GEYA GYL9 A-SI Type RCCB

GEYA GYL9 A-SI Type Time Delayed RCD RCCB ELCB Electromagnetic Circuit Breaker User Manual

Model: GYL9 A-SI Type RCCB

1. Introduction

The GEYA GYL9 A-SI Type Time Delayed RCD RCCB ELCB is an electromagnetic residual current circuit breaker designed for enhanced electrical safety. This device provides protection against earth leakage currents, ensuring safety in various electrical installations. This manual provides essential information for the safe and effective installation, operation, and maintenance of your GYL9 A-SI Type RCCB.

GEYA GYL9 A-SI Type RCD RCCB ELCB 2P and 4P models

Figure 1: GEYA GYL9 A-SI Type RCD RCCB ELCB (2P and 4P models)

2. Key Features

  • Earth-Leakage Protection Class: Type A-SI (Super Immunised)
  • Tripping Characteristics: Ensures tripping for sinusoidal, alternating residual currents, and pulsed DC residual currents (quickly applied or slowly increasing).
  • Nuisance Tripping Prevention: Designed to avoid unwanted tripping due to polluted networks, lightning effects, high-frequency currents, RF waves, etc., by incorporating a small tripping delay (80ms~500ms).
  • Rated Current Options: Available in 25A, 40A, 63A, 80A, 100A.
  • Poles: Available in 2-Pole and 4-Pole configurations.
  • Rated Sensitivity: 30mA.
  • Rated Voltage: AC230/400V.
  • Breaking Capacity: 6KA.
  • Standard: IEC61008-1.
  • Certification: CE.
Diagram illustrating Type A-SI RCD features for sinusoidal and pulsed DC residual currents

Figure 2: Type A-SI RCD Features

Diagram illustrating Type SI RCD features for avoiding nuisance tripping

Figure 3: Type SI RCD Features

3. Technical Specifications

Table of Electrical Features and Installation Specifications

Figure 4: Electrical Features and Installation Specifications

Table 1: Electrical Features
FeatureValue
Rated Current25A, 40A, 63A, 80A, 100A
Poles2P, 4P
Rated Voltage Ue2P: 230V~; 4P: 400V~
Insulation Voltage Ui500V
Rated Frequency50/60Hz
Rated Sensitivity IΔn0.03A (30mA)
Rated Residual Making and Breaking Capacity IΔm500 (IΔn=25-40A), 630 (IΔn=63A)
Short-circuit Current Inc=IΔc10000A
SCPD Fuse≤10000
Break Time Under IΔn≤0.1S
Rated Impulse Withstand Voltage (1.2/50)Uimp6000V
Dielectric Test Voltage at Ind. Freq. for 1min2.5KV
Electrical Life and Mechanical Life4000 cycles
Pollution Degree2
Table 2: Installation Specifications
FeatureValue
Fault Current IndicatorNO
Protection ClassIP20
Ambient Temperature (with daily average ≤35°C)-5 ~ +40°C
Storage Temperature-25 ~ +70°C
Terminal Connection TypeCable/U-type busbar/Pin-type busbar
Terminal Size Top/Bottom for Cable35mm²
Tightening Torque3.5 N•M
MountingOn DIN rail FN 60715 (35mm) by means of fast clip device
ConnectionFrom top and bottom
Neutral PositionLeft
Table showing Detection Waveform Type and Classification for AC, A, and A-SI types

Figure 5: Detection Waveform Type and Classification

4. Installation and Setup

Installation of the GYL9 A-SI Type RCCB should only be performed by a qualified electrician in accordance with local electrical codes and regulations.

4.1 Mounting

The device is designed for mounting on a 35mm DIN rail (FN 60715) using its fast clip device. Ensure the DIN rail is securely installed before mounting the RCCB.

Mounting and dimension diagram for GYL9 A-SI Type RCCB

Figure 6: Mounting & Dimension Diagram (Dimensions in mm)

4.2 Wiring Connections

Connections can be made from both the top and bottom terminals. The neutral position is on the left. Use copper wires with the nominal section area specified in Table 3 for optimal performance and safety. Ensure all connections are tight with a tightening torque of 3.5 N•M.

Connection table showing recommended nominal section area of copper wire for various rated currents

Figure 7: Connection Table

Table 3: Recommended Wire Sizes
Rated CurrentNominal Section Area of Copper Wire (mm²)
1~6A1
10A1.5
16, 20A2.5
25A4
32A6
40, 50A10
63A16
80A25
100A35

5. Operation

The GYL9 A-SI Type RCCB operates automatically to detect and interrupt earth leakage currents. It features a test button for periodic verification of its functionality.

5.1 Test Button

A 'Test Monthly' button is located on the front of the device. Pressing this button simulates an earth leakage fault and should cause the RCCB to trip, disconnecting the circuit. This confirms the internal mechanism is functioning correctly.

Front view of GEYA GYL9 A-SI Type RCCB 2P model showing the 'Test Monthly' button

Figure 8: Front View of 2P Model with Test Button

6. Maintenance

Regular maintenance is crucial to ensure the continued reliable operation of your GYL9 A-SI Type RCCB.

  • Monthly Test: Press the 'Test Monthly' button at least once a month. If the device does not trip, it may be faulty and should be replaced immediately by a qualified professional.
  • Visual Inspection: Periodically inspect the device for any signs of physical damage, discoloration, or loose connections.
  • Cleaning: Keep the device clean and free from dust and debris. Use a dry, soft cloth for cleaning. Do not use abrasive cleaners or solvents.

7. Troubleshooting

If your GYL9 A-SI Type RCCB is not functioning as expected, consider the following:

  • Device Does Not Trip During Monthly Test: This indicates a fault within the RCCB. The device must be replaced by a qualified electrician.
  • Frequent Nuisance Tripping: While the A-SI type is designed to minimize nuisance tripping, persistent issues might indicate:
    • A genuine, intermittent earth leakage fault in the circuit.
    • High levels of electrical noise or transient currents in the installation that exceed the device's immunity.
    • Incorrect wiring or an overloaded circuit.
    Consult a qualified electrician to diagnose the cause.
  • Device Does Not Reset: If the RCCB trips and cannot be reset, there is likely a persistent earth leakage fault in the circuit. Do not attempt to force the reset. Disconnect all loads and try resetting. If it still trips, contact a qualified electrician to identify and rectify the fault.

8. User Tips

  • Understanding Poles: The GYL9 A-SI Type RCCB is available in 2-Pole and 4-Pole configurations. Ensure you have the correct number of poles for your specific electrical system (e.g., 2-Pole for single-phase, 4-Pole for three-phase with neutral).
  • Installation Environment: The device is rated IP20, meaning it is protected against solid objects over 12.5mm but has no protection against liquids. Ensure it is installed in a dry environment, free from excessive dust or moisture.
  • Temperature Considerations: Operate the device within the specified ambient temperature range of -5°C to +40°C. Extreme temperatures can affect performance.

9. Warranty and Support

For detailed warranty information and technical support, please refer to the official GEYA documentation. A comprehensive user manual in PDF format is available for download. You can access the PDF manual at GEYA GYL9 A-SI Type RCCB User Manual (PDF).

10. Company Overview

GEYA Electric, established in 2007, is a private-owned enterprise specializing in the research, manufacturing, and sales of low-voltage electrical and automatic controlling products. The company is committed to top quality and constant innovation, utilizing advanced numerical control machines and fully automated process lines to ensure steady and stable production quality.

Video 1: GEYA Company Introduction and Manufacturing Process

GEYA Company Information including establishment year, turnover, headquarters, product range, and certifications

Figure 9: GEYA Company Information and Certifications

Related Documents - GYL9 A-SI Type RCCB

Preview GEYA Miniature Circuit Breakers, Contactors, and Transfer Switches Catalog | Technical Specifications
Comprehensive catalog from GEYA detailing Miniature Circuit Breakers (MCB), Residual Current Circuit Breakers (RCCB), Residual Current Circuit Breakers with Overcurrent Protection (RCBO), Molded Case Circuit Breakers (MCCB), AC Contactors, Automatic Transfer Switches, and Intelligent Circuit Breakers. Includes technical specifications, scope of application, product features, and compliance information for various models, serving industrial, commercial, and residential applications.
Preview GEYA Electrical Equipment Catalog - Circuit Breakers, Contactors, and More
Comprehensive catalog of GEYA electrical products including miniature circuit breakers, contactors, transfer switches, and other safety equipment, detailing specifications, applications, and compliance standards.
Preview GEYA GRD9L-W WiFi Controlled MCB/RCCB/RCBO: Instruction Manual & Technical Guide
Comprehensive instruction manual and technical guide for the GEYA GRD9L-W WiFi-controlled MCB/RCCB/RCBO. Covers applications, features, technical specifications, installation, networking, troubleshooting, and dimension details for intelligent electrical systems.
Preview GEYA WiFi Series Intelligent Miniature Circuit Breaker - Operating Instructions
Detailed operating instructions and FAQs for the GEYA WiFi Series Intelligent Miniature Circuit Breaker (ZJSB9 series). Learn about installation, setup, troubleshooting, safety, and application for smart home electrical protection.
Preview GEYA Low Voltage Electrical Products Catalog | Industrial Control Integration
Comprehensive catalog of GEYA low voltage electrical appliances and automation control products, including circuit breakers, relays, contactors, timers, and more. Featuring industrial control integration solutions.
Preview GEYA GRD9L-W WiFi Controlled MCB/RCCB/RCBO: Instruction Manual & Technical Guide
Detailed instruction manual for the GEYA GRD9L-W WiFi-controlled MCB/RCCB/RCBO. Covers applications in intelligent household electricity management and photovoltaic systems, function features, technical parameters, panel and wiring diagrams, installation, networking setup with Tuya Smart app, common faults, and dimensions. Essential guide for safe and efficient electrical control.