CNC YCQ1B-63/2P

Contents

CNC YCQ1B-63/2P Dual Power Automatic Transfer Switch Instruction Manual

Model: YCQ1B-63/2P | Brand: CNC Electric

1. Introduction

The CNC YCQ1B-63/2P Dual Power Automatic Transfer Switch (ATS) is designed to seamlessly switch between two power sources, typically a common power supply and a standby power supply. This ensures continuous power to your load in case of an outage or abnormality in the primary source. It supports both automatic and manual operation, offering flexibility for various applications. When the common power supply is restored after an outage, the system automatically switches back to it. For special circumstances, manual switching is also available.

2. Safety Information

  • Installation and maintenance should only be performed by qualified electricians.
  • Always disconnect all power sources before working on the device to prevent electric shock.
  • Ensure proper grounding to prevent electrical hazards.
  • Verify all connections are secure and correctly wired according to the diagrams.
  • Do not operate the switch if it is damaged or appears to be malfunctioning.
  • Keep children and unauthorized personnel away from the installation area.

3. Product Features

  • Dual Power Automatic Switching: Seamless transfer between primary and backup power sources.
  • Automatic and Manual Operation: Offers flexibility for normal use and maintenance/testing.
  • High Performance: Designed for reliable and stable operation.
  • Protection Features: Includes Overload Protection, Output Analysis Signal, Undervoltage Protection, and Current Protection.
  • Clear Indication: Indicator lights for primary and backup source status.
Diagram illustrating product features like Overload Protection, Output Analysis Signal, Undervoltage Protection, and Current Protection.

Figure 1: Key Protection Features of the ATS

4. Specifications

AttributeValue
Model NumberYCQ1B-63/2P
TypeMoulded Case / Circuit breaker
Poles Number2P
Rated Current10A~63A
Rated Voltage230/400V
Operating Voltage220V
Working Frequency50Hz/60Hz
Standards CompliantIEC60947-6-1
Operation MethodAutomatic and Manual
ATS LevelCB
Conversion Time≤2s
Conversion MethodSelf-return
Is Smart DeviceNo
OriginMainland China
CertificationCE

Product Dimensions (mm)

Diagram showing product dimensions for 2P, 3P, and 4P models. For 2P, width is 128mm, height is 138mm. For 3P, width is 163mm, height is 138mm. For 4P, width is 198mm, height is 138mm. Side view shows depth of 115mm.

Figure 2: Product Dimensions for 2P, 3P, and 4P Models

5. Package Contents

  • 1 x CNC YCQ1B-63/2P Dual Power Automatic Transfer Switch
  • 1 x Instruction Manual (this document)

6. Installation & Wiring

Proper installation and wiring are critical for the safe and effective operation of the ATS. Refer to the following diagrams and instructions carefully.

Wiring Diagrams

The following diagrams illustrate the wiring for 2P, 3P, and 4P configurations. Ensure you match the correct diagram to your specific model and application.

Wiring diagrams for 2P, 3P, and 4P Automatic Transfer Switches. Each diagram shows connections for Common Fire Wire, Standby Fire Wire, Spare Neutral, Common Zero Line, and Load Output.

Figure 3: Product Wiring Diagrams (2P, 3P, 4P)

General Wiring Steps:

  1. Identify the primary (common) power source and the backup (standby) power source.
  2. Connect the primary source to the 'N' (Normal) input terminals of the ATS.
  3. Connect the backup source to the 'R' (Reserve) input terminals of the ATS.
  4. Connect the load to the output terminals of the ATS.
  5. Ensure all neutral and ground connections are correctly made.
  6. Double-check all connections for tightness and correctness before applying power.

Installation Video

Video 1: CNC Mini Dual Power Automatic Transfer Switch Wiring and Operation Demonstration

This video demonstrates the wiring and operation of the CNC Mini Dual Power Automatic Transfer Switch. It highlights the primary source, backup source, and load side connections. The video also shows how to switch between manual and automatic modes, and the behavior of the ATS during primary source abnormalities and recovery.

7. Operating Instructions

The ATS offers both manual and automatic operating modes.

Manual Mode

Manual mode is primarily used for testing, maintenance, or when specific control over power source selection is required. To operate in manual mode:

  1. Ensure the ATS is set to 'Manual' using the selector switch.
  2. Manually switch the power source using the lever on the device. This allows you to select between the primary ('N' or 'ON R') and backup ('R' or 'ON N') sources, or to turn the power 'OFF'.
  3. Observe the indicator lights to confirm the active power source.

Automatic Mode

In automatic mode, the ATS continuously monitors the primary and backup power sources and switches automatically as needed.

  1. Set the ATS to 'Auto' using the selector switch.
  2. Normal Operation: When both primary and backup sources are normal, the ATS will be connected to the primary source, and the 'Common' indicator light will be on.
  3. Primary Source Abnormal: If the primary source becomes abnormal (e.g., power outage), the ATS will automatically switch to the backup source. The 'Backup' indicator light will illuminate.
  4. Primary Source Recovery: When the primary source returns to normal, the ATS will automatically switch back to the primary source, and the 'Common' indicator light will be on again.

8. Maintenance

  • Regularly inspect the ATS for any signs of physical damage, loose connections, or overheating.
  • Keep the device clean and free from dust and debris.
  • Periodically test the automatic transfer function by simulating a primary power failure (if safe to do so and with proper precautions).
  • Ensure proper ventilation around the device.

9. Troubleshooting

  • Device not switching: Check if the ATS is in 'Auto' mode. Verify both primary and backup power sources are available and within operational parameters. Inspect wiring for loose connections.
  • Indicator lights not working: Check power supply to the ATS. If power is present and indicators are off, the unit may require professional inspection.
  • Frequent switching: This could indicate unstable power sources. Consult with your utility provider or an electrician to assess power quality.
  • If the problem persists after basic troubleshooting, contact a qualified electrician or the manufacturer for assistance.

10. User Tips

  • For optimal performance, ensure the ATS is installed in a dry, well-ventilated area, away from direct sunlight or extreme temperatures.
  • Regularly check the indicator lights to confirm the operational status of your power sources.
  • Consider labeling your primary and backup power sources clearly for easy identification during maintenance.

11. Certification

This product is CE certified, indicating compliance with European safety, health, and environmental protection requirements.

12. Disposal Information

This product should not be disposed of with household waste. Please recycle it at an appropriate collection point for electrical and electronic equipment. Proper disposal helps prevent potential negative consequences for the environment and human health.