1. Overview
The SmartGen CMM366A-4G Cloud Monitoring Communication Module is a 4G GPRS wireless network communication protocol switch module designed to connect gensets (with SCI) to the internet. Once connected to the cloud server, the module receives the corresponding genset controller communication protocol and acquires genset data via RS485, USB, LINK, or RS232 ports. This data is then transmitted to the cloud server via the 4G wireless network, enabling real-time monitoring of running status and access to running records through a mobile app (iOS or Android) or PC terminal devices.
The CMM366A-4G module also features GPS location functionality, allowing it to upload longitude, latitude, and altitude data to the cloud server. Beyond genset monitoring, it can integrate digital alarm input/output signals for monitoring generator room access, theft prevention, and fire facilities.
The CMM366A-ET model offers similar cloud monitoring capabilities but utilizes a wired Ethernet connection instead of 4G GPRS for internet connectivity.
Key Features:
- Connects to a cloud server via 4G wireless network (CMM366A-4G) or wired Ethernet (CMM366A-ET) for one-to-one genset monitoring.
- Multiple communication ports (RS485, RS232, LINK, USB Host) support a wide range of international genset control modules.
- Wide power supply range: DC 8-35V, compatible with genset built-in batteries.
- ARM-based 32-bit SCM for high integration and strong programming.
- GPS location function (CMM366A-4G) for gaining location information.
- Uses JSON network data communication protocol with compression algorithms to reduce network flow.
- Immediate data upload to the server upon alarm events.
- Two auxiliary digital input ports for external alarm signals.
- One auxiliary relay output port for various alarm signals.
- Front panel indicators for power and communication status.
- Lamp test function.
- Parameters adjustable via USB port.
- Standard 35mm guide-rail or screw-fixed installation.
- Modular design with self-extinguishing ABS plastic shell, lightweight, and compact structure.
2. Setup and Installation
2.1 Case Dimensions and Installation
The module can be installed in two ways: using a 35mm guide rail within a box or via M4 screws.



2.2 Antenna Connection (CMM366A-4G Only)
For the CMM366A-4G model, connect the GPRS antenna to the GPRS/4G port and the GPS antenna to the GPS port. Both antennas should be 50Ω/SMA female type. The GPS antenna requires an open outdoor placement for accurate location information.

NOTE: GPRS antenna and GPS antenna cannot be connected reversely.
2.3 SIM Card Installation (CMM366A-4G Only)
Insert a 4G, 3G, or 2G SIM card into the module. The CMM366A-4G will use this to connect to servers via the wireless mobile network. Use a standard SIM card (25mm x 15mm).

NOTE: If the GPS and GPRS indicators blink simultaneously, the SIM card may not be inserted correctly or has bad contacts.
2.4 Terminal Wiring
Connect the module to the genset controller using the appropriate ports (RS485, RS232, LINK, USB) as per the diagrams below. Ensure correct polarity and use recommended cable sizes.
| No. | Function | Cable Size | Note |
|---|---|---|---|
| 1 | B- | 1.0mm² | Connected with negative of starter battery. |
| 2 | B+ | 1.0mm² | Connected with positive of starter battery. 3A fuse is recommended. |
| 3 | Digital Input 1 | 1.0mm² | Active when connected to B-. |
| 4 | Digital Input 2 | 1.0mm² | Active when connected to B-. |
| 5-7 | Relay Output (Normally Open, Common, Normally Close) | 1.0mm² | Volt free output with 1A DC30V. |
| 8-10 | RS485 B(-), A(+), (SCR) | 0.5mm² | Impedance-120Ω shielding wire is recommended, its single-end earthed. |
| 11-13 | RS232 RX, TX, GND | 0.5mm² | RS232 port. |
RS485 Connection
Connect the module's RS485 port with the genset controller's RS485 port. If communication is abnormal, a 120Ω terminal resistance is recommended. One end of the shield wire should hang in the air, and the other end connects to SCR.

RS232 Connection
Connect the module's RS232 port with the genset controller's RS232 port.

LINK Connection
Connect the module's LINK port with the genset controller's LINK port.

USB HOST Connection
Connect the module's A-type USB host port (female) with the genset controller's USB port via a USB cable.

3. Operating Instructions
3.1 Panel Indicators and Buttons
The front panel features various LED indicators and a Lamp Test/Reset Hole to show the module's status.


| Icon | Note |
|---|---|
| POWER/ALARM | Green LED Light: Power supply normal indicator; Red LED Light: Common alarm indicator. |
| RS485 (Red) | Normally Extinguish: RS485 disabled; Normally Light: Communication fail; Blink: Communication normal. |
| USB (Red) | Normally Extinguish: USB(Host) disabled; Normally Light: Communication fail; Blink: Communication normal. |
| GPS (Red) | Normally Extinguish: GPS disabled; Normally Light: GPS not gained satellite signal; Blink: GPS gained satellite signal. |
| LINK (Red) | Normally Extinguish: Disabled; Normally Light: Communication fail; Blink: Communication normal. |
| RS232 (Red) | Normally Extinguish: RS232 disabled; Normally Light: Communication fail; Blink: Communication normal. |
| GPRS/4G (Red) | Extinguish: CMM366A-4G login with server unsuccessfully; Light: Login with server successfully; Blink: Real-time communication normal. |
| Lamp Test/Reset | Press for 1s: All LEDs illuminate. Press for 10s: Reset module to default, all LEDs blink 3 times. |
NOTE: After resetting the module, parameters need to be re-configured via PC software. Operate cautiously.
3.2 System Diagram
The CMM366A module connects with one genset monitor module. It can be connected via RS485, LINK, RS232, or USB port to a router, which then connects to the cloud server. Users can monitor the genset via cellphone, tablet, or PC.

3.3 PC Configuration Interface
Parameters can be configured and the CMM366A-4G ID & Login password can be viewed by connecting the module's USB port to a PC via a USB disk and using the PC software.

3.4 Programmable Parameters
The module's parameters can be configured via the PC software. Key parameters include Gateway settings (Site Name, URL, Server Port, Security Code), GPS settings (Enabled, Longitude, Latitude, Altitude), GSM settings (Enabled, GPRS Password, Message Center, PIN Enabled, APN), Digital Input settings (Setting, Type, Delay), and Digital Output settings (Setting).
NOTE: Configuration of monitoring genset controller model, communication port, communication baud rate, and communication ID need to be set on the platform, and the monitoring module needs to restart after all parameters have been set.
4. Maintenance
- Regularly check all wiring connections to ensure they are secure and free from corrosion.
- Keep the module clean and free from dust and debris.
- Periodically check the status indicators on the front panel to ensure normal operation.
- If the module is exposed to harsh environments, ensure its enclosure is properly sealed.
- Perform a lamp test periodically to verify all LED indicators are functional.
5. Troubleshooting
| Symptoms | Possible Solutions |
|---|---|
| Controller No Response for Power | Check power voltage; Check controller connection wirings. |
| GPRS/4G Indicator Not Light | Check SIM card is inserted or not; Check GPRS antenna is connected or not. |
| GPS Not Gain Location | Check GPS parameters are enabled or not; Check GPS antenna is connected or not and placed outdoor or not. |
| RS485 Comm. Abnormal | Check connections; Check RS485 port is enabled or not; Check settings of genset ID and baud rate are correct or not; Check RS485's connections of A and B is reverse connect or not. |
| RS232 Comm. Abnormal | Check connections; Check RS232 port is enabled or not; Check settings of genset ID and baud rate are correct or not. |
| LINK Comm. Abnormal | Check connections; Check LINK port is enabled or not; Check settings of genset ID and baud rate are correct or not. |
6. Specifications
| Items | Contents |
|---|---|
| Operating Voltage | DC 8.0V~35.0V, continuous power supply. |
| Power Consumption | Standby: ≤2W; Working: ≤5W |
| Digital Input | Digital Input, connect (B-) is active. |
| Relay Output | 1A DC30V Volts free output |
| USB Host | A-type USB female port |
| RS485 | Isolated type |
| RS232 | General type |
| LINK | SmartGen exclusive port |
| USB Device | B-type USB female port |
| GPRS Port | Standard SMA port (female), SMA port (male) for antenna |
| GPS Port | Standard SMA port (female), SMA port (male) for antenna, active antenna |
| Wireless Network (CMM366A-4G) | LTE-TDD/LTE-FDD/HSPA+/TD-SCDMA/EVDO, GSM/GPRS/EDGE |
| Case Dimensions | 72.5mm x 105mm x 34mm |
| Working Temperature | (-25~+70)°C |
| Working Humidity | (20~93)%RH |
| Storage Temperature | (-25~+70)°C |
| Weight | 0.15kg |
7. User Tips
- Model Selection: Carefully ensure you select the correct model (CMM366A-4G for 4G GPRS or CMM366A-ET for wired Ethernet) based on your application's connectivity requirements.
- Control Codes/Credentials: Control codes or login credentials for the cloud server are typically provided upon purchase or registration. If you do not receive them, please contact SmartGen support.
8. Warranty and Support
This product is manufactured by SmartGen. For detailed warranty information, please refer to the official SmartGen documentation or contact their support directly. A comprehensive user manual in PDF format is available for download: User Manual (PDF).
Contact Information:
SmartGen (Zhengzhou) Technology Co., Ltd.No. 28 Xuemei Street, Zhengzhou, Henan, China
Tel: +86-371-67988888 / 67981888 / 67992951
Fax: +86-371-67992952
Web: www.smartgen.com.cn/
Email: sales@smartgen.cn