SHANGSIMOUDLECX HXDSBOXAI

Digital Analog Input Display Meter User Manual

Model: HXDSBOXAI Series

1. Introduction

The SHANGSIMOUDLECX HXDSBOXAI series is a versatile digital display meter designed to work with various sensors that provide analog output. It can display actual physical quantities such as temperature, frequency, motor speed, pressure, liquid level, and concentration.

This instrument supports both current and voltage input signals. It is pre-configured to adapt to standard inputs like 0-10V, 2-10V, 0-20mA, and 4-20mA. Users can also configure bias and gain parameters to adapt to other analog inputs within the 0-10V or 0-20mA range.

By default, the display shows values as a percentage. The display range can be customized using parameters F0-2 to F0-4. Models equipped with an RS485 interface facilitate communication between multiple meters for networked display solutions.

2. Main Features

  • Model Variants:
    • Standard Version: HXDSBOXAI-NR
    • With RS485 Version: HXDSBOXAI-485
    • With Relay Output Version: HXDSBOXAI-RL
  • Power Supply:
    • Standard and RS485 Versions: DC 6-25V (Power consumption: 24V/40mA)
    • Relay Output Version: DC 8-25V (Power consumption: 24V/50mA)
    • Features anti-reverse connection and surge protection.
  • Analog Input: One analog input, selectable as voltage type or current type.
  • Input Impedance: >30kΩ for voltage input, <250Ω for current input.
  • User Interface: Rich parameter settings accessible via integrated buttons. Features a 0.56-inch 4-digit digital tube display.
  • Communication (RS485 Version): Supports standard Modbus-RTU protocol for easy networking and multi-display setups.
  • Relay Output (Relay Output Version): Includes 1 normally open relay output with a load capacity of 3A30VDC/3A250VAC.
  • Physical Dimensions: Mechanical size: 79×43×25mm; Installation opening: 76.5×39.5mm.

3. Specifications

3.1. General Specifications

  • Display: 0.56 inch, 4-digit digital tube
  • Input Signal Types: 0-10V, 2-10V, 0-20mA, 4-20mA (configurable)
  • Operating Temperature: Not specified, typically industrial standard.
  • Storage Temperature: Not specified.

3.2. Port Signal Description

SignalExplanation
PWRConnect to the positive pole of the power supply (Standard/RS485: DC6~30V; Relay Output: DC8~30V)
GNDPower and signal ground
AiAnalog input signal (voltage type)
mACurrent-type analog input signal configuration interface. Short-circuit with Ai for current-type input.
485-RS485 signal negative (for 'with RS485 version' only)
485+RS485 signal positive (for 'with RS485 version' only)
KARelay normally open contact output port (for 'with relay output version' only)
KBRelay normally open contact output port (for 'with relay output version' only)

4. Setup and Wiring

4.1. Physical Installation

The meter has mechanical dimensions of 79×43×25mm and requires an installation opening of 76.5×39.5mm. Ensure proper ventilation and avoid locations with excessive heat, moisture, or vibration.

4.2. Wiring Diagrams

Refer to the following diagrams for common wiring configurations:

Wiring diagrams for Voltage input, Current input, and Two-wire current sensor
Figure 4.1: Common Wiring Diagrams
This image illustrates three wiring configurations: Voltage input (PWR, GND, Ai, mA, KA, KB terminals, with 0-10V input and 24V power for KA/KB), Current input (PWR, GND, Ai, mA, 485+, 485- terminals, with 4-20mA input and Modbus connection), and a Two-wire current sensor wiring example (PWR, GND, Ai, NC, NC terminals, with 4-20mA sensor and 24V power). Ensure correct polarity and terminal connections.

4.3. Back Panel Overview

Back panel of the digital display meter showing model number HXDSBOXAI-NR and wiring diagram
Figure 4.2: Back Panel with Wiring Diagram
This image shows the back of the HXDSBOXAI-NR model, featuring the model name and a detailed wiring diagram for power (6-25V), ground, analog input (0-10V or 0/4-20mA), and optional RS485 connections. The terminals are labeled PWR, GND, Ai, mA, NC, NC, 485+, 485-.

5. Operation and Menu Navigation

5.1. Front Panel Controls

Front panel diagram of the digital display meter showing SET, Up, Down, and OK buttons, and R, T, S indicator lights
Figure 5.1: Front Panel Diagram
The front panel features a digital display and four control buttons: SET, Up arrow, Down arrow, and OK. Indicator lights R, T, and S are also visible. R and T indicate RS485 communication (Receive and Transmit), while S indicates relay closure (for relay output versions).

5.2. Indicator Lights

  • R (Receive): Only for 'with RS485 version'. Indicates communication data reception.
  • T (Transmit): Only for 'with RS485 version'. Indicates communication data transmission.
  • S (Status): Only for 'with relay output version'. Illuminates when the relay is closed.

5.3. Menu Navigation and Parameter Adjustment

Menu navigation flowchart for the digital display meter
Figure 5.2: Menu Navigation Flowchart
This diagram illustrates the menu navigation: From the 'Monitor menu' (displaying F0-1 value), press and hold SET for 2 seconds to enter the 'First level menu' (F0---). Press OK to enter the 'Secondary menu' (F0-0), then OK again for the 'Three level menu' (parameter value). Use Up/Down arrows to modify parameter values. Press OK to save and return to the previous menu (parameter number automatically increments). Press SET to return to the previous menu without saving. Long pressing the Up Up arrow icon or Down Down arrow icon buttons allows for rapid adjustment of values.

Special Note: In the third-level menu, pressing OK saves the modified parameter value and returns to the previous menu, automatically incrementing the parameter number. Pressing SET directly returns to the previous menu without saving changes. Long pressing the Up or Down buttons allows for quick adjustment of values.

6. Parameter Description

6.1. F0 Attendant Array Display

ParameterParameter NameScope and DescriptionDefaultsRead/Write
F0-0Collected value monitoringMonitors the percentage of the current analog input value. Range: 0-100.0%Read-only
F0-1Display value monitoringThe display value in "Monitoring Menu" is calculated by F0-0, F0-2~F0-4.Read-only
F0-2Display accuracyThe number of decimal places displayed in the "Monitor Menu", range: 0-3.1Read/Write
F0-3Show minimumIn the "Monitoring Menu", the value corresponding to "acquisition value" is 0%. Range: -1999~99990Read/Write
F0-4Show maximumIn the "Monitoring Menu", the value corresponding to the "Acquisition Value" is 100.0%. Range: 1999~99991000Read/Write
F0-5Offline status0: Not disconnected; 1: Disconnected. (Disconnection detection is set by F1-4) (starting from V2.10)Read-only

6.2. F1 Parameter Group - Analog Configuration Parameters

ParameterParameter NameScope and DescriptionDefaultsRead/Write
F1-0Input type selection0: 0~10V or 0~20mA corresponds to 0~100.0%; 1: 2~10V or 4~20mA corresponds to 0~100.0%, and 0 when it is lower than 2V or 4mA.0Read/Write
F1-1Input filter timeAnalog input filter time, range: 0~10.000s. Longer time means stronger filtering.0.200Read/Write
F1-2Input gainRange: 0~1000.0%.100.0Read/Write
F1-3Input offset-99.9~99.9%, with 10V or 20mA as 100.0%.0.0Read/Write
F1-4Drop detection thresholdRange: 0.0-100.0%. This value is based on 0-10V or 0-20mA as 0.0-100.0% as a reference (and F1-0 and gain offset are not related). Detection is not started if less than 0.5, with a hysteresis of ±0.3. When input signal is lower than this value, meter displays E.oFL. (Starting from V2.10)0.0Read/Write
F1-5Enter the parameter setting selection0: Long press SET button for 3s to enter parameter setting mode; 1: Keep pressing SET button for more than 3s, and press OK to enter parameter setting mode.0Read/Write

Analog Input Calculation: The adjustment result is calculated as: (collected value + offset) × gain. The result is limited to 0.0% to 100.0%. Values greater than 100.0% are capped at 100.0%, and values less than 0.0% are set to 0.0%.

6.3. F2 Parameter Group - Relay Output Dosing (for 'with Relay Output version' only)

ParameterParameter NameScope and DescriptionDefaultsRead/Write
F2-0Relay output status configurationWhen output conditions are met: 0: No control (always open); 1: Relay closed; 2: Relay open (not satisfied, closed on condition)0Read/Write
F2-1Condition type0: Greater than comparison value 1; 1: Less than comparison value 2; 2: Greater than comparison value 1 AND less than comparison value 2.0Read/Write
F2-2Comparison value 1Range: 0-100.0%50.0Read/Write
F2-3Comparison value 2Range: 0-100.0%50.0Read/Write
F2-4Hysteresis intervalPrevents frequent relay operation near comparison value. Range: 0.0%~80.0%.5.0Read/Write
F2-5Relay status when offlineWhen F1-4 offline condition is met, the relay output state. Priority over comparison relay output. 0: Not used; 1: Relay closed; 2: Relay disconnected (starting from V2.10)0Read/Write

Hysteresis Interval Example: If F2-1 is "greater than comparison value 1", F2-2 is 50.0%, and F2-4 (hysteresis) is 5.0%. When the collected value increases and exceeds 50.0% + 5.0%/2, the output condition is met. If the value then decreases, it must fall below 50.0% - 5.0%/2 to cease the output condition.

6.4. F7 Communication Parameters and Software Version (for 'with RS485 version' only)

ParameterParameter NameScope and DescriptionDefaultsRead/Write
F7-0Local addressRange: 1~2471Read/Write
F7-1Baud rate0: 1200bps; 1: 2400bps; 2: 4800bps; 3: 9600bps; 4: 19200bps; 5: 38400bps3Read/Write
F7-2Data Format0: 8,1, None (8 data bits, 1 stop bit, no parity); 1: 8,1, Even (8 data bits, 1 stop bit, even parity); 2: 8,1, Odd (8 data bits, 1 stop bit, odd parity); 3: 8,2, None (8 data bits, 2 stop bits, no parity)0Read/Write
F7-3Response delayCommunication response delay time 0~500ms5Read/Write
F7-4Communication type0: Display table is Modbus slave, user host can read collected values; 1: Display table is network slave between tables, receives data from master; 2: Display table is network host between tables, sends display value via broadcast; 3: Display table is network host between tables, sends display value via address polling (range 1~F70 value). (Use above V1.02)0Read/Write
F7-5Parameter recoverySet to 111 to restore parameters to factory settings; other values are invalid.1313Read-only
F7-6Model codeModule model code 0521H0.1
F7-7Send interval timeThe interval time for the host to send data during master-slave communication. Range: 0.1~100.0sRead/Write
F7-8Software version numberModule software version number, two decimal places. E.g., 1.00 corresponds to v1.00.Read-only

7. Communication Protocol (for 'with RS485 communication version' only)

7.1. User Host Access to Collected Value

The communication utilizes the standard Modbus-RTU protocol. Use the multi-read instruction 03H to read data. The returned parameter value is an integer, representing the display value of the digital tube with the decimal point removed. For example, if the F0-0 digital tube displays 60.0, the communication will read 600. Modbus register addresses correspond directly to parameters (e.g., F7-2 corresponds to Modbus address 0702H).

Example: Reading F0-0 and F0-1 parameters (with default F7 parameters):

Host SendsValueSlave (HXDSBOXAI) ResponseValue
Slave address (F7-0)01HSlave address (F7-0)01H
Modbus function number03HModbus function number03H
Start address (high byte)00HReturns the number of bytes (4 bytes)04H
Start address (low byte)00HHigh byte of address content (F0-0)02H
Read word count (high byte)00HLow byte of the content of 000 address (F0-0)58H
Read word count (low byte)02HHigh byte of 0001H address content (F0-1)02H
CRC (low byte)C4HLow byte of 0001H address content (F0-1)58H
CRC (high byte)0BHCRC (low byte)7AH
CRC (high byte)C2H

In this example, the read F0-0 and F0-1 values are 0258H = 600, meaning the collected value F0-0 is 60.0% and the displayed value F0-1 is 60.0.

7.2. Networking Between Tables

The RS485 interface allows for networking multiple display meters. A master meter can transmit its collected data to slave meters for display. A network can only have one master table but multiple slave tables. Only the master table needs to have its display range configured; slave tables do not require this.

7.2.1. Broadcast Mode Network Diagram (F7-4 = 2)

RS485 broadcast mode network diagram
Figure 7.1: Broadcast Mode Network Diagram
This diagram shows a 'Primary table' (master) with F7-0=3 and F7-4=3, connected via an RS485 total line to three 'From table' (slave) units, each with F7-0=1 and F7-4=1. In this mode, the master broadcasts data to all slaves.

Advantages of Broadcast Mode: Simple setup with fewer parameters. All slave meters only need to set one parameter (F7-4 = 1). Fast networking.

7.2.2. Address Polling Network Diagram (F7-4 = 3)

RS485 address polling network diagram
Figure 7.2: Address Polling Network Diagram
This diagram shows a 'main table' (master) with F7-4=2, connected via an RS485 total line to three 'From table' (slave) units, each with F7-4=1. In this mode, the master polls each slave individually for data.

Advantages of Address Polling: Each slave display table can return data, allowing for network connectivity verification via the master meter's receiving indicator. However, each meter requires individual parameter settings.

7.3. Operating as a Modbus-RTU Display Slave (Applicable to V1.02 and above)

Set parameter F7-4 to 1. In this mode, parameters F0-1 (register address 01H) and F0-2 (register address 02H) can be modified using Modbus-RTU 06H and 10H commands. The meter's display will no longer be associated with analog quantity collection. The device address is set by the F7-0 parameter.

Example (assuming F7-0 = 1, F7-4 = 1):

  • Writing 16.88 data to the meter (F0-1 is 1688, F0-2 is 2): The meter will display 16.88 upon reception.
    Host sends: 01 10 00 01 00 02 04 06 98 00 02 32 C5
    Table response: 01 10 00 01 00 02 10 08
  • Setting F0-2 to 1 (one decimal place) and writing 1234 to register 01 (F0-1): The meter will display 123.4.
    Host send (06H write): 01 06 00 01 04 D2 5A 97
    Table response (06H write): 01 06 00 01 04 D2 5A 97
    OR
    Host send (10H write): 01 10 00 01 00 01 02 04 D2 25 1C
    Table response (10H write): 01 10 00 01 00 01 50 09

8. User Tips

  • Configuration: Many users inquire about configuration. Always refer to the parameter tables (F0, F1, F2, F7) and the menu navigation flowchart (Figure 5.2) for precise adjustments.
  • Analog Sensor Compatibility: This meter is confirmed to read 4-20mA sensors. Ensure correct wiring as per Figure 4.1 and configure F1-0 for the appropriate input type.
  • Manual Adjustment: Displayed numbers can be manually increased or decreased using the Up and Down arrow buttons during parameter setting. Long-press for faster changes.
  • Offline Status: If the meter displays 'E.oFL', check the input signal against the F1-4 drop detection threshold.

9. Troubleshooting

  • No Display/Incorrect Reading:
    • Verify power supply connections (PWR, GND) and ensure voltage is within the specified range for your model.
    • Check analog input wiring (Ai, mA) for correct polarity and connection.
    • Ensure F1-0 (Input type selection) is correctly set for your sensor (0-10V, 2-10V, 0-20mA, or 4-20mA).
    • If using current input, confirm that Ai and mA terminals are short-circuited.
    • Check F1-2 (Input gain) and F1-3 (Input offset) parameters if the displayed value is incorrect but the input signal is present.
  • 'E.oFL' Displayed: This indicates an offline status. Check the input signal level. If it falls below the F1-4 (Drop detection threshold) value, this error will appear.
  • Relay Not Activating (Relay Output Version):
    • Verify F2-0 (Relay output status configuration) is set to 1 (Relay closed) or 2 (Relay open) as desired.
    • Check F2-1 (Condition type), F2-2 (Comparison value 1), and F2-3 (Comparison value 2) to ensure the conditions for relay activation are met.
    • Consider the F2-4 (Hysteresis interval) which prevents rapid switching.
    • If F2-5 (Relay status when offline) is configured, an offline condition might override normal relay operation.
  • RS485 Communication Issues (RS485 Version):
    • Check RS485 wiring (485+, 485-) for correct polarity and secure connections.
    • Ensure F7-0 (Local address), F7-1 (Baud rate), and F7-2 (Data Format) match the settings of your Modbus master device.
    • Observe the R and T indicator lights on the front panel to confirm data transmission and reception.
    • If networking multiple meters, ensure F7-4 (Communication type) is correctly set for master/slave roles.
  • Parameter Reset: If configuration becomes problematic, you can restore factory settings by setting F7-5 to 111.

10. Maintenance

  • Cleaning: Use a soft, dry cloth to clean the display and casing. Do not use abrasive cleaners or solvents.
  • Environmental Conditions: Operate the device within its specified environmental limits to ensure longevity. Avoid exposure to extreme temperatures, humidity, or corrosive environments.
  • Firmware Updates: Check the manufacturer's website for any available firmware updates. Follow instructions carefully if performing an update.
  • Regular Checks: Periodically inspect wiring connections for looseness or damage.

11. Warranty and Support

For warranty information, technical support, or service inquiries, please contact your retailer or the manufacturer directly. Keep your purchase receipt as proof of purchase.

Related Documents - HXDSBOXAI

Preview Aideepen HXDSBOXAI Digital Display Meter - Analog Signal Input, RS485, Relay Output
Explore the Aideepen HXDSBOXAI series digital display meters. These versatile panel meters accept 0-10V, 2-10V, 0-20mA, and 4-20mA analog inputs, featuring optional RS485 communication and relay outputs. Ideal for process monitoring and control.
Preview Aideepen HXDSBOXAI Series Analog Input Digital Display Meter - Features and Specifications
Comprehensive details on the Aideepen HXDSBOXAI series analog input digital display meters, covering features, technical specifications, model variations (Standard, RS485, Relay Output), and wiring diagrams.
Preview Danfoss AMB 162, AMB 182 Operating Guide
Comprehensive operating guide for Danfoss AMB 162 and AMB 182 actuators, covering installation, wiring, configuration via DIP switches, signal types (voltage/current), LED indicators, and manual override for HVAC systems.
Preview Varia Intelligent Gas Detector by Detector Ltd. - Technical Specifications and Features
Discover the Varia, an intelligent and user-friendly gas detector developed by Detector Ltd. This document outlines its technical specifications, environmental parameters, and supported gas detection principles, highlighting its Finnish design and suitability for demanding industrial conditions.
Preview Halisense Analog to RS485 Modbus RTU Conversion Modules User Manual
Technical specifications and user guide for Halisense 2, 4, and 8-channel Analog to RS485 Modbus RTU conversion modules. Includes features, wiring diagrams, and operational parameters.
Preview ESBE ARC300 Series Actuator Electrical Settings and Operation Guide
A comprehensive guide to the electrical settings, wiring, and operational modes of the ESBE ARC300 series actuators, including ARC361, ARC363, ARC368, and ARC369 models. Covers valve and damper assembly, wiring configurations, and auxiliary switch settings for clockwise (CW) and counter-clockwise (CCW) operation.

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.