GEYA GSP9-C40PV

Contents

GEYA GSP9 Photovoltaic DC Surge Protective Device

Model: GSP9-C40PV

Instruction Manual

1. Introduction

The GEYA GSP9 DC Surge Protective Device (SPD) is designed to safeguard DC power line systems and associated equipment from overvoltage and instantaneous overvoltage damage. Manufactured to IEC EN 61643-11 standards, this device is crucial for maintaining the integrity and longevity of photovoltaic (PV) installations.

It is widely utilized in photovoltaic combiner boxes, power inverters, DC distribution cabinets, and other critical components within solar energy systems.

GEYA GSP9 DC SPD product image

Figure 1: GEYA GSP9 Photovoltaic DC Surge Protective Device

2. Key Features

  • High Discharge Capacity: Effectively handles large surge currents.
  • Quick Response: Provides fast protection against transient overvoltages.
  • Module Pluggable Design: Allows for easy replacement of defective modules without disconnecting the entire unit.
  • Double Thermal Disconnection Devices: Offers enhanced and reliable protection.
  • Visual Fault Indication: Features a clear indicator window (green for normal, red for defect).
  • Remote Alarm Terminal (Optional): Enables remote monitoring of the device status.
  • T1+T2 Surge Protection: Provides comprehensive protection against direct and indirect lightning strikes.
  • Din Rail Installation: Designed for easy mounting on a 35mm DIN rail.
GSP9 DC SPD with removable module

Figure 2: GSP9 DC SPD with removable module for easy maintenance

3. Specifications

AttributeValue
ModelGSP9-C40PV
Product NameSurge Protection Device/SPD DC
Test StandardIEC/EN 61643-11; GB18802.11
IEC Test ClassificationT1+T2/Class I+ II
Max. PV Voltage [Uc pv]600V DC, 1000V DC, 1500V DC
Nominal Discharge Current (8/20μs)20KA
Maximum Discharge Current (8/20μs)40KA
Iimp Current (10/350μs)6.25KA
Poles2P (for 600V DC), 3P (for 1000V DC, 1500V DC)
Voltage Protection Level Up pv≤2.6KV (600V DC), ≤3.6KV (1000V DC), ≤5.6KV (1500V DC)
Response Time Ta25ns
Connecting Cable4mm² (L-N); 6mm² (PE)
Method of Installation35mm Din Rail
Matched Fuse or Circuit Breaker32A
Type of Remote Signaling ContactSwitching contact (Optional): C+NC (Normally closed), C+NO (Normally open), C (Common contact)
Switching CapacityAC: 250V/0.5A; DC: 250V/0.1A, 125V/0.2A, 75V/0.5A
Cross-sectional Area for Remote Signal ContactMax 1.5mm² solid / flexible
Operating Temperature Range-40℃ to +80℃
Technical Data Table for GSP9-C40PV

Figure 3: Detailed Technical Specifications

4. Dimensions

The GSP9-C40PV DC SPD is designed for compact installation. Refer to the diagrams below for detailed dimensions (in millimeters) for both standard and 1500V special size models.

Dimensions for 2P and 3P GSP9-C40PV DC SPD

Figure 4: Dimension details for 2P and 3P models (Remote terminal optional)

Dimensions for 1500V special size GSP9-C40PV DC SPD

Figure 5: Dimension details for 1500V special size model (Remote terminal optional)

5. Installation

The GSP9-C40PV DC SPD is designed for easy installation on a 35mm DIN rail. Ensure all connections are secure and follow local electrical codes and safety regulations.

5.1 Wiring Diagrams

Refer to the following diagrams for correct wiring of 2P and 3P configurations. Ensure proper polarity (+ and -) and a secure ground connection.

Installation Diagram for 2P and 3P GSP9-C40PV DC SPD

Figure 6: Installation Diagram for 2P and 3P models

Installation Diagram for 1500V special size GSP9-C40PV DC SPD

Figure 7: Installation Diagram for 1500V special size model

5.2 Connection Guidelines

  • Use connecting cables of 4mm² for L-N connections and 6mm² for PE (Protective Earth) connections.
  • Ensure the SPD is matched with a 32A fuse or circuit breaker for optimal protection.
  • For models with optional remote signaling contacts, use a maximum of 1.5mm² solid or flexible cable for connection.

6. Operating State Indication

The GSP9-C40PV DC SPD features a visual indicator window on each module to show its operational status:

  • Green Window: Indicates normal operation. The SPD is functioning correctly and providing protection.
  • Red Window: Indicates a defect. The module has absorbed a surge and is no longer providing protection. It needs to be replaced.
Front view of GSP9 DC SPD modules with indicators

Figure 8: Visual indicators on SPD modules

7. Maintenance

Regular inspection of the indicator windows is recommended to ensure continuous protection of your PV system.

7.1 Module Replacement

If an indicator window turns red, the corresponding module is defective and must be replaced. The pluggable design allows for easy and safe replacement:

  1. Ensure the DC power supply to the SPD is disconnected before attempting any maintenance.
  2. Carefully pull out the defective module from its base.
  3. Insert a new, compatible replacement module into the base, ensuring it clicks securely into place.
  4. Restore the DC power supply and verify that the new module's indicator window shows green.

Replacement cores for various voltage ratings (600V, 1000V, 1500V) are available. Ensure you select the correct voltage for your system.

AC DC SPD Replacement Core modules

Figure 9: Example of replacement core modules

8. Troubleshooting

ProblemPossible CauseSolution
Indicator window is REDSPD module has absorbed a surge and is defective.Replace the defective module with a new, compatible one.
No indication / Device not functioningNo power supply, incorrect wiring, or complete device failure.Check DC power connections. Verify wiring according to diagrams. If issues persist, contact support.

9. User Tips

Based on general usage and product design, here are some tips for optimal performance:

  • Always ensure proper grounding for effective surge protection.
  • Regularly check the indicator windows, especially after severe weather conditions, to confirm the SPD is operational.
  • When replacing modules, ensure the new module's voltage rating matches your system's requirements.

No specific user tips or common questions were available from customer reviews or Q&A for this product at this time.

10. Warranty and Support

GEYA Electric is committed to providing high-quality electrical products. Our products are certified to various industry standards, ensuring reliability and safety.

10.1 Certifications

GEYA products, including the GSP9-C40PV DC SPD, are certified to meet stringent international standards:

  • CE
  • CB
  • SAA
  • SEMKO
  • TUV
  • RoHS
GEYA product certifications

Figure 10: GEYA Product Certifications

10.2 Contact Information

For technical support, warranty inquiries, or any other assistance, please contact GEYA Electric:

  • Website: www.geya.net
  • Email: cassie@cngeya.com
  • Phone: +86 13968799499
  • Address: Wenzhou Bridge Industrial Zone, Beibaixiang Town, Wenzhou City, Zhejiang Province, China

Video: GEYA Company Introduction

© 2023 GEYA Electric. All rights reserved.


Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.