1. Product Overview

The LEFOO LFS10 Air Velocity Transmitter is a high-precision sensor designed for accurate wind speed measurement. Utilizing advanced MEMS technology and based on the heat conduction principle, it offers high measurement accuracy, a wide measurement range, excellent stability, and strong environmental adaptability. It is an ideal solution for applications in HVAC systems, pipeline air volume measurement, process control, and environmental monitoring.
Key Features:
- Adopts imported high-precision MEMS sensor for long-term stability and anti-interference capability.
- Power supply and output feature overload and reversed-connection protection.
- Isolated output is optional.
- Strong anti-pollution ability, ensuring easy installation and maintenance.
2. Specifications
| Parameter | Value |
|---|---|
| Working Voltage | 24V AC/DC ±20% |
| Range | 0-10m/s, 0-15m/s, 0-20m/s, 0-30m/s (optional) |
| Accuracy | ±(0.2m/s + 3% of mv) (at 20℃, 45%RH and 1013hPa) |
| Resolution | 0.01m/s |
| Output Mode | RS485/Modbus, 0~10VDC/4~20mA (3-wire) (optional) |
| Output Load | ≤500Ω (Current mode), ≥2KΩ (Voltage type) |
| Working Temperature | -10~60℃ |
| Storage Temperature | -20~80℃ |
| Probe Length | 210mm (optional) |
| Display | Optional LCD display with unit display and backlight |
| Protection | IP65 (overall), IP20 (probe) |
| Sheathing Material | PC, PA6 (Probe) |
| Electromagnetic Compatibility | EN 61326-1 |
| Certification | ROHS, EU Electrical Safety Standards CE |
Product Dimensions (Duct Type)

The diagram above illustrates the dimensions for the duct type LFS10 sensor. Key dimensions include a probe length of 210mm, a main body width of 46mm, a height of 80mm, and a top housing width of 100mm. All measurements are in millimeters.
Product Dimensions (Split Type)
For the split type LFS10 sensor, the dimensions of the probe and main body are similar to the duct type, but the sensor head is separate from the main housing. Refer to the wiring diagram image in Section 5 for a visual representation of the split type dimensions. Key dimensions include a probe length of 210mm, a main body width of 46mm, a height of 80mm, and a top housing width of 100mm. All measurements are in millimeters.
3. Product Selection
The LFS10 series offers various configurations based on output type, installation method, and display option. Use the table below to select the appropriate model for your application.
| Prefix | Description | Category |
|---|---|---|
| LFS10- | Air Velocity Transmitter | Base Model |
| VI | 0~10VDC / 4~20mA | Output |
| RS | RS485/Modbus | Output |
| 1 | Duct Type Air Velocity Transmitter | Installation Method |
| 2 | Split Type Wind Speed Transmitter | Installation Method |
| D | With display | Display |
| N | Without display | Display |
Selection Example: LFS10-RS1D indicates a Duct-type wind speed transmitter with RS485/Modbus output and a digital display.
4. Installation Instructions
Mounting Flange Size and LFS101 Installation

The mounting flange has a central hole of Ø15.5mm for the probe and two Ø5mm mounting holes spaced 60mm apart.
Installation Procedure (LFS101 Duct Type):
- Drill the surface of the pipeline at the desired installation point.
- Install the mounting flange onto the drilled surface.
- Secure the mounting flange by locking the fixing screws.
- Insert the transmitter probe into the flange and adjust its position as needed.
- Lock the flange screws to firmly hold the probe in place.
Installation Procedure (LFS102 Split Type)

For LFS102 models, flange accessories are recommended for installation, allowing for adjustable insertion depth. The mounting flange should be fixed to the air duct with two screws, and the flange screws will lock the inserted probe. The required opening in the duct is Ø15.5mm. After installation, ensure the duct is sealed to prevent air leakage.
Important: When installing in an air duct, pay special attention to the fact that the air inlet is consistent with the wind speed flow inside the duct, and the sensor is parallel to the wind speed flow.
5. Wiring Instructions
Before wiring, open the upper cover of the device. Connect the power and signal wires through the waterproof connector into the bottom box. Follow the specific wiring diagrams below for your output type. After wiring, ensure the upper cover is reinstalled correctly, paying attention to the sealing rings for both the waterproof joint and the upper cover to maintain the IP65 protection level.

RS485 Output Wiring
- A: RS485 Data A
- B: RS485 Data B
- G: Ground
- V+: 24VDC Power Supply
Voltage Output Wiring (0-10VDC)
- I: Voltage Output Signal
- V: Voltage Reference
- G: Ground
- V+: 24VDC Power Supply
Current Output Wiring (4-20mA)
- I: Current Output Signal
- V: Voltage Reference
- G: Ground
- V+: 24VDC Power Supply
6. Operating Instructions
DIP Switch Settings (RS485 Version Only)
The 8-digit DIP switch is used to set the slave address for RS485 communication. The address can be set from 1 to 255. The factory default setting is 01. To set an address, dial the corresponding switch to 'ON' for a '1' and 'OFF' for a '0'. Digits 1-8 on the dial panel represent low to high bit values.

- Default Address 01: Binary 0000 0001 (Hex 0x01)
- Example Address 133: Binary 10000 101 (Hex 0x85) - calculated as 1 (bit 1) + 4 (bit 3) + 128 (bit 8)
Note 1: To prevent product damage, always adjust the DIP switch when the power is off. After changing the address, power cycle the device for the new setting to take effect.
Note 2: The address set by the DIP switch takes precedence over online slave address modifications. If you need to modify the slave address online, ensure all DIP switches are set to '0' first. The DIP switch method is generally preferred for address modification.
Range Selection (Analog Output Version Only)
For analog output products (0-10VDC or 4-20mA), the measurement range can be configured using jumper caps. Refer to the product's specific documentation or internal markings for jumper cap configurations corresponding to different ranges (e.g., 0-10m/s, 0-15m/s, 0-20m/s, 0-30m/s).
7. Maintenance
- Do not touch or rub the sensor probe.
- Do not use any mechanical tools to clean the sensor probe.
- Regularly inspect the waterproof connectors and sealing rings to ensure the IP65 protection level is maintained.
- Keep the device free from excessive dust and moisture to ensure optimal performance and longevity.
8. Troubleshooting
While specific troubleshooting steps are not provided, general issues can often be resolved by:
- No Power/Display: Check the 24V AC/DC power supply connections and ensure they are secure and within the specified voltage range.
- Incorrect Readings: Verify the sensor probe is correctly positioned and aligned with the airflow. Ensure the duct is properly sealed. Check if the correct output mode and range settings are selected (DIP switches/jumper caps).
- Communication Issues (RS485): Confirm DIP switch settings for the slave address are correct and the device has been power cycled after changes. Check wiring for continuity and correct polarity.
- Output Signal Problems: Ensure the output load meets the specified requirements for current or voltage mode.
- Environmental Factors: Ensure the operating temperature is within the specified -10~60℃ range.
If problems persist, contact technical support for further assistance.
9. User Tips
Based on common practices for similar devices, consider the following tips for optimal use:
- Always ensure the sensor is installed in a location where it can accurately measure the airflow without obstructions.
- For critical applications, periodic calibration checks are recommended to maintain measurement accuracy.
- When integrating with control systems, double-check the RS485 communication protocol or analog signal scaling to ensure correct data interpretation.
- Protect the sensor from physical impact and harsh chemicals that could damage the probe or housing.
10. Warranty and Support
For warranty information, technical support, or service inquiries, please refer to the seller's official website or contact their customer service department. Keep your purchase receipt or order details handy when seeking support.