1. Introduction
The GEYA GYL9 A-SI Type Time Delayed RCD RCCB ELCB is an electromagnetic residual current circuit breaker designed for enhanced electrical safety. This device provides protection against earth leakage currents, ensuring safety in various electrical installations. This manual provides essential information for the safe and effective installation, operation, and maintenance of your GYL9 A-SI Type RCCB.

Figure 1: GEYA GYL9 A-SI Type RCD RCCB ELCB (2P and 4P models)
2. Key Features
- Earth-Leakage Protection Class: Type A-SI (Super Immunised)
- Tripping Characteristics: Ensures tripping for sinusoidal, alternating residual currents, and pulsed DC residual currents (quickly applied or slowly increasing).
- Nuisance Tripping Prevention: Designed to avoid unwanted tripping due to polluted networks, lightning effects, high-frequency currents, RF waves, etc., by incorporating a small tripping delay (80ms~500ms).
- Rated Current Options: Available in 25A, 40A, 63A, 80A, 100A.
- Poles: Available in 2-Pole and 4-Pole configurations.
- Rated Sensitivity: 30mA.
- Rated Voltage: AC230/400V.
- Breaking Capacity: 6KA.
- Standard: IEC61008-1.
- Certification: CE.

Figure 2: Type A-SI RCD Features

Figure 3: Type SI RCD Features
3. Technical Specifications

Figure 4: Electrical Features and Installation Specifications
| Feature | Value |
|---|---|
| Rated Current | 25A, 40A, 63A, 80A, 100A |
| Poles | 2P, 4P |
| Rated Voltage Ue | 2P: 230V~; 4P: 400V~ |
| Insulation Voltage Ui | 500V |
| Rated Frequency | 50/60Hz |
| Rated Sensitivity IΔn | 0.03A (30mA) |
| Rated Residual Making and Breaking Capacity IΔm | 500 (IΔn=25-40A), 630 (IΔn=63A) |
| Short-circuit Current Inc=IΔc | 10000A |
| SCPD Fuse | ≤10000 |
| Break Time Under IΔn | ≤0.1S |
| Rated Impulse Withstand Voltage (1.2/50)Uimp | 6000V |
| Dielectric Test Voltage at Ind. Freq. for 1min | 2.5KV |
| Electrical Life and Mechanical Life | 4000 cycles |
| Pollution Degree | 2 |
| Feature | Value |
|---|---|
| Fault Current Indicator | NO |
| Protection Class | IP20 |
| Ambient Temperature (with daily average ≤35°C) | -5 ~ +40°C |
| Storage Temperature | -25 ~ +70°C |
| Terminal Connection Type | Cable/U-type busbar/Pin-type busbar |
| Terminal Size Top/Bottom for Cable | 35mm² |
| Tightening Torque | 3.5 N•M |
| Mounting | On DIN rail FN 60715 (35mm) by means of fast clip device |
| Connection | From top and bottom |
| Neutral Position | Left |

Figure 5: Detection Waveform Type and Classification
4. Installation and Setup
Installation of the GYL9 A-SI Type RCCB should only be performed by a qualified electrician in accordance with local electrical codes and regulations.
4.1 Mounting
The device is designed for mounting on a 35mm DIN rail (FN 60715) using its fast clip device. Ensure the DIN rail is securely installed before mounting the RCCB.

Figure 6: Mounting & Dimension Diagram (Dimensions in mm)
4.2 Wiring Connections
Connections can be made from both the top and bottom terminals. The neutral position is on the left. Use copper wires with the nominal section area specified in Table 3 for optimal performance and safety. Ensure all connections are tight with a tightening torque of 3.5 N•M.

Figure 7: Connection Table
| Rated Current | Nominal Section Area of Copper Wire (mm²) |
|---|---|
| 1~6A | 1 |
| 10A | 1.5 |
| 16, 20A | 2.5 |
| 25A | 4 |
| 32A | 6 |
| 40, 50A | 10 |
| 63A | 16 |
| 80A | 25 |
| 100A | 35 |
5. Operation
The GYL9 A-SI Type RCCB operates automatically to detect and interrupt earth leakage currents. It features a test button for periodic verification of its functionality.
5.1 Test Button
A 'Test Monthly' button is located on the front of the device. Pressing this button simulates an earth leakage fault and should cause the RCCB to trip, disconnecting the circuit. This confirms the internal mechanism is functioning correctly.

Figure 8: Front View of 2P Model with Test Button
6. Maintenance
Regular maintenance is crucial to ensure the continued reliable operation of your GYL9 A-SI Type RCCB.
- Monthly Test: Press the 'Test Monthly' button at least once a month. If the device does not trip, it may be faulty and should be replaced immediately by a qualified professional.
- Visual Inspection: Periodically inspect the device for any signs of physical damage, discoloration, or loose connections.
- Cleaning: Keep the device clean and free from dust and debris. Use a dry, soft cloth for cleaning. Do not use abrasive cleaners or solvents.
7. Troubleshooting
If your GYL9 A-SI Type RCCB is not functioning as expected, consider the following:
- Device Does Not Trip During Monthly Test: This indicates a fault within the RCCB. The device must be replaced by a qualified electrician.
- Frequent Nuisance Tripping: While the A-SI type is designed to minimize nuisance tripping, persistent issues might indicate:
- A genuine, intermittent earth leakage fault in the circuit.
- High levels of electrical noise or transient currents in the installation that exceed the device's immunity.
- Incorrect wiring or an overloaded circuit.
- Device Does Not Reset: If the RCCB trips and cannot be reset, there is likely a persistent earth leakage fault in the circuit. Do not attempt to force the reset. Disconnect all loads and try resetting. If it still trips, contact a qualified electrician to identify and rectify the fault.
8. User Tips
- Understanding Poles: The GYL9 A-SI Type RCCB is available in 2-Pole and 4-Pole configurations. Ensure you have the correct number of poles for your specific electrical system (e.g., 2-Pole for single-phase, 4-Pole for three-phase with neutral).
- Installation Environment: The device is rated IP20, meaning it is protected against solid objects over 12.5mm but has no protection against liquids. Ensure it is installed in a dry environment, free from excessive dust or moisture.
- Temperature Considerations: Operate the device within the specified ambient temperature range of -5°C to +40°C. Extreme temperatures can affect performance.
9. Warranty and Support
For detailed warranty information and technical support, please refer to the official GEYA documentation. A comprehensive user manual in PDF format is available for download. You can access the PDF manual at GEYA GYL9 A-SI Type RCCB User Manual (PDF).
10. Company Overview
GEYA Electric, established in 2007, is a private-owned enterprise specializing in the research, manufacturing, and sales of low-voltage electrical and automatic controlling products. The company is committed to top quality and constant innovation, utilizing advanced numerical control machines and fully automated process lines to ensure steady and stable production quality.
Video 1: GEYA Company Introduction and Manufacturing Process

Figure 9: GEYA Company Information and Certifications