1. Introduction
The ComWinTop CWT-TM-16TC is a high-performance 16-channel temperature acquisition module designed for industrial and laboratory applications. It accurately measures temperatures using K-type thermocouples and outputs the data via an RS485 interface using the Modbus RTU protocol. This module provides a reliable and efficient solution for monitoring multiple temperature points in various environments.

2. Features
- 16-Channel Input: Supports up to 16 independent K-type thermocouple inputs.
- Wide Measurement Range: Capable of measuring temperatures from -200°C to +1350°C.
- High Resolution: Provides temperature readings with a resolution of 0.25°C.
- RS485 Communication: Utilizes RS485 interface with Modbus RTU protocol for robust data transmission.
- Isolation Design: Ensures stable and interference-free operation.
- Wide Power Supply: Operates on a DC 8V-30V power input.
- Durable Construction: Housed in an ABS material casing.
- Easy Installation: Designed for 35mm Din-rail mounting.
3. Specifications

| Parameter | Value |
|---|---|
| Power supply | DC8-30V |
| Power consumption | 19mA@30V, 22mA@24V, 45mA@12V, 41mA@8V |
| Input | K-thermocouple, Measure range: -200°C ~ +1350°C, Resolution 0.25°C |
| Output | RS485 (Modbus RTU protocol), isolation design |
| Working environment | -30~+55°C / 0-95%RH |
| Material | ABS |
| Mounting type | 35mm Din-rail |
| Dimensions | 145x90x40mm |

4. Setup and Wiring
Proper wiring is crucial for the correct operation of the CWT-TM-16TC module. Follow the instructions below for power, thermocouple, and RS485 connections.
4.1 Terminal Description

| Terminals | Description |
|---|---|
| +V | Power + (DC 8-30V) |
| GND | Power - |
| TD(n)+ | Thermocouple Sensor + (for channel n) |
| TD(n)- | Thermocouple Sensor - (for channel n) |
| A (D+) | RS485 + |
| B (D-) | RS485 - |
4.2 Wiring Diagram

4.3 Mounting
The module is designed for 35mm Din-rail mounting. Simply attach the module to a standard Din-rail using the integrated clips on the back of the unit.

5. Operating Instructions
Once the module is correctly wired and powered, it will begin acquiring temperature data from the connected K-type thermocouples. Communication and configuration are performed via the RS485 interface using the Modbus RTU protocol.
5.1 Modbus Communication Parameters
- Default Baud Rate: 9600 bps
- Default Parity: None (n)
- Data Bits: 8
- Stop Bits: 1
- Default Device Address: 1
5.2 Configuration Tool
A dedicated configuration tool is provided to assist with setting up the module's parameters, such as slave address, baud rate, and parity, and to read channel data. This tool simplifies the initial setup process.

6. Modbus Register Map
6.1 Parameter Register Map
Function code: 03H (read), 06H (write)

| Address (hex) | Byte order | Meaning | Description | Property |
|---|---|---|---|---|
| 10 | LO | Communication parameters | BIT<7:5> reserve BIT<4:3> 00=none 01=even 10=odd BIT<2:0> 000=9600 001=1200 010=2400 011=4800 100=9600 101=14400 110=19200 Initial value: 00 | RW |
| Hi | Address | 1-250 Initial value: 01 | RW |
6.2 Data Register Map
Function code: 03H (read)

| Address (hex) | Description | Format | Scale | Number of bytes | Property |
|---|---|---|---|---|---|
| 20H | Channel 1 | UINT | 0.1 | 2 | R |
| 21H | Channel 2 | UINT | 0.1 | 2 | R |
| 22H | Channel 3 | UINT | 0.1 | 2 | R |
| 23H | Channel 4 | UINT | 0.1 | 2 | R |
| 24H | Channel 5 | UINT | 0.1 | 2 | R |
| 25H | Channel 6 | UINT | 0.1 | 2 | R |
| 26H | Channel 7 | UINT | 0.1 | 2 | R |
| 27H | Channel 8 | UINT | 0.1 | 2 | R |
| 28H | Channel 9 | UINT | 0.1 | 2 | R |
| 29H | Channel 10 | UINT | 0.1 | 2 | R |
| 2AH | Channel 11 | UINT | 0.1 | 2 | R |
| 2BH | Channel 12 | UINT | 0.1 | 2 | R |
| 2CH | Channel 13 | UINT | 0.1 | 2 | R |
| 2DH | Channel 14 | UINT | 0.1 | 2 | R |
| 2EH | Channel 15 | UINT | 0.1 | 2 | R |
| 2FH | Channel 16 | UINT | 0.1 | 2 | R |
7. User Tips
- Thermocouple Type: Always ensure you are using K-type thermocouples for accurate measurements, as the module is specifically designed for this type.
- Wiring Polarity: Pay close attention to the polarity when connecting thermocouples (TD(n)+ and TD(n)-) to avoid incorrect readings.
- Modbus Configuration: Before initial use, verify the Modbus communication settings (baud rate, parity, and device address) using the provided configuration tool or your Modbus master software.
- Power Supply: Use a stable DC power supply within the specified range of 8V-30V to prevent damage and ensure reliable operation.
8. Troubleshooting
- No Power: Check the DC 8-30V power supply connection and ensure it is within the specified voltage range.
- No Communication:
- Verify RS485 wiring (A/D+ and B/D- connections).
- Confirm Modbus communication parameters (baud rate, parity, device address) match between the module and your Modbus master.
- Ensure no other devices on the RS485 bus have the same address.
- Incorrect Temperature Readings:
- Check if K-type thermocouples are correctly connected with the right polarity.
- Ensure thermocouples are functioning correctly and are within their specified measurement range.
- Verify the module's working environment is within -30~+55°C and 0-95%RH.
- Module Not Responding: Disconnect power, wait a few seconds, and then reconnect power to perform a soft reset. If the issue persists, re-check all wiring and configuration.
9. Maintenance
- Cleaning: Keep the module clean and free from dust and debris. Use a soft, dry cloth for cleaning. Avoid using harsh chemicals or solvents.
- Environmental Conditions: Ensure the module operates within its specified working environment (-30~+55°C / 0-95%RH) to prolong its lifespan.
- Connection Checks: Periodically inspect all wiring connections for tightness and signs of wear or corrosion.
- Firmware Updates: Check the manufacturer's website for any available firmware updates that may improve performance or add new features.
10. Warranty and Support
For warranty information, technical support, or service inquiries, please contact your vendor or the manufacturer directly. Ensure you have your product model number (CWT-TM-16TC) and purchase details available when seeking assistance.