1. Introduction
The GEYA GYR9NM Series RCBO (Residual Current Circuit Breaker with Over-current Protection) is designed for electrical systems with AC 50Hz or 60Hz, rated voltage of 240V (for 2-pole) or 415V (for 4-pole), and rated current up to 40A. This device integrates leakage, overload, and short-circuit protection functions.
Its primary purpose is to protect personal safety and prevent equipment failure by rapidly cutting off fault current (within 0.1s) when personal contact occurs or the power grid's leakage current exceeds specified values. It can also be used for infrequent breaking and switching of lines under normal conditions, making it suitable for building lighting and distribution systems.
2. Safety Information
- Always disconnect the main power supply before attempting any installation, wiring, or maintenance procedures.
- Installation and wiring should only be performed by a qualified and licensed electrician in accordance with local and national electrical codes.
- Do not operate the circuit breaker with wet hands or in damp conditions.
- Ensure proper grounding to prevent electrical shock.
- Verify that the product specifications (voltage, current, sensitivity) match your electrical system requirements.
- Never bypass or tamper with the safety features of the RCBO.
3. Specifications
3.1. Electrical Characteristics
| Parameter | Value |
|---|---|
| Type | Residual Current, RCD, RCBO Electro-mechanical (AC Type) |
| Poles | 2-Pole, 4-Pole |
| Rated Current (In) | 10A, 16A, 25A, 32A, 40A |
| Rated Sensitivity (IΔn) | 30mA, 100mA, 300mA |
| Rated Voltage (Ue) | 220V / AC230V (2-Pole), 400V / 415V (4-Pole) |
| Rated Frequency | 50/60Hz |
| Breaking Capacity | 6000A |
| Standard | IEC61009-1 |
| Rated Insulation Voltage (Ui) | 500V |
| Rated Impulse Withstand Voltage (Uimp) | 4kV |
| Break Time (Instantaneous) | 0.1s (1IΔn), 0.08s (2IΔn), 0.04s (5IΔn) |
3.2. Mechanical Properties
| Parameter | Value |
|---|---|
| Mechanical Life / Electric Life | 4000 cycles |
| Protection Class | IP20 (Direct Install), IP40 (In Distribution Box) |
| Ambient Temperature | -25°C to +60°C |
| Storage Temperature | -25°C to +70°C |
3.3. Other Characteristics
| Parameter | Value |
|---|---|
| Wiring Size (Copper/Hard Wire) | 1-25mm² |
| Wiring Size (Cord/Hoop Terminals) | 1-16mm² |
| Mounting | Din Rail |
| Contact Status Indication | Yes |
| Fault Indication | Yes |
| Circuit Identification | Yes |
| Connection | Top and bottom (ELM), Top line (ELE) |
3.4. Characteristics Curves and Temperature Compensation
The device features specific tripping characteristics (Curve B and Curve C) and temperature compensation factors. For precise application, refer to the detailed curves and the temperature correction coefficient table provided in the full manual.

Image: Characteristics Curve (B and C) and Temperature Compensation Table
4. Installation and Setup
4.1. Mounting
The GEYA GYR9NM RCBO is designed for Din Rail mounting. Ensure the Din Rail is securely installed in your distribution box or electrical panel.

Image: Installing Dimensions Diagram (Side and Front Views)
4.2. Wiring
Connect the RCBO according to the wiring diagrams and the specified nominal section area of copper wire for your chosen rated current. Always ensure connections are tight and secure.
- 2-Pole RCBO: Connect the live (L) and neutral (N) wires to the appropriate terminals as indicated on the device.
- 4-Pole RCBO: Connect the three live (L1, L2, L3) and one neutral (N) wires to the appropriate terminals.
Recommended Wire Sizes:
| Rated Current (In) | Nominal Section Area of Copper Wire (mm²) |
|---|---|
| 1-6A | 1 |
| 10A | 1.5 |
| 16A, 20A | 2.5 |
| 25A | 4 |
| 32A | 6 |
| 40A | 10 |

Image: GEYA 2-Pole RCBO (GYR9NM C32) with Integrated Wiring Diagram

Image: GEYA 4-Pole RCBO (GYR9NM C40) with Integrated Wiring Diagram

Image: Comparison of 2-Pole and 4-Pole AC Type RCBOs, highlighting MCB and RCCB functions.
5. Operation
5.1. Turning On/Off
- To turn on the power, push the operating lever(s) upwards to the 'ON' position.
- To turn off the power, push the operating lever(s) downwards to the 'OFF' position.
- In case of a fault (leakage, overload, or short circuit), the RCBO will automatically trip, moving the lever(s) to the 'OFF' position.
5.2. Test Button
The RCBO is equipped with a test button (marked 'T' or 'Test Monthly') to verify its residual current protection function. Pressing this button simulates a leakage current, and the RCBO should trip immediately.

Image: GEYA 2-Pole RCBO (GYR9NM C32) showing the 'Test Monthly' button.
6. Maintenance
- Regular Testing: It is crucial to test the residual current protection function monthly by pressing the 'Test' button. If the RCBO does not trip, it may be faulty and should be replaced immediately by a qualified electrician.
- Visual Inspection: Periodically inspect the RCBO for any signs of physical damage, discoloration, or loose connections.
- Cleaning: Keep the device clean and free from dust and debris. Use a dry, soft cloth for cleaning. Do not use liquids or abrasive cleaners.
7. Troubleshooting
| Problem | Possible Cause | Solution |
|---|---|---|
| RCBO trips frequently | Overload, short circuit, or persistent leakage current. | Identify and rectify the cause of overload, short circuit, or leakage. Consult a qualified electrician. |
| Both handles are in the OFF position | Indicates the presence of a residual current fault. | Check for ground faults or leakage in the circuit. Reset the RCBO after clearing the fault. |
| Left handle is in the OFF position (for multi-pole) | Indicates an MCB (Miniature Circuit Breaker) failure. | The device may be faulty. It should be inspected and potentially replaced by a qualified electrician. |
| RCBO does not trip when test button is pressed | The residual current protection function is faulty. | The RCBO is defective and must be replaced immediately by a qualified electrician. |
| No power to the circuit | RCBO tripped, loose connections, or upstream breaker tripped. | Check the RCBO status, inspect wiring, and check main circuit breaker. |
8. User Tips
- Verify Type: Always double-check that you are purchasing the correct type of RCBO (AC Type in this case) for your specific application. Some users have mistakenly ordered AC Type when they needed Type A, which is designed for different leakage current characteristics.
- Installation Location: This product is versatile and can be installed on a Din Rail in any room or various scenes requiring residual current protection, such as residential, commercial, or general industrial settings.
- Poles: The product is available in either 2-pole or 4-pole configurations, so ensure you select the correct option for your electrical system.
9. Frequently Asked Questions (FAQ)
- Q: What is the purpose of this RCBO?
- A: It provides protection against leakage current, overload, and short circuits in AC electrical systems.
- Q: How do I know if there's a residual current fault?
- A: If both handles are in the OFF position, it indicates a residual current. This is a safety feature to alert you to a potential issue.
- Q: What does it mean if the left handle is in the OFF position?
- A: If only the left handle is in the OFF position (for multi-pole units), it suggests an MCB (Miniature Circuit Breaker) failure, indicating an internal fault with the device itself.
- Q: How often should I test the RCBO?
- A: It is recommended to test the RCBO monthly using the test button to ensure its residual current protection function is working correctly.
- Q: Can this be used in residential settings?
- A: Yes, it is suitable for terminal distribution lines in commercial, residential, and general industrial use.
- Q: What mounting type does it use?
- A: It is designed for Din Rail mounting, which is a standard for electrical enclosures.
10. Warranty and Support
GEYA products are manufactured to high-quality standards and are CE certified, ensuring compliance with European safety, health, and environmental protection requirements.
For detailed warranty information, technical support, or further inquiries, please refer to the official GEYA website or contact your local distributor. A comprehensive user manual in PDF format is also available for download:
11. Product Overview Video
Video: An overview of the GEYA manufacturing process and product testing, highlighting quality control and production capabilities.