1. Introduction
The GEYA GYM9-125 DC Mini Circuit Breaker (MCB) is designed for protection against overload and short circuit conditions. It is suitable for a wide range of applications including communication systems, photovoltaic (solar) installations, and other DC system applications. This manual provides essential information for the safe and effective installation, operation, and maintenance of your circuit breaker.
For detailed product guides and documents, please refer to the official PDF manual: User Manual (PDF).
2. Product Features
- Standards Compliance: Conforms to IEC/EN60947-2 and GB14048.2.
- Wiring Flexibility: Features double busbar and single busbar wiring options to adapt to various installation requirements.
- Clear Indication: Equipped with a transparent identification function and a contact position indication function for easy status monitoring.
- Robust Connections: Maximum wiring capacity of 25mm², with a tightening torque of 3.5N·m, ensuring strong and reliable connections.
- Protection: Provides protection against overload, short circuit, and is suitable for isolation.

Figure 2.1: GEYA GYM9-125 DC Mini Circuit Breakers (Various Pole Configurations)
3. Specifications
| Attribute | Specification |
|---|---|
| Product Name | GYM9-125 Mini Circuit Breaker |
| Brand Name | GEYA |
| Model Number | GYM9-125 |
| Type | Mini Circuit Breaker |
| Rated Current (In) | 80A, 100A, 125A (Also available in 1A-63A for other models) |
| Poles | 1P, 2P, 3P, 4P |
| Rated Voltage (Ue) | 1P: 250VDC; 2P: 500VDC; 3P: 750VDC; 4P: 1000VDC |
| Rated Frequency | 50/60Hz |
| Tripping Curves | B, C, D |
| Breaking Capacity | 6kA |
| Thermo-magnetic release characteristic | C Curve & DC Type |
| Insulation Voltage (Ui) | 500V |
| Rated Impulse Withstand Voltage (Uimp) | 6kV |
| Dielectric Test Voltage (1min) | 2kV |
| Pollution Degree | 2 |
| Mechanical Life | 20000 cycles |
| Electrical Life | 1500 cycles |
| Protection Class | IP20 |
| Reference Temperature for Thermal Element Setting | 30°C |
| Ambient Temperature | -5°C to +40°C (with daily average ≤35°C) |
| Storage Temperature | -25°C to +70°C |
| Terminal Connection Type | Cable/U-type busbar/Pin-type busbar |
| Terminal Size (top/bottom for cable) | 50mm² (18-1/0 AWG) |
| Tightening Torque | 3.5N·m |
| Mounting | On DIN rail FN 60715 (35mm) by means of fast clip device |
| Connection | Top and bottom |
3.1. Temperature Compensation
When the ambient temperature deviates from the baseline temperature of 30°C, the reference correction coefficient for the rated current should be applied as follows:
| Ambient Temperature | -20°C | -10°C | 0°C | 10°C | 20°C | 30°C | 40°C | 50°C | 60°C |
|---|---|---|---|---|---|---|---|---|---|
| Current Correction Factor | 1.25 | 1.2 | 1.15 | 1.10 | 1.05 | 1.00 | 0.95 | 0.90 | 0.85 |
4. Installation
4.1. Mounting and Dimensions
The GYM9-125 DC MCB is designed for mounting on a 35mm DIN rail (FN 60715) using a fast clip device. Ensure adequate space for wiring and heat dissipation.

Figure 4.1: Outline Overall and Installing Dimensions for 1P, 2P, 3P, and 4P MCBs.
4.2. Wiring Connections
Connections are made at the top and bottom terminals. Use copper wire with the nominal section area corresponding to the rated current as per the table below. Ensure all connections are tight with a torque of 3.5N·m.
| Rated Current | Nominal Section Area of Copper Wire (mm²) |
|---|---|
| 1~6A | 1 |
| 10A | 1.5 |
| 16, 20A | 2.5 |
| 25A | 4 |
| 32A | 6 |
| 40, 50A | 10 |
| 63A | 16 |
| 80A | 25 |
| 100A | 35 |
| 125A | 50 |

Figure 4.2: Connection Table for Copper Wire Section Area.
4.3. Wiring Diagram (DC Applications)
For DC applications, proper polarity is crucial. The DC power supply typically uses an "L-" ground lead, and the neutral pole of the positive and negative power supply system uses an "M" ground lead.

Figure 4.3: DC Wiring Diagram for GYM9H-DC MCB.
Remark: L+: Positive Pole, L-: negative pole. ★: MCB of positive pole, ☆: negative pole. ★☆: Load.
5. Operating Instructions
The GEYA GYM9-125 DC MCB operates as a switch to control the flow of electricity and as a protective device. The lever on the front of the MCB indicates its status:
- ON Position: The circuit is closed, allowing current to flow.
- OFF Position: The circuit is open, interrupting current flow.
- Tripped Position: The lever will be in an intermediate position, indicating an overload or short circuit has occurred. To reset, move the lever to the OFF position first, then to the ON position.
The transparent identification window and contact position indicator provide visual confirmation of the breaker's status.
6. Maintenance
To ensure the longevity and reliable operation of your GEYA GYM9-125 DC MCB, follow these general maintenance guidelines:
- Regular Inspection: Periodically check the MCB for any signs of physical damage, discoloration, or loose connections.
- Cleanliness: Keep the MCB and its surroundings clean and free from dust and debris. Use a dry, soft cloth for cleaning.
- Tightness of Connections: Re-check the tightness of terminal screws periodically, especially after initial installation and during routine maintenance, to prevent overheating due to loose connections.
- Environmental Conditions: Ensure the operating environment adheres to the specified ambient and storage temperatures to prevent premature wear or malfunction.
Warning: Always disconnect power before performing any inspection or maintenance to prevent electric shock.
7. Troubleshooting
If the circuit breaker trips frequently or fails to operate correctly, consider the following:
- Frequent Tripping: This often indicates an overload or short circuit in the protected circuit.
- Disconnect all loads from the circuit.
- Reset the MCB. If it holds, reconnect loads one by one to identify the faulty device.
- If the MCB trips immediately after resetting with no load, there might be a short circuit in the wiring itself.
- Failure to Reset: If the MCB does not reset after being moved to the OFF position, it may indicate a persistent fault or internal damage to the breaker.
Important: For any persistent issues or complex electrical problems, consult a qualified electrician. Do not attempt repairs if you are not qualified, as this can lead to serious injury or further damage.
8. User Tips
- Value for Money: Users have noted the excellent quality and progressive design of GEYA products, offering good value.
- Packaging Check: Always inspect the product packaging upon arrival for any signs of damage to ensure the circuit breaker itself is intact.
- Versatile Application: The GYM9-125 MCB is suitable for various applications, including communication, photovoltaic, and other DC systems.
- Pole Configuration: The product is available in 1P, 2P, 3P, and 4P configurations. Ensure you select the correct pole configuration for your specific needs.
9. Warranty and Support
GEYA Electric, established in 2007, is a manufacturer of low voltage electrical and automatic controlling products. GEYA products are certified to required industry standards, including CCC, CE, CB, SAA, SEMKO, TUV, and RoHS.
For specific warranty terms and conditions, please refer to the documentation provided with your purchase or contact the seller directly. For technical support, please reach out to GEYA Official Store or an authorized distributor.
Video 9.1: GEYA Company Introduction and Product Overview.