1. Introduction
Congratulations on your purchase of HK588 series true RMS Clamp Meters. This range clamp meters have been designed according to IEC-61010-2-032 concerning electronic measuring instruments with 600V CAT III and pollution 2.
This range clamp meter measures AC/DC Current, AC/DC Voltage, Resistance, Temperature, Diode Test and Continuity. The special features include NCV (non-contact Voltage) Detection, Low Pass Filter Function, Surge Function, and so on. It features a rugged design for heavy duty use. Proper use and care of this meter will provide many years of reliable service.
To fully utilize this meter, please keep this manual for reference carefully.
2. Safety Information
WARNING:
This symbol indicates that the operator must refer to an explanation in the Operating Instruction to avoid personal injury or damage to the meter.
2.1 Cautions
- Before the measurements, the meter should be preheated to 30 seconds.
- Inspect the condition of the test leads and the meter itself for any damage before operating the meter.
- Improper use of this meter can cause damage, shock, injury or death. Read and understand this user manual before operating the meter.
- Always remove the test leads before replacing the battery or fuses.
- Voltage checks on electrical outlets can be different and misreading because of the uncertainty of connection to the recessed electrical contacts. Other means should be used to ensure that the terminals are not "live".
- Use great care when making measurements if the voltages are greater 60VDC or 36V AC RMS, these voltages are considered a shock hazard.
- Always discharge capacitors and remove power from the device under test before performing Diode, Resistance or Continuity tests.
- To avoid damages to the meter, do not exceed the maximum limits of the input values shown in the specification.
- In case the device is going to be unused for an extended period of time, remove the batteries to prevent them from draining.
- When the low battery icon appears at the display, please change the new battery to avoid wrong readings.
2.2 Safety Symbols
- ▲ This symbol, adjacent to another symbol or terminal, indicates the user must refer to the manual for further information.
- ⏚ Earth ground.
- ☐ Double insulation
3. Product Overview
3.1 Controls and Jacks
Familiarize yourself with the components of your clamp multimeter:



3.2 Front Panel Description
| No. | Function | Description |
|---|---|---|
| 1 | NCV Detection | Move the rotary switch to NCV position, hold the meter once detect the voltage, meter will be alarmed and LED flash. |
| 2 | Current Clamp | Clamp the cable once measuring the current, the current reading will be displayed in LCD. |
| 3 | Flash Light | Turn on the flash light and the light bulb will be lighted. |
| 4 | NCV Indicator | Once NCV function detects the voltage, the LED indicator will twinkle. |
| 5 | Lighting Switch | Push this button to activate flash light (for HK588A & HK588B). |
| 6 | Clamp Opening Trigger | The max. jaw opening size is 23mm. |
| 7 | Rotary Switch | Move the rotary switch for selecting proper range and function. |
| 8 | Backlight Button | Hold the button for approx. 2 sec. to activate the LCD backlight, hold again for approx. 2 sec. to exit LCD backlight (for HK588A). Push the button to activate the LCD backlight, with around 30 sec to exit LCD backlight automatically (for HK588B). Push the button to activate the LCD backlight, push one more time to exit. Once rotary switch move to current measurement range, push this button can also turn on the flash light (for HK588C, HK588D & HK588E). |
| 9 | LCD Display | To display the readings of measurement. |
| 10 | Function Buttons | SEL: Function Selection Button, push the SEL to shift AC/DC, °C/°F, resistance, diode & continuity test. RAN: Manual Range Select Button, push the button to switch proper range under voltage and resistance measurement mode. HOLD: Data Hold, push the button to hold the readings in LCD, press again to exit the data hold function. MAXH: Max. Value Hold, push this button to display the max. readings of measurement, if the max. value is changed during the measurement, it is updated automatically. Hz/%: Frequency and Duty Cycle Selection Button, under AC voltage measurement, press Hz/% to selection function from voltage frequency to duty cycle. REL: Relative Value Measurement. Under DC current measurement, press this button to reset reading. Under AC current measurement, hold this button to activate Inrush Current measurement and LCD display"----", after 0.5sec to restart measurement to display max. value from approx. 80ms cycle, hold this button to exit the function. |
| 11 | Input Jack | INPUT jack for all measurements except current testing connected with red test lead; COM jack if for public terminal connect with black test lead. |
3.3 Symbols of LCD Display

| Symbol | Description | Symbol | Description |
|---|---|---|---|
| HOLD | Data Hold | Low Voltage Indication | |
| Diode Test | Continuity Check | LPF | Low Pass Filter Function |
| MAXH | Max. Value Hold | INR | Inrush Current |
| NCV | Non-Contact Voltage Detection | uA, mA, A | Unit of Current |
| mV, V | Unit of Voltage | pF, nF, µF, mF | Unit of Capacitance |
| Hz, KHz, MHz | Unit of Frequency | AC | Alternating Current |
| DC | Direct Current | °C | Centigrade Temperature |
| hFE | Transistor | °F | Fahrenheit Temperature |
| TRMS | True RMS Measurement | REL | Relative Value Measurement |
| % | Duty Cycle Measurement |
4. Setup
4.1 Battery Installation
To avoid false readings, replace the battery as soon as the low battery indicator appears.
- Turn power off and disconnect the test leads from the meter.
- Open the rear battery cover by using a screwdriver.
- Insert the battery into the battery holder, observing the correct polarity.
- Put the battery cover back in place, secure with the screws.
5. Operating Instructions
NOTE:
Read and understand all Warning and Caution statements in this operation manual prior to using this meter. Set the rotary switch to the OFF position when the meter is not in use.
5.1 Current Measurements
WARNING:
- Disconnect the test leads before making clamp measurements.
- To avoid electrical shock and/or damage to the meter, do not attempt to take any voltage measurement that might exceed 600V.
- Set the rotary switch to the proper current range, select the correct range based on measurement.
- Press the clamp opening trigger to open the jaws and fully enclose one conducting wire.
- Read the measured current value in the LCD display.
- If display shows "OL", it means overload, and you should select a higher range of measurements.
- For HK588D & HK588E: To shift between AC or DC current, press the SEL button.

5.2 DC Voltage Measurement
WARNING:
The max. input DC voltage is 600V DC. To avoid electrical shock and/or damage to the meter, do not attempt to take any voltage measurement that might exceed 600V DC.
- Set the rotary switch to the V= position.
- Insert the black test lead banana plug into the COM jack, and the red test lead banana plug into the INPUT jack.
- Touch the black test probe tip to the negative side of the circuit; touch the red test lead probe tip to the positive side of the circuit.
- Read the voltage value in the display.
NOTE: Unstable display may occur, especially at low voltage range measurement (like 200mV range), even with no test leads inserted at input terminals. This is normal and does not influence accuracy.

5.3 AC Voltage Measurement
WARNING:
The max. input DC voltage is 600V DC. To avoid electrical shock and/or damage to the meter, do not attempt to take any voltage measurement that might exceed 600V DC.
- Set the function switch to the V~ position.
- Insert the black test lead banana plug into the COM jack, and the red test lead banana plug into the INPUT jack.
- Touch the black test probe tip to the negative side of the circuit; touch the red test lead probe tip to the positive side of the circuit.
- Read the voltage value in the display.
5.4 LPF (Low Pass Filter) Measurement (for HK588A & HK588B)
WARNING:
The max. input DC voltage is 600V DC. To avoid electrical shock and/or damage to the meter, do not attempt to take any voltage measurement that might exceed 600V DC.
- Set the function switch to the LPF position.
- Insert the black test lead banana plug into the COM jack, and the red test lead banana plug into the INPUT jack.
- Touch the black test probe tip to the negative side of the circuit; touch the red test lead probe tip to the positive side of the circuit.
- Read the voltage value in the display.
5.5 Resistance Measurement
WARNING:
To avoid electric shock, disconnect power to the unit under test and discharge all capacitors before taking any resistance measurements.
- Set the function switch to the Ω position and press the SEL button to select the Ω range.
- Insert the black test lead banana plug into the COM jack, and the red test lead banana plug into the INPUT jack.
- Touch the black test probe tip to one side of the resistance under test; touch the red test probe tip to the other side.
- Read the resistance value in the display.
NOTE: To ensure the best accuracy in measurement of low resistance, short the test leads before the measurement and subtract this resistance value of the test leads.
5.6 Diode Test
WARNING:
To avoid electric shock, disconnect power to the unit under test and discharge all capacitors before taking diode test.
- Set the function switch to the Diode Test position and press the SEL button to choose diode test mode.
- Insert the black test lead banana plug into the COM jack, and the red test lead banana plug into the INPUT jack.
- Place the red test lead on the anode of the diode and the black test lead on the cathode of the diode.
- The meter will show the approx. forward voltage of the diode. Reverse voltage will indicate OL.
5.7 Continuity Check
WARNING:
To avoid electric shock, disconnect power to the unit under test and discharge all capacitors before taking continuity check.
- Set the function switch to the Continuity Check position and press the SEL button to choose continuity check mode.
- Insert the black test lead banana plug into the COM jack, and the red test lead banana plug into the INPUT jack.
- Touch the test probe tips across the circuit or component under test.
- If the resistance is <30Ω, the audible signal will be sounded.
5.8 Temperature Measurement (not for HK588A)
- Set the function switch to the °C/°F position; the value of environmental temperature shows in the display. Press the SEL button to shift between °C mode or °F mode.
- Insert the red terminal of the temperature probe (K Type) into the INPUT jack, and the black terminal into the COM jack. Place the temperature probe tip where needed to measure.
- Read the temperature on the display.
5.9 NCV (Non-Contact Voltage) Detection
WARNING:
Due to external interference sources, this function may cause wrong voltage detection. The detection result is for reference only.
Set the function switch to the NCV position. Contact the top part of the meter with the circuit under test. The indicating LED will flash and an audible signal will sound once detecting the voltage. The signal strength will be shown in the LCD display.
NOTE:
- The detection result is for reference; do not determine the voltage by NCV detection ONLY.
- Detection may be interfered by socket design, insulation thickness, and other variable conditions.
- External interference sources, such as flashlights, motors, etc., may cause wrong detection.
5.10 LINE (Live Wire Recognition) Test
Set the rotary switch to the LINE position. Connect the black test lead to the COM jack and the red test lead to the VΩ jack. Hold the insulation part of the black test lead and do not put it into the circuit under measurement. Contact the red test lead to the live wire; the buzzer of the meter will be activated and the red LED will flicker. When the red test lead connects to the earth line, the buzzer will not sound and the LED will not flicker.
NOTE: When the circuit is in serious leakage (approx. over 15V), the red test lead may cause the buzzer to sound and LED to flicker even when contacting the earth line.
5.11 Capacitance Measurement
WARNING:
To avoid electric shock, disconnect power to the unit under test and discharge all capacitors before taking capacitance measurement.
- Set the rotary switch to the Capacitance position and press the SEL button to choose the mode.
- Insert the black test lead banana plug into the COM jack, and the red test lead banana plug into the INPUT jack.
- Touch the test probe tips across the capacitance under test.
- Read the capacitance value in the display.
6. Maintenance
WARNING:
- To avoid electric shock, disconnect the test leads from any source of voltage before removing the back cover or the battery or fuse covers.
- To avoid electric shock, do not operate the meter until the battery and fuse covers are in place and fastened securely.
6.1 Cleaning and Storage
Periodically wipe the case with a damp cloth and mild detergent; do not use abrasives or solvents. If the meter is not to be used for a long time, remove the battery and store it separately.
7. Troubleshooting
- "OL" Indication: This indicates an overload condition. Select a higher measurement range if available for the current function.
- Low Battery Indicator: If the low battery icon appears on the display, replace the batteries immediately to ensure accurate readings. Refer to the "Battery Installation" section for instructions.
- Unstable Display: An unstable display may occur, especially during low voltage range measurements (e.g., 200mV range), even without test leads inserted. This is normal and does not affect accuracy.
- NCV Detection Interference: Non-Contact Voltage (NCV) detection results are for reference only. External interference sources (e.g., flashlights, motors) or environmental factors (socket design, insulation thickness) can cause inaccurate readings.
- LINE Test False Positives: In circuits with significant leakage (approx. over 15V), the LINE test buzzer and LED may activate even when the red test lead contacts the earth line.
8. Technical Specifications
8.1 General Specifications
- Operating temperature: 0~40℃ / Humidity: < 80%RH
- Storage temperature: -10~60℃ / Humidity: < 70%RH (Remove Battery)
- Maximum input voltage between input socket and the earth: 600VRMS
- Measuring principle: double integral A/D conversion
- Sampling rate: about 2 times/sec.
- Display: HK588A & HK588B: 3 1/2 LCD display, max. reading 1999; HK588C & HK588D: 3 3/4 LDC display, max. reading 3999; HK588E: 3 5/6 LCD display, max. reading 5999 (based on measuring function to show function icons into the LCD automatically)
- Range selection: auto ranging switch
- Over range indication: Once input voltage over 600VRMS, LCD indicates "OL" (DCV & ACV Range)
- Input polarity: Display "-"
- Low battery indication: Once the battery lowers the normal working voltage, the low battery icon will be displayed in LCD.
- Power Supply: DC 1.5V x 3pcs (Size AAA)
- Max jaw opening capacity: Φ23mm
- Maximum measured conductor size: Φ23mm
- Dimension: 194 x 72 x 35mm (L x W x H)
- Weight: Approx. 230g (including batteries)
- Accessories: User manual - 1pc, Test Leads - 1set, Soft carrying case - 1pc, Gift box - 1pc, Temperature probe - 1pc (not available for HK588A)
8.2 Measurement Specifications
Accuracy: ±(%readings + digit), warranty period: 12 months. Environment temperature: 18℃~28℃; humidity: ≤80%.
* Under AC current measurement, put the conductor under test in the middle of clamp for getting the accurate value.
8.2.1 AC Current
| Range | Resolution | Accuracy (HK588A) | Accuracy (HK588B) |
|---|---|---|---|
| 2A | 0.001A | ±(2.5% reading + 10 digits) | ±(2.5% reading + 10 digits) |
| 20A | 0.01A | ||
| 200A | 0.1A | LPF (-3DB@1kHz) | |
| 600A | 1A |
Frequency response: HK588A: 40~60Hz; HK588B: TRMS 40Hz-1kHz
| Range | Resolution | Accuracy (HK588C) | Accuracy (HK588D) | Accuracy (HK588E) |
|---|---|---|---|---|
| 40A/60A | 0.01A | ±(2.5% reading + 10 digits) | ±(2.5% reading + 10 digits) | ±(2.5% reading + 10 digits) |
| 400A/600A | 0.1A | |||
| 1000A | 1A |
Frequency response: TRMS 40Hz-1kHz
8.2.2 DC Current
| Range | Resolution | Accuracy (HK588D) | Accuracy (HK588E) |
|---|---|---|---|
| 40A/60A | 0.01A | ±(2.5% readings + 10 digits) | ±(2.5% readings + 10 digits) |
| 400A/600A | 0.1A | ||
| 1000A | 1A |
8.2.3 DC Voltage
| Range | Resolution | Accuracy |
|---|---|---|
| 200mV/400mV/600mV | 0.1mV | ±(0.5% reading + 3 digits) |
| 2V/4V/6V | 0.001V | ±(0.8% reading + 5 digits) |
| 20V/40V/60V | 0.01V | |
| 200V/400V/600V | 0.1V | ±(1.0% reading + 5 digits) |
| 600V/1000V | 1V |
Input impedance: 10MΩ; Max. input voltage: 600V DC / 600V AC RMS
8.2.4 AC Voltage
| Range | Resolution | Accuracy |
|---|---|---|
| 200mV/400mV/600mV | 0.1mV | ±(1.0% reading + 10 digits) |
| 2V/4V/6V | 0.001V | ±(1.0% reading + 5 digits) |
| 20V/40V/60V | 0.01V | |
| 200V/400V/600V | 0.1V | ±(1.2% reading + 5 digits) |
| 600V/750V | 1V |
Input impedance: 10MΩ; Max. input voltage: 600V DC / 600V AC RMS. LPF (low pass filter) Function: HK588A LPFACV (-3db@1kHz). Frequency response: HK588A:40~60Hz; HK588B/HK588C/HK588D/HK588E:TRMS40Hz-1kHz.
8.2.5 Resistance
| Range | Resolution | Accuracy |
|---|---|---|
| 200Ω/400Ω/600Ω | 0.1Ω | ±(1.0% reading + 10 digits) |
| 2KΩ/4KΩ/6KΩ | 0.001KΩ | ±(0.8% reading + 5 digits) |
| 20kΩ/40kΩ/60kΩ | 0.01KΩ | |
| 200kΩ/400kΩ/600kΩ | 0.1KΩ | |
| 2MΩ/4MΩ/6MΩ | 0.001MΩ | ±(2.0% reading + 10 digits) |
| 20MΩ/40MΩ/60MΩ | 0.01Ω |
Overload protection: 250V DC or 250V AC RMS
8.2.6 Diode and Continuity
| Range | Function |
|---|---|
| Diode Symbol | Display approximate forward voltage of diode, reverse shows OL. |
| Continuity Symbol | Built-in buzzer will be sounded if resistance is less than 30Ω. |
Overload protection: 250V DC or 250V AC RMS
8.2.7 Temperature (not for HK588A)
| Range | Resolution | Accuracy |
|---|---|---|
| Celsius (°C) | ||
| -20°C ~ 1000°C | 1°C | |
| -20°C ~ 0°C | ±(5% reading + 4 digits) | |
| 0℃~400℃ | ±(2% reading + 3 digits) | |
| 400°C ~ 1000°C | ±(3% reading + 3 digits) | |
| Fahrenheit (°F) | ||
| 0°F~1800°F | 1°F | |
| -0°F ~ 50°F | ±(5% reading + 4 digits) | |
| 50°F ~750°F | ±(2% reading + 3 digits) | |
| 750°F ~ 1800°F | ±(3% reading + 3 digits) | |
Overload protection: 250V DC or 250V AC RMS
8.2.8 Frequency (not for HK588A & HK588B)
| Range | Resolution | Accuracy |
|---|---|---|
| 10Hz | 0.01Hz | ±(0.5% reading + 2 digits) |
| 100Hz | 0.1Hz | |
| 1kHz | 0.001kHz | |
| 10kHz | 0.01kHz | |
| 100kHz | 0.1kHz | |
| 1MHz | 0.001MHz | |
| 10MHz | 0.01MHz |
Overload protection: 250V DC or 250V AC RMS
8.2.9 Capacitance (not for HK588A & HK588B)
| Range | Resolution | Accuracy |
|---|---|---|
| 10nF | 0.01nF | ±(4.0% reading + 25 digits) |
| 100nF | 0.1nF | |
| 1µF | 0.001µF | ±(4.0% reading + 15 digits) |
| 10µF | 0.01µF | |
| 100µF | 0.1µF | |
| 1mF | 1µF | ±(5.0% reading + 25 digits) |
| 10mF | 10µF | |
| 100mF | 100µF |
Overload protection: 250V DC or 250V AC RMS
9. User Tips
- This multimeter series is designed for ease of use, often featuring a single button to switch between functions. Take advantage of this for quick operation.
- The clear LED display enhances the user experience, making readings easy to interpret.
- The portable design, often including a carrying bag, makes it convenient for on-the-go measurements.
- Users have reported high satisfaction and reliability with this device over several months of use.
10. Warranty and Support
This product comes with a 12-month warranty period for accuracy from the date of purchase.
For detailed information, further troubleshooting, or support, please refer to the complete User Manual (PDF) available at: User Manual (PDF).
If you encounter any problems, please contact customer support. The seller aims to reply within 10 minutes during working hours and resolve issues within 24 hours.