GEYA GYR9NM-RCBO Type A

Contents

GEYA GYR9NM Type A RCBO Instruction Manual

Residual Current Circuit Breaker with Over-current Protection

1. Introduction

The GEYA GYR9NM Series RCBO (Residual Current Circuit Breaker with Over-current Protection) is designed for lines with AC 50Hz or 60Hz, a rated voltage of 240V, and rated currents up to 40A. This device integrates leakage, overload, and short-circuit protection functions into a single unit, ensuring comprehensive electrical safety.

It is crucial for protecting personal safety by cutting off fault currents within 0.1 seconds when personal contact or grid leakage current exceeds specified values. Additionally, it safeguards equipment from failures caused by leakage currents and protects lines from overload and short-circuit conditions. The RCBO can also be used for infrequent breaking and switching of lines under normal conditions, primarily in building lighting and power distribution systems.

Product Overview

Front view of GEYA GYR9NM 2-pole Type A RCBO

Figure 1: Front view of GEYA GYR9NM 2-pole Type A RCBO

Front view of GEYA GYR9NM 4-pole Type A RCBO

Figure 2: Front view of GEYA GYR9NM 4-pole Type A RCBO

2. Safety Information

Always observe standard electrical safety precautions when installing or working with this device. Installation should only be performed by qualified personnel. Ensure the power supply is disconnected before any installation or maintenance work.

  • Do not operate the device with wet hands.
  • Ensure proper grounding according to local electrical codes.
  • Verify correct wiring connections to prevent damage to the device or electrical system.
  • Do not bypass or tamper with the protective functions of the RCBO.

3. Setup & Installation

3.1 Mounting

The GEYA GYR9NM RCBO is designed for DIN rail mounting (EN/IEC 60715 standard). Ensure the DIN rail is securely installed in the distribution box.

3.2 Wiring

Connect the electrical wires to the terminals as shown in the wiring diagrams below. Ensure all connections are tight to prevent loose contacts and overheating. The recommended tightening torque for terminals is 2.5 Nm.

  • Max. Connection Capacity (Hard Wire): 25mm²
  • Max. Connection Capacity (Flexible Wire): 16mm²
  • Incoming Method: Upward incoming line.

Wiring Diagrams

Wiring diagram for 2-pole and 4-pole GEYA GYR9NM RCBO

Figure 3: Wiring Diagram for 2-pole and 4-pole RCBO

Dimensions

Dimensions in mm for 2-pole GEYA GYR9NM RCBO

Figure 4: Dimensions (mm) for 2-pole RCBO

Dimensions in mm for 4-pole GEYA GYR9NM RCBO

Figure 5: Dimensions (mm) for 4-pole RCBO

4. Operating Instructions

4.1 Basic Operation

To turn the circuit ON, push the handle upwards. To turn the circuit OFF, push the handle downwards.

4.2 Protection Functions

  • Leakage Protection: Detects residual currents (earth faults) and trips the circuit to prevent electric shock.
  • Overload Protection: Trips the circuit when the current exceeds the rated current for a prolonged period, preventing overheating of wires and equipment.
  • Short Circuit Protection: Instantly trips the circuit in case of a short circuit, protecting the electrical system from severe damage.

4.3 Trip Indications

The RCBO provides visual cues to help diagnose the cause of a trip:

  • If all handles are in the OFF position: This indicates the presence of a residual current (earth fault).
  • If only the left handle is in the OFF position: This suggests an MCB (Miniature Circuit Breaker) failure or an internal fault within the device itself.

5. Maintenance

The GEYA GYR9NM RCBO is designed for long-term reliability with minimal maintenance. However, periodic checks are recommended to ensure optimal performance and safety.

  • Mechanical Life: 10,000 operations.
  • Electrical Life: 4,000 operations.
  • Operating Temperature: -5°C to +40°C (with daily average ≤ 35°C).
  • Storage Temperature: -25°C to +70°C.
  • Protection Degree: IP20 (Direct install), IP40 (Installed in distribution box).
  • Regularly inspect the device for any visible damage, discoloration, or loose connections.
  • Test the RCBO periodically using the integrated test button (if available) to ensure the residual current protection mechanism is functioning correctly.

6. Troubleshooting

If the RCBO trips, follow these steps to identify and resolve the issue:

  1. Identify Trip Cause: Observe the position of the handles to determine if it was a residual current fault or an MCB failure (as described in Section 4.3).
  2. Residual Current Fault (All handles OFF):
    • Disconnect all loads from the circuit protected by the RCBO.
    • Attempt to reset the RCBO. If it holds, reconnect loads one by one to identify the faulty appliance or wiring.
    • If the RCBO trips immediately without loads, inspect the wiring for insulation damage or moisture.
  3. MCB Failure (Only left handle OFF):
    • This indicates an overload or short circuit. Disconnect all loads from the circuit.
    • Check for any overloaded appliances or shorted wiring.
    • Attempt to reset the RCBO. If it trips again, there might be a persistent fault or an issue with the RCBO itself.
  4. Persistent Tripping: If the RCBO continues to trip after troubleshooting, consult a qualified electrician.

7. Specifications

GEYA GYR9NM Type A RCBO Technical Specifications
Feature Specification
Model NumberGYR9NM-RCBO Type A
TypeResidual Current, RCD, Electro-mechanical
Poles2P, 4P
Rated Voltage (Ue)2P: 240V~, 4P: 415V~ (AC230V)
Rated Insulating Voltage (Ui)500V
Rated Impulse Withstand Voltage (Uimp)4kV
Rated Frequency50/60Hz
Rated Current (In)6A, 10A, 16A, 25A, 32A, 40A
Rated Sensitivity (IΔn)30mA, 100mA, 300mA
Breaking Capacity (Icn)6/10kA
Tripping CurvesB, C
Action Time<0.1s
StandardIEC61009-1
MountingDIN Rail EN/IEC 60715
Max. Connection Capacity (Hard Wire)25mm²
Max. Connection Capacity (Flexible Wire)16mm²
Tightening Torque2.5Nm
Mechanical Life10,000 operations
Electrical Life4,000 operations
Operating Temperature-5°C to +40°C
Storage Temperature-25°C to +70°C
Protection DegreeIP20 (Direct install), IP40 (Distribution box)
Pollution Grade3
EU LVD VoltageBelow 50Vac or 75Vdc
Wireless FunctionalityNo
Battery IncludedNo
Smart DeviceNo
High-concerned chemicalnone

Characteristics Curves & Temperature Compensation

Characteristics Curve B and C, and Temperature Compensation Table

Figure 6: Characteristics Curves (B & C) and Temperature Compensation Table

8. User Tips

  • Integrated Protection: The GEYA GYR9NM RCBO combines residual current (earth fault) and over-current (overload and short circuit) protection in one device, simplifying installation and enhancing safety.
  • Clear Fault Indication: Pay attention to the handle positions after a trip. If all handles are OFF, it's a residual current fault. If only the left handle is OFF, it's an over-current fault (MCB failure). This helps in quickly diagnosing the issue.
  • Regular Testing: Periodically test the RCBO using its test button to ensure the residual current detection mechanism is fully functional.

9. Warranty & Support

GEYA is committed to providing high-quality electrical products that meet industry standards. For detailed warranty information and further technical support, please refer to the official GEYA documentation or contact GEYA customer service.

An official user manual in PDF format is available for download, which may contain additional detailed information: View User Manual (PDF).

10. GEYA Manufacturing Overview

Watch this video to learn more about GEYA's manufacturing processes and commitment to quality in producing low-voltage electrical and automatic controlling products.

Video: GEYA Company Introduction and Manufacturing Process

© 2023 GEYA. All rights reserved.