LILYTECH ZL-7918C Incubator Controller User Manual

Intelligent Temperature and Humidity Controller

1. Introduction

The LILYTECH ZL-7918C is an intelligent temperature and humidity controller designed for incubators, climate chambers, warehouses, and similar applications. It offers stable and reliable performance with convenient operation, supporting both Fahrenheit and Celsius temperature units, ventilation fan control, and lamp control based on door status.

Front view of the LILYTECH ZL-7918C Incubator Controller with digital displays
LILYTECH ZL-7918C Controller Front Panel

2. Specifications

FeatureDescription
Power Supply100 ~ 240Vac, 50/60Hz
Inputs1 Temperature Sensor (L=2.0m), 1 Humidity Sensor (L=2.0m), 1 Door Switch
Setting Range (Humidity)10 ~ 99%RH
Setting Range (Temperature)1 ~ 75℃ (34.0 ~ 167.0°F)
Display Range (Humidity)0 ~ 99%RH
Display Range (Temperature)-9.9 ~ 99.9℃ (14.0 ~ 212.0°F)
Measuring Accuracy (Humidity)3% @ 25°C
Measuring Accuracy (Temperature)1% @ 25°C
Outputs8 outputs (Main-Heater, Aux-Heater, Lamp, Humidity, Ventilation Fan, Right-Turning, Left-Turning, Exhaustion Fan)
Output Load (Main-Heater)≤ 1500W
Output Load (Aux-Heater)≤ 1500W
Output Load (Lamp)≤ 100W
Output Load (Others)≤ 1A/250Vac
Hatched Day CounterMax 99 days
Egg Turn Control (Period)1 ~ 999 minutes
Egg Turn Control (Driving Time)0 ~ 999 seconds
Egg Turn Control (Times Counter)0 ~ 999 times
Air Exhaustion Control (Period)1 ~ 999 minutes
Air Exhaustion Control (Exhausting Time)0 ~ 999 seconds
Lamp Control (Period)1 ~ 999 minutes
Lamp Control (Illuminating Time)1 ~ 999 seconds
Operation Environment-10 ~ 45℃, <90% RH (non-condensing)
Device Dimensions160 * 80 * 95 mm
Installation Drilling Size151.5 * 76.5 mm

Firmware Information

When the controller is powered on, the display will show the model "7918C" and its version, e.g., "A1.0".

3. Product Overview

The ZL-7918C controller features a clear digital display for temperature (TEMP PV), humidity (WET PV), and set values (SV). It includes buttons for 'Set', 'Up', 'Down', and 'Enter' (Lamp I/O).

Angled view of the LILYTECH ZL-7918C controller showing its display and buttons
ZL-7918C Controller

The back panel provides clearly labeled terminal blocks for all connections, including power, sensors, and output loads.

Side view of the LILYTECH ZL-7918C controller showing the terminal block with labels
ZL-7918C Terminal Block

The controller comes with a dedicated humidity sensor, model ZL-SHr05A, which measures humidity in the range of 0-80%RH.

Close-up of the ZL-SHr05A humidity sensor with its cable
ZL-SHr05A Humidity Sensor

4. Setup and Wiring

4.1 Installation

The ZL-7918C requires an installation drilling size of 151.5 mm x 76.5 mm for panel mounting.

4.2 Wiring Diagrams

Carefully follow the wiring diagrams below for proper connection of power, sensors, and output loads. Ensure all connections are secure and correct to prevent damage to the unit or connected devices.

Wiring diagram for ZL-7918C with AC220V egg-turning motor, showing connections for power, temperature sensor, humidity sensor, door switch, two heaters, humidifier, lamp, circulation fan, exhaust fan, and left/right egg turning motors.
Wiring Diagram: AC220V Egg-Turning Motor
Wiring diagram for ZL-7918C with DC12V/24V egg-turning motor, showing connections for power, temperature sensor, humidity sensor, door switch, two heaters, humidifier, lamp, circulation fan, exhaust fan, and left/right DC egg turning motors.
Wiring Diagram: DC12V/24V Egg-Turning Motor

4.3 Sensor Connection

Connect the temperature sensor, humidity sensor, and door switch to their designated terminals on the controller. Refer to the wiring diagrams for precise terminal assignments.

5. Operation

5.1 Setting Parameters

Set Temperature and Humidity Setpoint (P3, P9)

  1. Press and hold the Set button for 2 seconds to enter the setpoint setting status.
  2. The SV window will display "****" + "tt" for temperature setting or "****" + "HH" for humidity setting.
  3. Press the Enter button to switch between temperature and humidity setpoint.
  4. Use the ▲ (Up) or ▼ (Down) buttons to adjust the desired setpoint value. Holding the button will fast-set the value.
  5. Press and hold the Enter button for 2 seconds to save settings and exit. The controller will automatically generate P- parameters.
  6. If no key operation occurs for 15 seconds, the setting status will exit without saving.

Default Temperature Setpoint (P3): 37.8°C (Range: 1 ~ 75°C)

Default Humidity Setpoint (P9): 60%RH (Range: 0 ~ 99%RH)

Set Temperature and Humidity Control Parameters (P-)

Note: Setting these parameters will override automatically generated values.

  1. Press Set and ▲ simultaneously to enter the P- parameter setting status.
  2. Press Enter to select parameters from P0 to Pt.
  3. Use the ▲ (Up) or ▼ (Down) buttons to adjust the parameter value.
  4. Press and hold the Enter button for 2 seconds to save settings and exit.
  5. If no key operation occurs for 15 seconds, the setting status will exit without saving.

Set Function Control Parameters (F-)

  1. Press Set and ▼ simultaneously to enter the F- parameter setting status.
  2. Press Enter to select parameters from F1 to FB.
  3. Use the ▲ (Up) or ▼ (Down) buttons to adjust the parameter value.
  4. Press and hold the Enter button for 2 seconds to save settings and exit.
  5. If no key operation occurs for 15 seconds, the setting status will exit without saving.

5.2 Control Functions

On/Off Operation

Press and hold the Lamp I/O button for 2 seconds to switch the controller between online and offline modes.

Illumination Operation

  • Manual Control: Press Lamp I/O to turn the lamp on for the duration set by F9 (Illumination time). Press again to turn off.

  • Timer Control: The lamp will turn off for every Illumination period (F8), then turn on for Illumination time (F9).

Lamp Control According to Door Status (FR=1)

If Door control function (FR) is set to 1, the lamp will turn on for Illumination time (F9) when the door opens and turn off when the door closes.

Temperature Control

  • Main Heater: Activates when room temperature ≤ P4 (Main temperature low limit) and deactivates when room temperature ≥ P3 (Main temperature up limit).

  • Auxiliary Heater: Activates when room temperature ≤ P6 (Aux temperature low limit) and deactivates when room temperature ≥ P5 (Aux temperature up limit).

  • Exhaustion Fan: Activates when room temperature ≥ P1 (Exhaustion temperature up limit) and deactivates when room temperature ≤ P2 (Exhaustion temperature low limit).

  • If Door control function (FR) = 1, all temperature outputs will be off when the door opens. Control resumes when the door closes.

Humidity Control

  • Humidifier: Activates when room humidity ≤ Pb (Humidity low limit) and deactivates when room humidity ≥ P9 (Humidity up limit).

  • Exhaustion Fan (Over Wet Exhaustion Protection PE=1): Activates when room humidity ≥ Pc (Exhaustion humidity up limit) and deactivates when room humidity ≤ Pd (Exhaustion humidity low limit).

  • If Door control function (FR) = 1, the humidity output will be off when the door opens. Control resumes when the door closes.

Ventilation Fan Control

The ventilation fan is on when the controller is online and off when offline. If Door control function (FR) = 1, the fan stops when the door opens and resumes when the door closes.

Egg Turn Control

  • Timer Egg Turning: For every F1 (Egg turn period), the egg turn output will activate for F2 (Egg turn time). Left and right turns alternate. Each full egg turn (1 left + 1 right) increments the egg turned counter (FM). When FM reaches F3 (Egg turn times), egg turning stops, and "UP" and "DOWN" indicators will blink.

  • Manual Egg Turning: Can be operated both online and offline. Hold ▲ to force left turning. Hold ▼ to force right turning.

  • Egg Turning Status Saving (Ft=1): The controller saves the egg tray period status every 3 minutes. If power is lost during egg turning, it will resume after power is restored.

Fast Check Incubated Days (FF) and Egg Turned Counter (FM)

To quickly check these values:

  • Press Enter and ▲ simultaneously: SV window displays Incubated days (FF) as "days: hours" + "t1" for 2 seconds.
  • Press Enter and ▼ simultaneously: SV window displays Egg turned counter (FM) as "times" + "t2" for 2 seconds.

Reset Egg Turned Counter (FM)

If FE (Egg turned counter reset) is 0, FM will reset to zero after power is supplied or the unit is turned offline. If FE is 1, FM will retain its value. You can also manually set it to zero.

6. Maintenance

6.1 Humidity Sensor Care

The humidity sensor is sensitive to dust, water, and dew. To ensure accurate readings and proper function, keep the sensor clean and dry. Before cleaning, ensure there is no static electricity in your hands.

6.2 Calibration

The temperature and humidity sensors have inherent tolerances. You can calibrate them for improved accuracy:

  • Temperature Calibration: Adjust parameter F6.
  • Humidity Calibration: Adjust parameter F7.

7. Troubleshooting

7.1 Warning Codes

CodeIndication
E1Temperature sensor failure
E2Humidity sensor failure
E3High temperature alarm
E4Low temperature alarm
E5High humidity alarm
E6Low humidity alarm
doorDoor opening alarm

7.2 Temperature and Humidity Alarms

The controller will buzz and display values will blink under the following conditions:

  • Room temperature ≥ P0 (High temperature warning point)
  • Room temperature ≤ P7 (Low temperature warning point)
  • Room humidity ≥ P8 (High humidity warning point)
  • Room humidity ≤ PP (Low humidity warning point)

During an alarm, pressing Enter can stop/restore the buzzing.

7.3 LED Indication

LEDOnBlinkingOff
FANFan on during Air exhausting time (F5)Fan on, because of temperature and humidity protection exhaustionFan off
HEAT1Main heater onMain heater off
HEAT2Aux. heater onAux. heater off
UPEgg left turning nowEgg turned counter (FM) reaches Egg turn times (F3)No left turning
DOWNEgg right turning nowEgg turned counter (FM) reaches Egg turn times (F3)No right turning
WETHumidifying output onHumidify output off
ALARMRoom temperature or humidity is over warning points, or sensor fails

7.4 Restore to Factory Settings

To restore the controller to its default factory settings:

  1. Press and hold the ▲ (Up) and ▼ (Down) buttons simultaneously for 2 seconds.
  2. The SV window will display "0000" + "00".
  3. Press the Lamp I/O button twice. The buzzer will beep, indicating that the controller has been restored to factory defaults.

8. User Tips

  • Sensor Placement: Ensure both temperature and humidity sensors are placed in a location that accurately reflects the conditions within your incubator, away from direct heat sources or airflow.
  • Humidity Sensor Maintenance: Regularly check and clean the humidity sensor to prevent dust or moisture buildup, which can affect its accuracy. Always handle with care to avoid static discharge.
  • Parameter Review: Before starting a new incubation cycle, always review and adjust all P- and F- parameters to match the specific requirements of the eggs or environment.
  • PDF Manual: For more detailed information, including comprehensive parameter tables and advanced settings, please refer to the official PDF manual available at: https://www.suzhoulily.com.cn/doc/ZL-7918C/ZL-7918C_en_V1.0.pdf

9. Warranty and Support

The manufacturer is responsible for the device itself. For any issues or malfunctions, please contact LILYTECH Official Store for support. It is important to note that the manufacturer is not responsible for losses resulting from the failure of this device if not used as intended or if modifications are made.