1. About This Manual
1.1 Purpose
This manual describes the assembly, installation, operation, and troubleshooting of this unit. Please read this manual carefully before installations and operations. Keep this manual for future reference.
1.2 Scope
This manual provides safety and installation guidelines as well as information on tools and wiring.
2. Safety Instructions
WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
- Before using the unit, read all instructions and cautionary markings on the unit, the batteries and all appropriate sections of this manual.
- CAUTION --To reduce risk of injury, charge only deep-cycle lead acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
- Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
- To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
- CAUTION – Only qualified personnel can install this device with battery.
- NEVER charge a frozen battery.
- For optimum operation of this inverter/charger, please follow required spec to select appropriate cable size. It's very important to correctly operate this inverter/charger.
- Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
- Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please refer to INSTALLATION section of this manual for the details.
- One piece of 150A fuse is provided as over-current protection for the battery supply.
- GROUNDING INSTRUCTIONS -This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulation to install this inverter.
- NEVER cause AC output and DC input short circuited. Do NOT connect to the mains when DC input short circuits.
- Warning!! Only qualified service persons are able to service this device. If errors still persist after following troubleshooting table, please send this inverter/charger back to local dealer or service center for maintenance.
3. Introduction
This is a multi-function inverter/charger, combining functions of inverter, solar charger and battery charger to offer uninterruptible power support with portable size. Its comprehensive LCD display offers user-configurable and easy-accessible button operation such as battery charging current, AC/solar charger priority, and acceptable input voltage based on different applications.
3.1 Features
- Pure sine wave inverter
- Configurable input voltage range for home appliances and personal computers via LCD setting
- Configurable battery charging current based on applications via LCD setting
- Configurable AC/Solar Charger priority via LCD setting
- Compatible to mains voltage or generator power
- Auto restart while AC is recovering
- Overload/ Over temperature/ short circuit protection
- Smart battery charger design for optimized battery performance
- Cold start function
- Inverter running without battery.
- Output power factor 1.0
- High PV input voltage range (90~500VDC).
- WIFI & GPRS available for iOS and Android.
- Built-in anti-dusk kit for harsh environment.
- Built-in 160A MPPT solar charge controller.
- One-click restoration to factory Settings.
- Dual AC output and dual PV input.
- Built-in Lithium battery automatic activation.
- Touch button interface.
3.2 Basic System Architecture
The following illustration shows basic application for this inverter/charger. It also includes following devices to have a complete running system: Generator or Utility, PV modules. Consult with your system integrator for other possible system architectures depending on your requirements. This inverter can power all kinds of appliances in home or office environment, including motor-type appliances such as tube light, fan, refrigerator and air conditioner.

3.3 Product Overview







4. Setup and Installation
4.1 Unpacking and Inspection
Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should have received the following items:
- The unit x 1
- User manual x 1
- Ring terminal x 1
- MC4 terminal head x 2
4.2 Preparation
Before connecting all lines, remove the screws under the machine and remove the bottom cover plate.
4.3 Mounting the Unit
Consider the following points before selecting where to install:
- Do not mount the inverter on flammable construction materials.
- Mount on a solid surface.
- Install this inverter at eye level in order to allow the LCD display to be read at all times.
- For proper air circulation to dissipate heat, allow a clearance of approx. 20 cm to the side and approx. 50 cm above and below the unit.
- The ambient temperature should be between 0°C and 55°C to ensure optimal operation.
- The recommended installation position is to be adhered to the wall vertically.
- Make sure that other objects and surfaces are left with enough space from the machine to ensure adequate heat dissipation and that there is enough room to remove the wires.
WARNING: SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.
Install the unit by screwing two screws. It's recommended to use M4 or M5 screws.
4.4 Battery Connection
CAUTION: For safety operation and regulation compliance, it's requested to install a separate DC over-current protector or disconnect device between battery and inverter. It may not be requested to have a disconnect device in some applications, however, it's still requested to have over-current protection installed. Please refer to typical amperage in below table as required fuse or breaker size.
WARNING! All wiring must be performed by a qualified personnel.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for battery connection. To reduce risk of injury, please use the proper recommended cable as below.
| Model | Wire Size | Cable (mm²) | Torque value (max) |
|---|---|---|---|
| 8.2KW/10.2KW | 1 x 2AWG | 25 | 2 Nm |
Please follow below steps to implement battery connection:
- Remove insulation sleeve 18 mm for positive and negative conductors.
- Suggest to put bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
- Connect all battery packs as below chart.

- Insert the battery wires flatly into battery connectors of inverter and make sure the bolts are tightened with torque of 2 Nm in clockwise direction. Make sure polarity at both the battery and the inverter/charge is correctly connected and conductors are tightly screwed into the battery terminals. Recommended tool: #2 Pozi Screwdriver.
WARNING: Shock Hazard Installation must be performed with care due to high battery voltage in series.
CAUTION!! Before making the final DC connection or closing DC breaker/disconnector, be sure positive (+) must be connected to positive (+) and negative (-) must be connected to negative (-).
4.5 AC Input/Output Connection
CAUTION!! Before connecting to AC input power source, please install a separate AC breaker between inverter and AC input power source. This will ensure the inverter can be securely disconnected during maintenance and fully protected from over current of AC input. The recommended spec of AC breaker is 63A for 8.2KW/10.2KW.
CAUTION!! There are two terminal blocks with “IN” and “OUT” markings. Please do NOT mis-connect input and output connectors.
WARNING! All wiring must be performed by a qualified personnel.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce risk of injury, please use the proper recommended cable size as below.
| Model | Gauge | Cable (mm²) | Torque Value |
|---|---|---|---|
| 8.2KW/10.2KW | 10 AWG | 6 | 1.2 Nm |
Please follow below steps to implement AC input/output connection:
- Before making AC input/output connection, be sure to open DC protector or disconnector first.
- Remove insulation sleeve 10mm for six conductors. And shorten phase L and neutral conductor N 3 mm.
- Insert AC input wires according to polarities indicated on terminal block and tighten the terminal screws. Be sure to connect PE protective conductor (①) first.
- ① → Ground (yellow-green)
- L → LINE (brown or black)
- N → Neutral (blue)
WARNING: Be sure that AC power source is disconnected before attempting to hardwire it to the unit.
- Then, insert AC output wires according to polarities indicated on terminal block and tighten terminal screws.
- L → LINE (brown or black)
- N → Neutral (blue)
- Make sure the wires are securely connected.
4.6 PV Connection
CAUTION: Before connecting to PV modules, please install separately a DC circuit breaker between inverter and PV modules.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce risk of injury, please use the proper recommended cable size as below.
| Model | Wire Size | Cable (mm²) | Torque value (max) |
|---|---|---|---|
| 8.2KW/10.2KW | 1 x 10AWG | 6 | 1.2 Nm |
PV Module Selection:
When selecting proper PV modules, please be sure to consider below parameters:
- Open circuit Voltage (Voc) of PV modules not exceeds max. PV array open circuit voltage of inverter.
- Open circuit Voltage (Voc) of PV modules should be higher than min. battery voltage.
| INVERTER MODEL | 8.2KW/10.2KW |
|---|---|
| Max. PV Array Open Circuit Voltage | 500Vdc |
| PV Array MPPT Voltage Range | 90Vdc~450Vdc |
Take 250Wp PV module as an example. After considering above two parameters, the recommended module configurations are listed as below table.
| Solar Panel Spec. (reference) | SOLAR INPUT (Min in serial: 6 pcs, max. in serial: 13 pcs) | Q'ty of panels | Total input power |
|---|---|---|---|
| 250Wp, Vmp: 30.1Vdc, Imp: 8.3A, Voc: 37.7Vdc, Isc: 8.4A, Cells: 60 | 6 pcs in serial | 6 pcs | 1500W |
| 8 pcs in serial | 8 pcs | 2000W | |
| 12 pcs in serial | 12 pcs | 3000W | |
| 13 pcs in serial | 13 pcs | 3250W | |
| 12 pieces in serial and 3 sets in parallel | 36 pcs | 8200W | |
| 10 pieces in serial and 4 sets in parallel | 40 pcs | 10200W |
PV Module Wire Connection
Step 1: Check the input voltage of PV array modules. The acceptable input voltage of the inverter is 120VDC - 500VDC. Please make sure that the maximum current load of each PV input connector is 10A.
CAUTION: Exceeding the maximum input voltage can destroy the unit!! Check the system before wire connection.

4.7 Final Assembly
After connecting all wirings, please put bottom cover back by screwing two screws.
4.8 Communication Connection
1. Wi-Fi cloud communication (option):
Please use supplied communication cable to connect to inverter and Wi-Fi module. Download APP and installed from APP store, and Refer to "Wi-Fi Plug Quick Installation Guideline" to set up network and registering. The inverter status would be shown by mobile phone APP or webpage of computer.
2. GPRS cloud communication (option):
Please use supplied communication cable to connect to inverter and GPRS module, and then applied external power to GPRS module. Download APP and installed from APP store, and Refer to “GPRS RTU Quick Installation Guideline" to set up network and registering. The inverter status would be shown by mobile phone APP or webpage of computer.
3. Battery communication
The communication between the battery and the inverter can be realized through the battery communication interface, so that the inverter and the lithium battery can exchange information (Baudrate: 9600).
4. Lithium battery and inverter connection:
Use power cables, communication cables for lithium batteries, and inverters to connect. Note: Lithium battery and inverter positive and negative positions, check the correct installation; The RJ45 connector of the communication cable connects to the BMS port of the inverter, and the other RJ45 connector connects to the RS485 port of the lithium battery; Before connecting, make sure that the lithium battery and inverter are turned off. (It is recommended to install a circuit breaker for the power cables of the lithium battery and the inverter battery interface. Otherwise, a spark may occur.)

In order to communicate with the lithium battery BMS, you should press the "ENTER" button for a long time, and set the battery type as "LIB-485" in program 05. Then select the matching battery protocol in Program 43.
| Program | Setting | Value | Description |
|---|---|---|---|
| 05 | Battery type | AGM (05 AGn), Flooded (05 FLd), User Defined (05 USE), Lithium battery mode (05 L I b) | Select battery type. For Lithium, choose '05 L I b'. |
| Lithium battery communication mode | L I b 05 485 | Enable RS485 communication for Lithium batteries. | |
| 43 | Lithium battery protocol | PYLON (43 PYL), PACE (43 PAC) | Select the specific Lithium battery protocol. |
CAUTION: When the battery type is set to "LIB-485", the setting items 12, 13 and 29 are displayed in percentage. When the battery type is set to "LIB-485", the user cannot modify the maximum charging current. When communication fails, the inverter will cut off the output.
5. Operating Instructions
5.1 Power ON/OFF
Once the unit has been properly installed and the batteries are connected well, simply press the On/Off switch (located on the button of the case) to turn on the unit.
5.2 Operation and Display Panel
The operation and display panel, shown below, is on the front panel of the inverter. It includes three indicators, four function keys and an LCD display, indicating the operating status and input/output power information.
| LED Indicator | Messages |
|---|---|
| INV/AC (Green, Solid On) | Output is powered by utility in Line mode. |
| INV/AC (Green, Flashing) | Output is powered by battery or PV in battery mode. |
| CHG (Green, Solid On) | Battery is fully charged. |
| CHG (Green, Flashing) | Battery is charging. |
| FAULT (Red, Solid On) | Fault occurs in the inverter. |
| FAULT (Red, Flashing) | Warning condition occurs in the inverter. |
| Function Key | Description |
|---|---|
| ESC | To exit setting mode |
| UP | To go to previous selection |
| DOWN | To go to next selection |
| ENTER | To confirm the selection in setting mode or enter setting mode |
5.3 LCD Display Icons
| Icon | Function description |
|---|---|
| AC Input Icon | Indicates the AC input. |
| PV Input Icon | Indicates the PV input. |
| Input Voltage/Frequency/PV Voltage/Charger Current/Power/Battery Voltage Display | Indicate input voltage, input frequency, PV voltage, charger current (if PV in charging for 10.2KW models), charger power, battery voltage. |
| Setting Programs Icon | Indicates the setting programs. |
| Warning/Fault Codes Icon | Indicates the warning and fault codes. |
| Output Voltage/Frequency/Load Percent/Load in VA/Load in Watt/Discharging Current Display | Indicate output voltage, output frequency, load percent, load in VA, load in Watt and discharging current. |
| Overload Icon | Indicates overload. |
| Mains Connection Icon | Indicates unit connects to the mains. |
| PV Panel Connection Icon | Indicates unit connects to the PV panel. |
| AC Bypass Icon | Indicates load is supplied by utility power. |
| Utility Charger Circuit Icon | Indicates the utility charger circuit is working. |
| DC/AC Inverter Circuit Icon | Indicates the DC/AC inverter circuit is working. |
| Mute Icon | Indicates unit alarm is disabled. |
5.4 LCD Setting
After pressing and holding the ENTER button for 3 seconds, the unit will enter setting mode. Press "UP" or "DOWN" button to select setting programs. And then, press "ENTER" button to confirm the selection or ESC button to exit.
| Program | Description | Selectable option (Default) | Notes |
|---|---|---|---|
| 00 | Exit setting mode | 00 GOE, 00 GOH | One-button restore setting options. |
| 01 | Output source priority | Utility first (01 USb), Solar first (01 SOb), SBU priority (01 SBU), MKS priority (01 ntS) | Configures the priority of power sources (Utility, Solar, Battery) for loads. |
| 02 | Maximum charging current | 10A to 160A (e.g., 02 160 for 160A) | Configures total charging current from solar and utility chargers. |
| 03 | AC input voltage range | Appliances (03 APL), UPS (03 UPS) | Sets acceptable AC input voltage range (90-280VAC for Appliances, 170-280VAC for UPS). |
| 05 | Battery type | AGM (05 AGn), Flooded (05 FLd), User-Defined (05 USE), LIB-485 (05 L I b) | Selects the battery type. For Lithium batteries, choose LIB-485. |
| 06 | Auto restart when overload occurs | Restart disable (06 LFd), Restart enable (06 LYE) | Enables or disables automatic restart after an overload. |
| 07 | Auto restart when over temperature occurs | Restart disable (07 Erd), Restart enable (07 EYE) | Enables or disables automatic restart after an over temperature event. |
| 09 | Output frequency | 50Hz (09 50), 60Hz (09 60) | Sets the output frequency. |
| 10 | Output voltage | 220V (10 220), 230V (10 230), 240V (10 240) | Sets the output voltage. |
| 11 | Maximum utility charging current | 2A to 140A (e.g., 11 140 for 140A) | Sets the maximum charging current from the utility. |
| 12 | Battery SOC point for switching to utility source (SBU mode) | 10% to 50% (Default: 50%) | When SBU mode is selected, sets the battery SOC threshold for switching to utility. |
| 13 | Battery SOC point for switching to battery mode (SBU mode) | 30% to 100% (Default: 95%) | When SBU mode is selected, sets the battery SOC threshold for switching to battery. |
| 16 | Charger source priority | Solar first (16 CSO), Solar and Utility (16 SNU), Only Solar (16 OSO) | Configures the priority of charging sources. |
| 18 | Alarm control | Alarm on (18 OON), Alarm off (18 OOF) | Enables or disables audible alarms. |
| 19 | Auto return to default display screen | Return to default (19 ESP), Stay at latest (19 HEP) | Sets display behavior after inactivity. |
| 20 | Backlight control | Backlight on (20 LON), Backlight off (20 LOF) | Enables or disables LCD backlight. |
| 22 | Beeps while primary source is interrupted | Alarm on (22 AON), Alarm off (22 AOF) | Enables or disables beeping when power source changes. |
| 23 | Overload bypass | Bypass disable (23 BYd), Bypass enable (23 BYE) | When enabled, unit transfers to line mode if overload occurs in battery mode. |
| 25 | Record Fault code | Record enable (25 FEN), Record disable (25 FdS) | Enables or disables fault code recording. |
| 26 | Bulk charging voltage (C.V voltage) | Default: 56.4V. Range: 48.0V to 61.0V. | Sets the bulk charging voltage. Increment of 0.1V. |
| 27 | Floating charging voltage | Default: 54.0V. Range: 48.0V to 61.0V. | Sets the floating charging voltage. Increment of 0.1V. |
| 29 | Low DC cut-off voltage | Default: 40.0V. Range: 40.0V to 48.0V. | Sets the low DC cut-off voltage. Increment of 0.1V. If LIB-485 is selected, this is the battery low SOC shutdown point (20%, range 5-30%). |
| 30 | Battery equalization | Enable (30 EEn), Disable (30 EdS) | Enables or disables battery equalization. |
| 31 | Battery equalization voltage | Default: 58.4V. Range: 48.0V to 61.0V. | Sets the battery equalization voltage. Increment of 0.1V. |
| 33 | Battery equalized time | Default: 60min. Range: 5min to 900min. | Sets the duration of battery equalization. Increment of 5min. |
| 34 | Battery equalized timeout | Default: 120min. Range: 5min to 900min. | Sets the timeout for battery equalization. Increment of 5min. |
| 35 | Equalization interval | Default: 30 days. Range: 0 to 90 days. | Sets the interval between equalization cycles. Increment of 1 day. |
| 36 | Equalization activated immediately | Enable (36 AEn), Disable (36 AdS) | Activates or cancels equalization immediately. |
| 37 | GRID-tie operation | Off grid (37 OFF), Hybrid (37 HYd) | Sets inverter operation mode (off-grid or hybrid). |
| 38 | GRID-tie current | 10A (38 10) | Sets the GRID-tie current. Increment of 2A. |
| 39 | Led pattern light | Led pattern off (39 LOF), Led pattern on (39 LON) | Controls the LED pattern light. |
| 41 | Dual output | Disable (41 L2F), Use (41 L20) | Enables or disables the dual output function. |
| 42 | Enter the dual output functional voltage point | Default: 44.0V. Range: 40.0V to 52.0V. | Sets the voltage point for dual output function. Increment of 0.1V. |
| 43 | Lithium battery protocol | PYLON (43 PYL), PACE (43 PAC) | Selects the specific Lithium battery protocol. |
| 44 | Delayed grid access | Disable (44 dIS), Enable (44 ENA) | Enables or disables delayed grid access. |
| 45 | Maximum Second Load | 20%~70% | If dual output is enabled, the second channel output power can be changed to 20%~70% of rated power. |
5.5 Display Setting
The LCD display information will be switched in turns by pressing “UP” or “DOWN" key. The selectable information is switched as below order: input voltage, input frequency, PV voltage, charging current, charging power, battery voltage, output voltage, output frequency, load percentage, load in Watt, load in VA, load in Watt, DC discharging current, main CPU Version.
5.6 Operating Mode Description
RGB Light (option)
- Battery Mode: Red Light
- Utility Mode: Blue Light
- PV Mode: Purple Light
5.7 Battery Equalization Description
Equalization function is added into charge controller. It reverses the buildup of negative chemical effects like stratification, a condition where acid concentration is greater at the bottom of the battery than at the top. Equalization also helps to remove sulfate crystals that might have built up on the plates. If left unchecked, this condition, called sulfation, will reduce the overall capacity of the battery. Therefore, it's recommended to equalize battery periodically.
How to Apply Equalization Function
You must enable battery equalization function in monitoring LCD setting program 30 first. Then, you may apply this function in device by either one of following methods:
- Setting equalization interval in program 35.
- Active equalization immediately in program 36.
When to Equalize
In float stage, when the setting equalization interval (battery equalization cycle) is arrived, or equalization is active immediately, the controller will start to enter Equalize stage.
Equalize charging time and timeout
In Equalize stage, the controller will supply power to charge battery as much as possible until battery voltage raises to battery equalization voltage. Then, constant-voltage regulation is applied to maintain battery voltage at the battery equalization voltage. The battery will remain in the Equalize stage until setting battery equalized time is arrived. However, in Equalize stage, when battery equalized time is expired and battery voltage doesn't rise to battery equalization voltage point, the charge controller will extend the battery equalized time until battery voltage achieves battery equalization voltage. If battery voltage is still lower than battery equalization voltage when battery equalized timeout setting is over, the charge controller will stop equalization and return to float stage.
5.8 Mains and Lithium Battery Activation Function
- After 90s of mains power connection to the inverter, the machine is connected to the mains and starts to work.
- The inverter is in lithium battery mode (item 05 is LIP or LIL). After the mains is connected, the battery is not connected, and the mains activation function is automatically enabled.
6. Clearance and Maintenance for Anti-Dust Kit
6.1 Overview
Every inverter is already installed with an anti-dust kit from the factory. The inverter will automatically detect this kit and activate an internal thermal sensor to adjust the internal temperature. This kit also keeps dust from your inverter and increases product reliability in harsh environments.
6.2 Clearance and Maintenance
Step 1: Please loosen the screw in the counterclockwise direction on the top of the inverter.
Step 2: Then, the dustproof case can be removed, and the air filter foam can be taken out.
Step 3: Clean the air filter foam and dustproof case. After clearance, re-assemble the dust-kit back to the inverter.
NOTICE: The anti-dust kit should be cleaned from dust every one month.
7. Specifications
| INVERTER MODEL | 8.2KW | 10.2KW |
|---|---|---|
| Input Voltage Waveform | Pure Sine Wave (Utility or Generator) | |
| Nominal Input Voltage | 230Vac | |
| Low Loss Voltage | 170Vac±7V (UPS); 90Vac±7V (Appliances) | |
| Low Loss Return Voltage | 180Vac±7V (UPS); 100Vac±7V (Appliances) | |
| High Loss Voltage | 280Vac±7V | |
| High Loss Return Voltage | 270Vac±7V | |
| Max AC Input Voltage | 300Vac | |
| Nominal Input Frequency | 50Hz / 60Hz (Auto detection) | |
| Low Loss Frequency | 40±1Hz | |
| Low Loss Return Frequency | 42±1Hz | |
| High Loss Frequency | 65±1Hz | |
| High Loss Return Frequency | 63±1Hz | |
| Output Short Circuit Protection | Circuit Breaker | |
| Efficiency (Line Mode) | >95% (Rated R load, battery full charged) | |
| Transfer Time | 10ms typical (UPS); 20ms typical (Appliances) | |
| INVERTER MODEL | 8.2KW | 10.2KW |
|---|---|---|
| Rated Output Power | 8.2KW | 10.2KW |
| Output Voltage Waveform | Pure Sine Wave | |
| Output Voltage Regulation | 230Vac±5% | |
| Output Frequency | 50Hz/60Hz | |
| Peak Efficiency | 0.93 | |
| Overload Protection | 3s@≥150% load; 5s@101%~150% load | |
| Surge Capacity | 2* rated power for 5 seconds | |
| Nominal DC Input Voltage | 48Vdc | |
| Cold Start Voltage | 46.0Vdc | |
| Low DC Warning Voltage @load < 50% | 44.0Vdc | |
| Low DC Warning Voltage @load ≥ 50% | 42.0Vdc | |
| Low DC Warning Return Voltage @load < 50% | 45.0Vdc | |
| Low DC Warning Return Voltage @load ≥ 50% | 44.0Vdc | |
| Low DC Cut-off Voltage @load < 50% | 41.0Vdc | |
| Low DC Cut-off Voltage @load ≥ 50% | 40.0Vdc | |
| High DC Recovery Voltage | 62Vdc | |
| High DC Cut-off Voltage | 63Vdc | |
| No Load Power Consumption | 70W | 75W |
| INVERTER MODEL | 8.2KW | 10.2KW |
|---|---|---|
| Full Load | 8200W | 10200W |
| Maximum Main Load | 8200W | 10200W |
| Maximum Second Load (battery model) | 2733W | 3400W |
| Main Load Cut Off Voltage | 44VDC | |
| Main Load Return Voltage | 54VDC | |
| INVERTER MODEL | 8.2KW | 10.2KW |
|---|---|---|
| Utility Charging Mode | ||
| Charging Algorithm | 3-Step | |
| AC Charging Current (Max) | 140Amp | 140Amp |
| Bulk Charging Flooded Battery Voltage | 58.4 | |
| Bulk Charging AGM / Gel Battery Voltage | 56.4 | |
| Floating Charging Voltage | 54Vdc | |
| MPPT Solar Charging Mode | ||
| Max. PV Array Power | PV1 Channel: 5400W, PV2 Channel: 5400W | PV1 Channel: 5400W, PV2 Channel: 5400W |
| IMax.PV | PV1 Channel: 18A, PV2 Channel: 18A | PV1 Channel: 18A, PV2 Channel: 18A |
| Nominal PV Voltage | 360Vdc | |
| PV Array MPPT Voltage Range | 90Vdc~500Vdc | |
| Max. PV Array Open Circuit Voltage | 500Vdc | |
| Max Charging Current (AC charger plus solar charger) | 160Amp | |
| INVERTER MODEL | 8.2KW | 10.2KW |
|---|---|---|
| Nominal Output Voltage | 220/230/240 VAC | |
| Feed-in Grid Voltage Range | 195~253VAC | |
| Feed-in Grid Frequency Range | 50±1Hz/60±1Hz | |
| Nominal Output Current | 35.6A | 44.3A |
| Power Factor Range | >0.99 | |
| Maximum Conversion Efficiency (DC/AC) | 98% | |
| INVERTER MODEL | 8.2KW | 10.2KW |
|---|---|---|
| Safety Certification | CE | |
| Operating Temperature Range | -10°C to 50°C | |
| Storage temperature | -15°C~60°C | |
| Humidity | 5% to 95% Relative Humidity (Non-condensing) | |
| Dimension (D*W*H), mm | 500*390*136mm | |
| Net Weight, kg | 14.5 | 14.7 |
| Model | Load (W) | Backup Time @ 48Vdc 100Ah (min) | Backup Time @ 48Vdc 200Ah (min) |
|---|---|---|---|
| 8.2KW/10.2KW | 500 | 613 | 1288 |
| 1000 | 268 | 613 | |
| 1500 | 158 | 402 | |
| 2000 | 111 | 271 | |
| 2500 | 90 | 215 | |
| 3200 | 76 | 182 | |
| 3500 | 65 | 141 | |
| 4000 | 50 | 112 | |
| 4500 | 44 | 100 | |
| 5000 | 40 | 90 | |
| 6200 | 36 | 80 | |
| 7200 | 32 | 70 | |
| 8200 | 28 | 60 | |
| 9200 | 24 | 50 | |
| 10200 | 20 | 40 |
Note:
- Backup time depends on the quality of the battery, age of battery and type of battery. Specifications of batteries may vary depending on different manufacturers.
- The final interpretation right of this product belongs to the company.
8. Troubleshooting
5.9 Fault Reference Code
| Fault Code | Fault Event | Icon on |
|---|---|---|
| 01 | Fan is locked when inverter is off. | 01 ERROR |
| 02 | Over temperature | 02 ERROR |
| 03 | Battery voltage is too high | 03 ERROR |
| 04 | Battery voltage is too low | 04 ERROR |
| 05 | Output short circuited or over temperature is detected by internal converter components. | 05 ERROR |
| 06 | Output voltage is too high. | 06 ERROR |
| 07 | Overload time out | 07 ERROR |
| 08 | Bus voltage is too high | 08 ERROR |
| 09 | Bus soft start failed | 09 ERROR |
| 51 | Over current or surge | 51 ERROR |
| 52 | Bus voltage is too low | 52 ERROR |
| 53 | Inverter soft start failed | 53 ERROR |
| 55 | Over DC voltage in AC output | 55 ERROR |
| 57 | Current sensor failed | 57 ERROR |
| 58 | Output voltage is too low | 58 ERROR |
| 59 | PV voltage is over limitation | 59 ERROR |
| Fault code | Fault event | Fault condition |
|---|---|---|
| 02 | The battery temperature is too high Procedure | Lithium battery charging battery temperature ≥65°C; The discharge temperature of the lithium battery is higher than 70°C. |
| 03 | The battery voltage is too high Procedure | Lithium battery maximum single cell voltage >3.65V; Total voltage of lithium battery >54.6V (48V lithium battery). |
| 04 | The battery voltage is too low Procedure | Minimum voltage of a lithium battery cell<2.71V; Lithium battery total voltage<40.4V (48V lithium battery). |
5.10 Warning Indicator
| Warning Code | Warning Event | Audible Alarm | Icon flashing |
|---|---|---|---|
| 01 | Fan is locked when inverter is on. | Beep three times every second | 01 |
| 03 | Battery is over-charged | Beep once every second | 03 |
| 04 | Low battery | Beep once every second | 04 |
| 07 | Overload | Beep once every 0.5 second | 07 |
| 10 | Output power derating | Beep twice every 3 seconds | 10 |
| 15 | PV energy is low. | Beep twice every 3 seconds | 15 |
| E9 | Battery equalization | None | E9 |
| 6P | Battery is not connected | None | 6P |
| Warning code | Warning event | Warning condition |
|---|---|---|
| 04 | The battery voltage is too low | Minimum voltage of a lithium battery cell<2.85V; Lithium battery total voltage<42V (48V lithium battery). |
| 05 | The battery voltage is too high | Lithium battery maximum single cell voltage >3.55V; Total voltage of lithium battery >54V (48V lithium battery). |
| 06 | The battery is low warning | Remaining battery capacity ≤10% |
Troubleshooting Table
| Problem | LCD/LED/Buzzer | Explanation / Possible cause | What to do |
|---|---|---|---|
| Unit shuts down automatically during startup process. | LCD/LEDs and buzzer will be active for 3 seconds and then complete off. | The battery voltage is too low (<1.91V/Cell) | 1. Re-charge battery. 2. Replace battery. |
| No response after power on. | No indication. | 1. The battery voltage is far too low. (<1.4V/Cell) 2. Internal fuse tripped. | 1. Contact repair center for replacing the fuse. 2. Re-charge battery. 3. Replace battery. |
| Input voltage is displayed as 0 on the LCD and green LED is flashing. | Input protector is tripped | Check if AC breaker is tripped and AC wiring is connected well. | |
| Mains exist but the unit works in battery mode. | Green LED is flashing. | Insufficient quality of AC power. (Shore or Generator) | 1. Check if AC wires are too thin and/or too long. 2. Check if generator (if applied) is working well or if input voltage range setting is correct. (UPS/Appliances) |
| Green LED is flashing. | Set "Solar First" as the priority of output source. | Change output source priority to Utility first. | |
| When the unit is turned on, internal relay is switched on and off repeatedly. | LCD display and LEDs are flashing | Battery is disconnected. | Check if battery wires are connected well. |
| Fault code 07 | Overload error. The inverter is overload 110% and time is up. | Reduce the connected load by switching off some equipment. | |
| Fault code 05 | Output short circuited. | Check if wiring is connected well and remove abnormal load. | |
| Fault code 02 | Temperature of internal converter component is over 120°C. Internal temperature of inverter component is over 100°C. | Check whether the air flow of the unit is blocked or whether the ambient temperature is too high. | |
| Buzzer beeps continuously and red LED is on. | Fault code 03 | Battery is over-charged. The battery voltage is too high. | Return to repair center. Check if spec and quantity of batteries are meet requirements. |
| Fault code 01 | Fan fault | Replace the fan. | |
| Fault code 06/58 | Output abnormal (Inverter voltage below than 190Vac or is higher than 260Vac) | 1. Reduce the connected load. 2. Return to repair center. | |
| Fault code 08/09/53/57 | Internal components failed. | Return to repair center. | |
| Fault code 51 | Over current or surge. | Restart the unit, if the error happens again, please return to repair center. | |
| Fault code 52 | Bus voltage is too low. | Restart the unit, if the error happens again, please return to repair center. | |
| Fault code 55 | Output voltage is unbalanced. | Restart the unit, if the error happens again, please return to repair center. |
9. User Tips
- Battery Compatibility: This inverter supports a wide range of battery types including Lifepo4, Lithium, Flooded, Gel, and Lead-acid Batteries. Ensure you select the correct battery type in the LCD settings (Program 05) for optimal performance and safety.
- Smart Device Integration: The inverter is a smart device, offering WIFI and GPRS communication for monitoring via iOS and Android apps. Utilize these features for remote monitoring and control.
- Output Frequency: The inverter supports both 50Hz and 60Hz output frequencies. Configure this setting (Program 09) to match your local grid requirements.
- Geographic Applicability: This product is designed for use in various regions including Asia, Europe, Africa, and North America, supporting 220-240VAC drivers.
- Single-Phase Operation: This inverter is a single-phase unit. It cannot be directly combined with other units to create a 3-phase (400V) application. For 3-phase systems, specialized inverters are required.
- Wind Generator Compatibility: While the inverter supports general 'Generator' input, specific compatibility with wind generators may depend on the wind generator's output characteristics. Consult with a solar professional for integration with wind power systems.
10. Frequently Asked Questions (FAQ)
- Q: Does it come with a built-in battery?
- A: No, the inverter does not come with a built-in battery. It supports external 48V batteries (Lifepo4, Lithium, Flooded, Gel, Lead-acid). It does, however, have a built-in Lithium battery automatic activation feature.
- Q: What's the maximum power this item can handle?
- A: The rated output power of the 10.2KW model is 10200W.
- Q: Is this item smart device compatible?
- A: Yes, it is a smart device with WIFI & GPRS available for iOS and Android monitoring.
- Q: What types of batteries does it support?
- A: It supports Lifepo4, Lithium, Flooded, Gel, and Lead-acid Batteries.
- Q: What are the available output frequencies?
- A: The output frequency is configurable to either 50HZ or 60HZ.
- Q: Where can I use this product?
- A: It is applicable in Asia, Europe, Africa, and North America (with 220-240VAC drivers).
11. Warranty and Support
For technical support or warranty inquiries, please contact PowMr directly using the information below:
SHENZHEN HEHEJIN INDUSTRIAL CO.,LTDTel/Fax: +86 755-28219903
Email: support@powmr.com
Web: www.powmr.com
Address: Henggang Street, Longgang District, Shenzhen, Guangdong, China
For additional resources, including video guides, please visit the official PowMr Solar YouTube channel:
A PDF version of the user manual is also available for download: User manual (PDF)