GEYA GRI8-05 Current Monitoring Relay

Contents

GEYA GRI8-05 DC Current Monitoring Relay User Manual

Model: GRI8-05 Series

Brand: GEYA

1. Introduction

The GEYA GRI8-05 series current monitoring relay is designed for reliable over-current and under-current protection in various electrical applications. It is suitable for monitoring heating in rail-switches, heating cables, and the consumption of single-phase motors, providing clear indication of current flow. This manual provides essential information for the safe and effective installation, operation, and maintenance of your GRI8-05 relay.

2. Product Overview and Features

The GRI8-05 series offers advanced features for current monitoring:

  • Through-Center Design: Facilitates easy installation without needing to disconnect the current circuit.
  • Flexible Monitoring Modes: Supports both over-current and under-current monitoring, configurable via a jumper.
  • Versatile Testing: Available in GRI8-05A for AC current measurement and GRI8-05B for AC/DC current measurement.
  • Expandable Current Range: Utilizes an isolation current transformer, allowing connection of external current transformers to extend the monitoring range.
  • Universal Power Supply: Operates with a wide AC/DC 24-240V universal supply.
  • Status Indication: Equipped with an LED indicator to show the relay's operational status.
  • Compact Design: 1-MODULE size for DIN rail mounting, saving space in electrical panels.
GEYA GRI8-05B DC Current Monitoring Relay

Figure 2.1: GEYA GRI8-05B Current Monitoring Relay

GEYA GRI8-05A AC Current Monitoring Relay

Figure 2.2: GEYA GRI8-05A Current Monitoring Relay

3. Installation and Setup

3.1 Mounting

The GRI8-05 series relay is designed for DIN rail mounting (EN/IEC 60715). Ensure secure installation in a suitable electrical enclosure.

3.2 Wiring Diagram

Refer to the following diagram for proper wiring connections. Always ensure power is disconnected before performing any wiring.

Panel Diagram, Dimensions, Functions Diagram, and Wiring Diagram for GRI8-05 Series

Figure 3.1: Panel Diagram, Dimensions, Functions Diagram, and Wiring Diagram

Wiring Instructions:

  • Supply Terminals (A1-A2): Connect the power supply (AC/DC 24-240V) to terminals A1 and A2.
  • Output Contact (1SPDT): The relay features a single pole double throw (1SPDT) output contact. Connect your controlled circuit to terminals 11, 12, and 14 as required.
    • 11: Common
    • 12: Normally Closed (NC)
    • 14: Normally Open (NO)
  • Current Monitoring:
    • Monitored current ≤ 20A: Pass the load wire directly through the integrated current transformer (CT) opening on the relay.
    • Monitored current > 20A: Use an external current transformer (CT) for current transformation. Connect the secondary output of the external CT to terminals Y1 and Y2 on the relay.

3.3 Setting Monitoring Mode

The monitoring mode (over-current or under-current) can be selected using the jumper setting on the device. Consult the device markings or the function diagram (Figure 3.1) for specific jumper positions.

4. Operating Instructions

4.1 Power On

Once correctly wired and mounted, apply power to the A1-A2 terminals. The green "Un" LED will illuminate, indicating the device is powered.

4.2 Current Range Setting

Adjust the current range using the potentiometer on the front panel. The available range is 2A-20A. Set the potentiometer to the desired current threshold for your application.

4.3 Status Indication

The red "R" LED indicates the status of the output relay. Refer to the function diagram (Figure 3.1) for detailed behavior of the output relay based on current levels and set thresholds.

4.4 Function Diagram Interpretation

The function diagram illustrates the relay's behavior under different current conditions relative to the set threshold (Iset) and hysteresis. It shows how the output contacts (11-14) switch based on whether the monitored current (I) is above or below the set limits, considering the hysteresis.

5. Maintenance

The GEYA GRI8-05 series current monitoring relay is designed for long-term, maintenance-free operation. However, regular checks are recommended to ensure optimal performance and safety:

  • Visual Inspection: Periodically inspect the device for any signs of physical damage, loose connections, or overheating.
  • Cleaning: Keep the device clean and free from dust and debris. Use a dry, soft cloth for cleaning. Do not use abrasive cleaners or solvents.
  • Connection Integrity: Ensure all terminal connections remain tight and secure.
  • Environmental Conditions: Verify that the operating environment remains within the specified temperature and humidity ranges to prevent premature failure.

For any repairs or internal servicing, contact qualified personnel or GEYA customer support.

6. Troubleshooting

If the device is not functioning as expected, consider the following common issues:

  • No Power Indication (Green "Un" LED off):
    • Check the power supply voltage at terminals A1-A2.
    • Ensure the power supply is within the AC/DC 24-240V range.
    • Verify all power connections are secure.
  • Incorrect Relay Operation (Red "R" LED / Output Contacts):
    • Confirm the current monitoring mode (over-current/under-current) is correctly set via the jumper.
    • Check the current range setting on the potentiometer.
    • Verify the actual current flowing through the monitored circuit is within expected limits.
    • Ensure the load is correctly connected to the output contacts (11, 12, 14).
  • Inaccurate Current Reading:
    • For currents ≤ 20A, ensure the wire passes correctly through the internal CT.
    • For currents > 20A, verify the external CT is correctly installed and its secondary output is connected to Y1-Y2.
    • Check the calibration of any external current measurement devices.

If problems persist after checking these points, contact GEYA technical support.

7. Specifications

The following table details the technical parameters for the GEYA GRI8-05 series current monitoring relays:

Technical Parameters Table for GRI8-05A and GRI8-05B

Figure 7.1: Technical Parameters for GRI8-05A and GRI8-05B

ParameterGRI8-05AGRI8-05B
FunctionAC measurementAC/DC measurement
Supply terminalsA1-A2
Rated supply voltageAC/DC 24-240V
Rated supply frequency50/60Hz, 0
Burdenmax 25VA
Supply voltage tolerance-15%; +10%
Current range2A-20A
Current frequencyAC 50HzAC 50Hz, DC
Setting accuracypotentiometer
Supply indicationgreen LED
Setting accuracy10 %
Hysteresis5 %
Output1×SPDT
Current rating10A/AC1
Switching voltage250VAC/24VDC
Min. breaking capacity DC500mW
Output indicationred LED
Mechanical life1×107
Electrical life (AC1)1×105
Operating temperature-20°C ~ +55°C
Storage temperature-35°C ~ +75°C
Mounting/DIN railDin rail EN/IEC 60715
Protection degreeIP20
Operating positionany
Overvoltage categoryIII.
Pollution degree2
Max. cable size (mm2)1x2.5mm2 or 2x1.5mm2 0.4N·m
Dimensions90mm × 18mm × 64mm

8. User Tips

  • Minimum Current: The device requires a minimum current of 2A for proper operation and detection. Ensure your application meets this minimum threshold.

9. Warranty and Support

GEYA products are manufactured to high-quality standards and are certified to required industry standards, including CE, CB, and ROHS. For any technical assistance, warranty claims, or support, please contact GEYA customer service through their official channels.

GEYA is committed to providing top-quality products and services to its clients.

10. About GEYA

Learn more about GEYA's commitment to quality, innovation, and customer satisfaction by watching this company overview video:

Video: GEYA Company Overview and Manufacturing Process

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.