Built-in anti-dusk kit for harsh environment
  • Built-in 160A MPPT solar charge controller
  • One-click restoration to factory settings
  • Dual output
  • Built-in Lithium battery automatic activation
  • Touch button interface

3.2 Basic System Architecture

The following illustration shows basic application for this inverter/charger. It also includes following devices to have a complete running system: Generator or Utility, PV modules. Consult with your system integrator for other possible system architectures depending on your requirements. This inverter can power all kinds of appliances in home or office environment, including motor-type appliances such as tube light, fan, refrigerator and air conditioner.

Diagram of Hybrid Power System showing connections between PV Panel, Generator, Utility, Solar Inverter Charger, 48V Battery, and Household Load.
Figure 1: Hybrid Power System. This diagram illustrates how the inverter integrates PV panels, a generator or utility power, a 48V battery, and household loads.

3.3 Product Overview - Components

The PowMr POW-HVM10.2M is a high-quality all-in-one solar inverter with an attractive design that meets the requirements of most environments. It features a built-in MPPT charging control module with a wide PV input voltage range of 90-500V. It offers a dual-channel AC output configuration of up to 10.2KW. The inverter also includes multiple built-in protection features for the safety of your solar power system.

Front view of the PowMr 10.2KW Solar Hybrid Inverter with dimensions and key features.
Front view of the PowMr 10.2KW Solar Hybrid Inverter, highlighting its 160A MPPT solar charge controller, 10200W max PV array power, 500VDC max PV open circuit voltage, pure sine wave output, RGB lights, and one-click restoration feature. Dimensions are approximately 21.1 inches (height), 15.3 inches (width), and 5.1 inches (depth).
Product views of the PowMr Solar Inverter Charger from various angles, including front, side, and rear panels.
Various product views of the PowMr Solar Inverter Charger, showing the front display, side cooling vents, and the rear panel with connection terminals for PV, AC input/output, battery, and communication ports (WIFI, BMS).
Diagram illustrating the Smart Design features of the PowMr Solar Inverter Charger, including RGB light indicators for different working modes, three cooling fans, and an anti-dusk kit.
Smart Design features: RGB lights indicate working modes (Stationary-White, Battery-Red, Utility-Blue, PV-Purple). Equipped with three cooling fans for efficient heat dissipation and an anti-dust kit for product reliability in harsh environments.
Diagram showing 15 intelligent protection modes of the PowMr Solar Inverter.
Intelligent Protection Systems: The inverter includes 15 protection modes such as charge low/high temperature, discharge low/high temperature, discharge overcurrent, charging overcurrent, charging undervoltage, short-circuit, solar panel reverse connection, battery overvoltage, over temperature, and overload protection.
Diagram showing remote monitoring and control via the SMARTESS app for the PowMr Solar Inverter.
Remote Monitoring and Control: The inverter can be monitored and controlled via the 'SMARTESS' app, available on the App Store and Google Play. A WiFi module and GPRS data are optional and need to be purchased separately.
Product unboxing and overview video for the PowMr POW-HVM10.2M solar inverter. It shows the contents of the package, including the inverter, user manual, MC4 connectors, and grounding terminals, and highlights key features.

4. Installation

4.1 Unpacking and Inspection

Before installation, inspect the unit. Ensure that nothing inside the package is damaged. You should have received the following items:

  • The unit x 1
  • User manual x 1
  • Ring terminal x 1
  • MC4 terminal head x 2

4.2 Preparation

Before connecting all lines, remove the screws under the machine and remove the bottom cover plate.

4.3 Mounting the Unit

Consider the following points before selecting where to install:

  • Do not mount the inverter on flammable construction materials.
  • Mount on a solid surface.
  • Install this inverter at eye level in order to allow the LCD display to be read at all times.
  • For proper air circulation to dissipate heat, allow a clearance of approx. 20 cm to the side and approx. 50 cm above and below the unit.
  • The ambient temperature should be between 0°C and 55°C to ensure optimal operation.
  • The recommended installation position is to be adhered to the wall vertically.
  • Make sure that other objects and surfaces are left with enough space from the machine to ensure adequate heat dissipation and that there is enough room to remove the wires.

WARNING: SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.

Install the unit by screwing two screws. It's recommended to use M4 or M5 screws.

4.4 Battery Connection

CAUTION: For safety operation and regulation compliance, it's requested to install a separate DC over-current protector or disconnect device between battery and inverter. It may not be requested to have a disconnect device in some applications, however, it's still requested to have over-current protection installed. Please refer to typical amperage in below table as required fuse or breaker size.

WARNING! All wiring must be performed by a qualified personnel.

WARNING! It's very important for system safety and efficient operation to use appropriate cable for battery connection. To reduce risk of injury, please use the proper recommended cable size as below.

Recommended battery cable size
ModelWire SizeCable (mm²)Torque value (max)
8.2KW/10.2KW1 x 2AWG252 Nm

Please follow below steps to implement battery connection:

  1. Remove insulation sleeve 18 mm for positive and negative conductors.
  2. Suggest to put bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
  3. Connect all battery packs as below chart.
  4. Insert the battery wires flatly into battery connectors of inverter and make sure the bolts are tightened with torque of 2 Nm in clockwise direction. Make sure polarity at both the battery and the inverter/charge is correctly connected and conductors are tightly screwed into the battery terminals. Recommended tool: #2 Pozi Screwdriver.
Diagram showing battery connection in series for the inverter.
Battery connection diagram. This illustrates connecting multiple 12V batteries in series to achieve the required 48V for the inverter, ensuring correct polarity.

WARNING: Shock Hazard. Installation must be performed with care due to high battery voltage in series.

CAUTION!! Before making the final DC connection or closing DC breaker/disconnector, be sure positive (+) must be connected to positive (+) and negative (-) must be connected to negative (-).

4.5 AC Input/Output Connection

CAUTION!! Before connecting to AC input power source, please install a separate AC breaker between inverter and AC input power source. This will ensure the inverter can be securely disconnected during maintenance and fully protected from over current of AC input. The recommended spec of AC breaker is 63A for 8.2KW/10.2KW.

CAUTION!! There are two terminal blocks with “IN” and “OUT” markings. Please do NOT mis-connect input and output connectors.

WARNING! All wiring must be performed by a qualified personnel.

WARNING! It's very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce risk of injury, please use the proper recommended cable size as below.

Suggested cable requirement for AC wires
ModelGaugeCable (mm²)Torque Value
8.2KW/10.2KW10 AWG61.2 Nm

Please follow below steps to implement AC input/output connection:

  1. Before making AC input/output connection, be sure to open DC protector or disconnector first.
  2. Remove insulation sleeve 10mm for six conductors. And shorten phase L and neutral conductor N 3 mm.
  3. Insert AC input wires according to polarities indicated on terminal block and tighten the terminal screws. Be sure to connect PE protective conductor (①) first.
    • ① → Ground (yellow-green)
    • L → LINE (brown or black)
    • N → Neutral (blue)
Diagram showing AC input wiring connections to the inverter terminal block.
AC Input Wiring Diagram. Ensure correct polarity and secure connections for Ground, Line, and Neutral.

WARNING: Be sure that AC power source is disconnected before attempting to hardwire it to the unit.

  1. Then, insert AC output wires according to polarities indicated on terminal block and tighten terminal screws.
    • L → LINE (brown or black)
    • N → Neutral (blue)
  2. Make sure the wires are securely connected.

4.6 PV Connection

CAUTION: Before connecting to PV modules, please install separately a DC circuit breaker between inverter and PV modules.

WARNING! It's very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce risk of injury, please use the proper recommended cable size as below.

Suggested cable requirement for PV wires
ModelWire SizeCable (mm²)Torque value (max)
8.2KW/10.2KW1 x 10AWG61.2 Nm

PV Module Selection:

When selecting proper PV modules, please be sure to consider below parameters:

  1. Open circuit Voltage (Voc) of PV modules not exceeds max. PV array open circuit voltage of inverter.
  2. Open circuit Voltage (Voc) of PV modules should be higher than min. battery voltage.
PV Array Voltage Range
INVERTER MODELMax. PV Array Open Circuit VoltagePV Array MPPT Voltage Range
8.2KW/10.2KW500Vdc90Vdc~450Vdc

Take 250Wp PV module as an example. After considering above two parameters, the recommended module configurations are listed as below table.

Recommended PV Module Configurations (Example: 250Wp PV module)
Solar Panel Spec. (reference)SOLAR INPUT (Min in serial: 6 pcs, max. in serial: 13 pcs)Q'ty of panelsTotal input power
250Wp, Vmp: 30.1Vdc, Imp: 8.3A, Voc: 37.7Vdc, Isc: 8.4A, Cells: 606 pcs in serial6 pcs1500W
8 pcs in serial8 pcs2000W
12 pcs in serial12 pcs3000W
13 pcs in serial13 pcs3250W
12 pieces in serial and 3 sets in parallel36 pcs8200W
10 pieces in serial and 4 sets in parallel40 pcs10200W

PV Module Wire Connection

Step 1: Check the input voltage of PV array modules. The acceptable input voltage of the inverter is 120VDC - 500VDC. Please make sure that the maximum current load of each PV input connector is 10A.

CAUTION: Exceeding the maximum input voltage can destroy the unit!! Check the system before wire connection.

Step 2: Disconnect the DC circuit breaker.

Step 3: Assemble provided PV connectors with PV modules by the following below steps. Components for PV connectors and Tools:

Diagram showing MC4 connector components and assembly process.
MC4 Connector Assembly Process. This diagram illustrates how to strip cables, insert them into terminals, crimp, and then assemble the terminals into the connector housings.

Then, use spanner to screw pressure dome tightly to female connector and male connector as shown below.

Step 4: Check correct polarity of connection cable from PV modules and PV input connectors. Then, connect positive pole (+) of connection cable to positive pole (+) of PV input connector. Connect negative pole (-) of connection cable to negative pole (-) of PV input connector.

4.7 Final Assembly

After connecting all wirings, please put bottom cover back by screwing two screws as shown below.

4.8 Communication Connection

  1. Wi-Fi cloud communication (option): Please use supplied communication cable to connect to inverter and Wi-Fi module. Download APP and installed from APP store, and Refer to "Wi-Fi Plug Quick Installation Guideline" to set up network and registering. The inverter status would be shown by mobile phone APP or webpage of computer.
  2. GPRS cloud communication (option): Please use supplied communication cable to connect to inverter and GPRS module, and then applied external power to GPRS module. Download APP and installed from APP store, and Refer to “GPRS RTU Quick Installation Guideline" to set up network and registering. The inverter status would be shown by mobile phone APP or webpage of computer.
  3. Battery communication: The communication between the battery and the inverter can be realized through the battery communication interface, so that the inverter and the lithium battery can exchange information (Baudrate: 9600).
  4. Lithium battery and inverter connection: Use power cables, communication cables for lithium batteries, and inverters to connect. Note: Lithium battery and inverter positive and negative positions, check the correct installation; The RJ45 connector of the communication cable connects to the BMS port of the inverter, and the other RJ45 connector connects to the RS485 port of the lithium battery; Before connecting, make sure that the lithium battery and inverter are turned off. (It is recommended to install a circuit breaker for the power cables of the lithium battery and the inverter battery interface. Otherwise, a spark may occur.)
Diagram showing the lithium battery communication cable interface and connection to the inverter.
Lithium Battery Communication Cable Interface. This diagram shows the RJ45 connections for the BMS port on the inverter and the RS485 port on the lithium battery.

5. Operation

5.1 Power ON/OFF

Once the unit has been properly installed and the batteries are connected well, simply press the On/Off switch (located on the button of the case) to turn on the unit.

5.2 Operation and Display Panel

The operation and display panel, shown in the chart below, is on the front panel of the inverter. It includes three indicators, four function keys, and an LCD display, indicating the operating status and input/output power information.

LED Indicator Messages
LED IndicatorMessages
INV/AC (Green Solid On)Output is powered by utility in Line mode.
INV/AC (Green Flashing)Output is powered by battery or PV in battery mode.
CHG (Green Solid On)Battery is fully charged.
CHG (Green Flashing)Battery is charging.
FAULT (Red Solid On)Fault occurs in the inverter.
FAULT (Red Flashing)Warning condition occurs in the inverter.
Function Keys Description
Function KeyDescription
ESCTo exit setting mode
UPTo go to previous selection
DOWNTo go to next selection
ENTERTo confirm the selection in setting mode or enter setting mode

5.3 LCD Display Icons

LCD Display Icons and Descriptions
IconFunction description
Input Source Information: AC iconIndicates the AC input.
Input Source Information: PV iconIndicates the PV input.
Input Source Information: Voltage/Current/Power displayIndicate input voltage, input frequency, PV voltage, charger current (if PV in charging for 10.2KW models), charger power, battery voltage.
Configuration Program and Fault Information: (8.8.8)Indicates the setting programs.
Configuration Program and Fault Information: Warning/Fault iconIndicates the warning and fault codes.
Output Information: KW VA %Indicate output voltage, output frequency, load percent, load in VA, load in Watt and discharging current.
Load Information: OVER LOAD iconIndicates overload.
Mode Operation Information: Mains iconIndicates unit connects to the mains.
Mode Operation Information: PV panel iconIndicates unit connects to the PV panel.
Mode Operation Information: AC BYPASS iconIndicates load is supplied by utility power.
Mode Operation Information: Utility charger circuit iconIndicates the utility charger circuit is working.
Mode Operation Information: DC/AC inverter circuit iconIndicates the DC/AC inverter circuit is working.
Mute Operation: Mute iconIndicates unit alarm is disabled.

5.4 LCD Setting

After pressing and holding the ENTER button for 3 seconds, the unit will enter setting mode. Press "UP" or "DOWN" button to select setting programs. And then, press "ENTER" button to confirm the selection or ESC button to exit.

Refer to the PDF manual for detailed tables of all LCD settings (Programs 00-46) and their selectable options, including output source priority, charging current, AC input voltage range, battery type, auto restart settings, output frequency, output voltage, utility charging current, voltage point back to utility source, power point back to common power supply, alarm control, backlight control, beeps, overload bypass, record fault code, bulk charging voltage, floating charging voltage, low DC cut-off voltage, battery equalization settings, equalization interval, equalization activated immediately, GRID-tie operation, GRID-tie current, LED pattern light, dual output, dual output functional voltage point, lithium battery protocol, delayed grid access, and maximum second load.

5.5 Display Setting

The LCD display information will be switched in turns by pressing “UP” or “DOWN" key. The selectable information is switched as below order: input voltage, input frequency, PV voltage, charging current, charging power, battery voltage, output voltage, output frequency, load percentage, load in Watt, load in VA, load in Watt, DC discharging current, main CPU Version.

Refer to the PDF manual for detailed examples of display screens in charged and discharged states, both for power less than 1kW and greater than 1kW, as well as main CPU version checking.

5.6 Operating Mode Description

Refer to the PDF manual for detailed tables and display examples of the inverter's operating modes, including Standby mode, Line mode, Grid-Tie Operation, and Battery mode.

5.7 Battery Equalization Description

Equalization function is added into the charge controller. It reverses the buildup of negative chemical effects like stratification, a condition where acid concentration is greater at the bottom of the battery than at the top. Equalization also helps to remove sulfate crystals that might have built up on the plates. If left unchecked, this condition, called sulfation, will reduce the overall capacity of the battery. Therefore, it's recommended to equalize battery periodically.

RGB Light (option)

  • Battery Mode: Red Light
  • Utility Mode: Blue Light
  • PV Mode: Purple Light

How to Apply Equalization Function

You must enable battery equalization function in monitoring LCD setting program 30 first. Then, you may apply this function in device by either one of following methods:

  1. Setting equalization interval in program 35.
  2. Active equalization immediately in program 36.

When to Equalize

In float stage, when the setting equalization interval (battery equalization cycle) is arrived, or equalization is active immediately, the controller will start to enter Equalize stage.

Diagram showing battery equalization stages: Bulk, Absorption, Float, Equalize.
Battery Equalization Stages. This graph illustrates the voltage and current profiles during Bulk, Absorption, Float, and Equalize stages of battery charging.

Equalize charging time and timeout

In Equalize stage, the controller will supply power to charge battery as much as possible until battery voltage raises to battery equalization voltage. Then, constant-voltage regulation is applied to maintain battery voltage at the battery equalization voltage. The battery will remain in the Equalize stage until setting battery equalized time is arrived.

However, in Equalize stage, when battery equalized time is expired and battery voltage doesn't rise to battery equalization voltage point, the charge controller will extend the battery equalized time until battery voltage achieves battery equalization voltage. If battery voltage is still lower than battery equalization voltage when battery equalized timeout setting is over, the charge controller will stop equalization and return to float stage.

5.8 Mains and Lithium Battery Activation Function

  1. After 90s of mains power connection to the inverter, the machine is connected to the mains and starts to work.
  2. The inverter is in lithium battery mode (item 05 is LIP or LIL). After the mains is connected, the battery is not connected, and the mains activation function is automatically enabled.

5.9 Fault Reference Code

Refer to the PDF manual for detailed tables of Fault Codes and their corresponding Fault Events and Fault Conditions, including specific battery fault codes for lithium battery mode.

5.10 Warning Indicator

Refer to the PDF manual for detailed tables of Warning Codes, Warning Events, Audible Alarms, and Icon Flashing indicators, including specific battery warning codes for lithium battery mode.

6. Maintenance

6.1 Overview

Every inverter is already installed with an anti-dust kit from the factory. The inverter will automatically detect this kit and activate an internal thermal sensor to adjust internal temperature. This kit also keeps dust from your inverter and increases product reliability in harsh environments.

6.2 Clearance and Maintenance

  1. Step 1: Please loosen the screw in a counterclockwise direction on the top of the inverter.
  2. Step 2: Then, the dustproof case can be removed, and the air filter foam can be taken out as shown in the below chart.
  3. Step 3: Clean the air filter foam and dustproof case. After clearance, re-assemble the dust-kit back to the inverter.

NOTICE: The anti-dust kit should be cleaned from dust every one month.

7. Specifications

Table 1: Line Mode Specifications
INVERTER MODEL8.2KW10.2KW
Input Voltage WaveformSinusoidal (utility or generator)
Nominal Input Voltage230Vac
Low Loss Voltage170Vac±7V (UPS); 90Vac±7V (Appliances)
Low Loss Return Voltage180Vac±7V (UPS); 100Vac±7V (Appliances)
High Loss Voltage280Vac±7V
High Loss Return Voltage270Vac±7V
Max AC Input Voltage300Vac
Nominal Input Frequency50Hz / 60Hz (Auto detection)
Low Loss Frequency40±1Hz
Low Loss Return Frequency42±1Hz
High Loss Frequency65±1Hz
High Loss Return Frequency63±1Hz
Output Short Circuit ProtectionCircuit Breaker
Efficiency (Line Mode)>95% (Rated R load, battery full charged)
Transfer Time10ms typical (UPS); 20ms typical (Appliances)
Output power derating: When AC input voltage drops to 170V, the output power will be derated.Output Power Derating Curve
Table 2: Inverter Mode Specifications
INVERTER MODEL8.2KW10.2KW
Rated Output Power8.2KW10.2KW
Output Voltage WaveformPure Sine Wave
Output Voltage Regulation230Vac±5%
Output Frequency50Hz
Peak Efficiency93%
Overload Protection3s@≥150% load; 5s@101%~150% load
Surge Capacity2* rated power for 5 seconds
Nominal DC Input Voltage48Vdc
Cold Start Voltage46.0Vdc
Low DC Warning Voltage @load < 50%44.0Vdc
Low DC Warning Voltage @load ≥ 50%42.0Vdc
Low DC Warning Return Voltage @load < 50%45.0Vdc
Low DC Warning Return Voltage @load ≥ 50%44.0Vdc
Low DC Cut-off Voltage @load < 50%41.0Vdc
Low DC Cut-off Voltage @load ≥ 50%40.0Vdc
High DC Recovery Voltage62Vdc
High DC Cut-off Voltage63Vdc
No Load Power Consumption70W75W
Table 3: Two Load Output Power
INVERTER MODEL8.2KW10.2KW
Full Load8200W10200W
Maximum Main Load8200W10200W
Maximum Second Load (battery model)2733W3400W
Main Load Cut Off Voltage44VDC
Main Load Return Voltage54VDC
Table 4: Charge Mode Specifications
Utility Charging Mode8.2KW10.2KW
Charging Algorithm3-Step
AC Charging Current (Max)140Amp140Amp
Bulk Charging Flooded Battery Voltage58.4V
AGM / Gel Battery Voltage56.4V
Floating Charging Voltage54Vdc
Charging CurveCharging Curve Diagram
MPPT Solar Charging Mode
INVERTER MODEL8.2KW10.2KW
Max. PV Array PowerPV1 Channel: 5400W, PV2 Channel: 5400WPV1 Channel: 5400W, PV2 Channel: 5400W
IMax.PVPV1 Channel: 18A, PV2 Channel: 18A
Nominal PV Voltage360Vdc
PV Array MPPT Voltage Range90Vdc~450Vdc
Max. PV Array Open Circuit Voltage500Vdc
Max Charging Current (AC charger plus solar charger)160Amp
Table 5: Grid-Tie Operation
INVERTER MODEL8.2KW10.2KW
Nominal Output Voltage220/230/240VAC
Feed-in Grid Voltage Range195~253VAC
Feed-in Grid Frequency Range50±1Hz/60±1Hz
Nominal Output Current35.6A44.3A
Power Factor Range>0.99
Maximum Conversion Efficiency (DC/AC)98%
Table 6: General Specifications
INVERTER MODEL8.2KW10.2KW
Safety CertificationCE
Operating Temperature Range-10°C to 50°C
Storage temperature-15°C~60°C
Humidity5% to 95% Relative Humidity (Non-condensing)
Dimension (D*W*H), mm500*390*136mm
Net Weight, kg14.514.7

Appendix: Approximate Back-up Time Table

Approximate Back-up Time Table for 8.2KW/10.2KW Inverter
ModelLoad (W)Backup Time @ 48Vdc 100Ah (min)Backup Time @ 48Vdc 200Ah (min)
8.2KW/10.2KW5006131288
1000268613
1500158402
2000111271
250090215
320076182
350065141
400050112
450044100
50004090
62003680
72003270
82002860
92002450
102002040

Note: 1. Backup time depends on the quality of the battery, age of battery and type of battery. Specifications of batteries may vary depending on different manufacturers. 2. The final interpretation right of this product belongs to the company.

8. Troubleshooting

Troubleshooting Guide
ProblemLCD/LED/BuzzerExplanation / Possible causeWhat to do
Unit shuts down automatically during startup process.LCD/LEDs and buzzer will be active for 3 seconds and then complete off.The battery voltage is too low (<1.91V/Cell)1. Re-charge battery. 2. Replace battery.
No response after power on.No indication.1. The battery voltage is far too low. (<1.4V/Cell) 2. Internal fuse tripped.1. Contact repair center for replacing the fuse. 2. Re-charge battery. 3. Replace battery.
Input voltage is displayed as 0 on the LCD and green LED is flashing.Input protector is trippedCheck if AC breaker is tripped and AC wiring is connected well.
Mains exist but the unit works in battery mode.Green LED is flashing.Insufficient quality of AC power. (Shore or Generator)1. Check if AC wires are too thin and/or too long. 2. Check if generator (if applied) is working well or if input voltage range setting is correct. (UPS/AP Appliance)
Green LED is flashing.Set "Solar First" as the priority of output source.Change output source priority to Utility first.
When the unit is turned on, internal relay is switched on and off repeatedly.LCD display and LEDs are flashingBattery is disconnected.Check if battery wires are connected well.
Fault code 07Overload error. The inverter is overload 110% and time is up.Reduce the connected load by switching off some equipment.
Fault code 05Output short circuited.Check if wiring is connected well and remove abnormal load.
Fault code 02Temperature of internal converter component is over 120°C. Internal temperature of inverter component is over 100°C.Check whether the air flow of the unit is blocked or whether the ambient temperature is too high.
Buzzer beeps continuously and red LED is on.Fault code 03Battery is over-charged. The battery voltage is too high.Return to repair center. Check if spec and quantity of batteries are meet requirements.
Fault code 01Fan faultReplace the fan.
Fault code 06/58Output abnormal (Inverter voltage below than 190Vac or is higher than 260Vac)1. Reduce the connected load. 2. Return to repair center
Fault code 08/09/53/57Internal components failed.Return to repair center.
Fault code 51Over current or surge.Restart the unit, if the error happens again, please return to repair center.
Fault code 52Bus voltage is too low.Restart the unit, if the error happens again, please return to repair center.
Fault code 55Output voltage is unbalanced.Restart the unit, if the error happens again, please return to repair center.

9. User Tips

  • Output Power: This inverter has an output power of 10200W.
  • Included Accessories: The package typically includes the inverter unit, a user manual, MC4 connectors, and a grounding terminal.
  • Off-Grid Functionality: This is a hybrid inverter, meaning it can function both with and without a grid connection.
  • PV Input Voltage: For normal operation, ensure the voltage from the connected solar panels is above 150V.

10. Warranty and Support

For technical support or warranty inquiries, please contact:

SHENZHEN HEHEJIN INDUSTRIAL CO.,LTD
Tel/Fax: +86 755-28219903
Email: support@powmr.com
Web: www.powmr.com
Add: Henggang Street, Longgang District, Shenzhen, Guangdong, China

The product comes with a 2-year warranty.