1. Product Overview
The LEFOO LFS10 Split Type Anemometer Sensor Air Volume Transmitter is a high-precision device designed for accurate wind speed measurement. It utilizes an imported MEMS sensor, ensuring long-term stability and strong anti-interference capabilities. This transmitter is an ideal choice for various applications including HVAC systems, pipeline air volume measurement, process control, and environmental monitoring.
Key features include:
- High-precision MEMS sensor for accurate measurements.
- Long-term stability and anti-interference capability.
- Overload and reversed-connection protection for power supply and output.
- Optional isolated output.
- Strong anti-pollution ability, ensuring easy installation and maintenance.
- Available with digital display for real-time readings.
2. Specifications
The LFS10 series offers various configurations to suit different application needs. Below are the general specifications:

Figure 2.1: Overview and Parameters (Page 01 of Manual)

Figure 2.2: Detailed Specifications (Page 02 of Manual)
| Parameter | Value |
|---|---|
| Model Number | LFS10 |
| Working Voltage | 24V AC/DC ±20% |
| Range (Optional) | 0-10m/s, 0-15m/s, 0-20m/s, 0-30m/s |
| Accuracy | ±(0.2m/s + 3% of mv) (at 20°C, 45%RH and 1013hPa) |
| Resolution | 0.01m/s |
| Output Mode (Optional) | RS485/Modbus, 0-10VDC/4-20mA (3-wire) |
| Output Load | ≤500Ω (Current mode), ≥2KΩ (Voltage type) |
| Working Temperature | -10 ~ 60°C |
| Storage Temperature | -20 ~ 80°C |
| Probe Length | 210mm (optional) |
| Display | Optional LCD display with unit display and backlight |
| Protection | IP65 (main unit), IP20 (Probe) |
| Sheathing Material | PC, PA6 (Probe) |
| Electromagnetic Compatibility | EN 61326-1 |
| Certification | ROHS, EU Electrical Safety Standards CE |
| Origin | Mainland China |
3. Setup and Installation
The LFS10 anemometer is designed for easy installation, particularly in ducting systems. Ensure all power is disconnected before proceeding with installation.
3.1. Mounting the Sensor
The LFS10 recommends flange accessories for installation, allowing for adjustable insertion depth. The opening of the duct for the probe should be approximately Ø 15.5mm.

Figure 3.1: Mounting Flange Size and LFS101 Installation Diagram (Page 05 of Manual)

Figure 3.2: LFS102 Installation Diagram (Page 06 of Manual)
- Drill a hole on the surface of the pipeline.
- Install the fixing flange.
- Lock the fixing screws.
- Insert the transmitter and adjust its position.
- Lock the flange screws to secure the probe.
Important Notes for Installation:
- After the probe is installed, the duct should be sealed to avoid air leakage.
- When installing the air duct, pay special attention to ensuring the air inlet is consistent with the wind speed flow inside the duct, and the sensor probe is parallel to the wind speed flow.
3.2. Wiring Instructions
After mounting, connect the power and signal wires to the bottom box through the waterproof connector. Ensure the wiring is completed according to the provided wiring diagrams and that the upper cover is reinstalled securely. Pay attention to the sealing between the waterproof joint and the bottom box (with sealing ring) to maintain the IP65 protection level.

Figure 3.3: Wiring Instructions for RS485, Voltage, and Current Outputs (Page 03 of Manual)
Refer to Figure 3.3 for specific wiring configurations:
- RS485 Output: Connect A, B, G (Ground), and V+ (Power Supply).
- Voltage Output: Connect I (Output), V (Voltage Output), G (Ground), and V+ (Power Supply).
- Current Output: Connect I (Output), G (Ground), and V+ (Power Supply).
4. Operating Instructions
4.1. DIP Switch Settings (RS485 Version Only)
The 8-digit DIP switch sets the slave address for the RS485 communication. The address can be set from 1 to 255. The factory default setting is 01. To set the address, dial the switches to ON for '1' and vice versa for '0'. The 1-8 digits on the dial panel represent low to high bits.

Figure 4.1: DIP Switch Settings (RS485 Version) (Page 04 of Manual)
Example:
- Default address: 01 (hex), 0000 0001 (binary)
- Address 133: 1+4+128 = 133 (hex 0x85), 1000 0101 (binary)
Note 1: To prevent product damage, it is recommended to adjust the DIP switch in the event of a power failure. After changing the address using the DIP switch, the device must be powered on again for the change to take effect.
Note 2: The address set by the DIP switch has the highest priority when modifying the slave address online. All DIP switches must be set to 0 to modify successfully. If necessary, the DIP switch is preferred for address modification.
4.2. Range Selection (Analog Output Version Only)
Analog output products can have their measurement range selected by means of jumper caps. Refer to the specific product documentation or internal diagrams for jumper cap configurations.
5. Maintenance
Proper maintenance ensures the longevity and accuracy of your LEFOO LFS10 anemometer.
- Sensor Probe Care: Do not touch or rub the sensor probe. Avoid using any mechanical tools or abrasive materials to clean it, as this can damage the sensitive MEMS sensor.
- Cleaning: For general cleaning of the main unit, use a soft, dry cloth. If necessary, a slightly damp cloth can be used, but ensure no moisture enters the electrical connections.
- Inspection: Periodically inspect the wiring and connectors for any signs of wear, corrosion, or damage. Ensure all waterproof seals are intact.
- Recalibration: If you suspect inaccurate readings, consult a qualified technician for recalibration services.
6. Troubleshooting
This section provides solutions to common issues you might encounter with your LFS10 anemometer.
| Problem | Possible Cause | Solution |
|---|---|---|
| No display/No output | No power or incorrect wiring. | Check power supply (24V AC/DC). Verify wiring connections according to Figure 3.3. Ensure power is on. |
| Inaccurate readings | Sensor probe obstructed or damaged; incorrect installation angle; environmental interference. | Ensure probe is clean and unobstructed. Verify probe is parallel to airflow. Check for strong electromagnetic interference. Consider professional recalibration if issues persist. |
| RS485 communication error | Incorrect slave address; wiring issues; software configuration. | Verify DIP switch settings for the slave address (refer to Section 4.1). Ensure RS485 wiring is correct. Check communication software settings (baud rate, parity, etc.). Remember to power cycle after changing DIP switch settings. |
| Water ingress/Moisture inside unit | Improper sealing during installation. | Ensure all waterproof connectors are tightened and sealing rings are properly seated when closing the bottom box. Re-seal any compromised areas. |
7. User Tips
- Optimal Placement: For the most accurate readings, ensure the sensor probe is positioned in a section of the duct where airflow is stable and laminar, away from bends, fans, or other obstructions that could cause turbulence.
- Power Cycling for DIP Changes: Always remember to power off and then power on the device after making any changes to the DIP switch settings for the RS485 address to ensure the changes take effect.
- Environmental Considerations: While the main unit is IP65 rated, the probe is IP20. Avoid exposing the probe directly to harsh weather conditions or environments where it might be submerged or heavily splashed, unless additional protection is provided.
8. Frequently Asked Questions (FAQ)
- Q: What is the difference between the LFS10-RS2D and LFS10-VI2D models?
- A: The LFS10-RS2D model features an RS485/Modbus output, while the LFS10-VI2D model provides 0-10VDC/4-20mA analog output. Both typically include a digital display ('D').
- Q: Can I use this sensor outdoors?
- A: The main unit has an IP65 protection rating, making it suitable for outdoor use where it might be exposed to dust and water jets. However, the probe itself is IP20, meaning it is not protected against water. For outdoor applications, ensure the probe is adequately shielded from direct water exposure.
- Q: How do I change the measurement range?
- A: For analog output versions, the measurement range is typically selected using internal jumper caps. Refer to the specific product documentation or contact technical support for detailed instructions on jumper cap configurations for your desired range.
- Q: What is the maximum cable length for RS485 communication?
- A: While not explicitly stated in the provided information, RS485 communication generally supports cable lengths up to 1200 meters (4000 feet) with proper termination and cable type. However, always refer to the specific installation guidelines for your system.