1. Introduction
The Smartgen HGM6100N series automatic controller, encompassing models like HGM6110N and HGM6120N, is an advanced control and monitoring system designed for gensets. It integrates digital, intelligent, and network techniques to provide comprehensive functionality. This controller supports automatic start/stop operations, precise data measurement, alarm protection, and remote capabilities including remote control, remote measurement, and remote communication.
Featuring an intuitive LCD display, the HGM6100N series offers multiple language options such as Chinese, English, Spanish, Russian, Portuguese, Turkish, Polish, and French, ensuring user-friendly and reliable operation. Built with micro-processing technology, it achieves accurate measurements, value adjustments, timing, and threshold settings. All operational parameters can be configured directly from the front panel or via a PC using the USB or RS485 interface. Its compact design, straightforward connections, and high reliability make it suitable for a wide range of automatic control systems.
Product overview video of the Smartgen Genset Controller.
2. Model Variants and Characteristics
The HGM6100N series controllers are available in several variants, each offering specific functionalities:
- HGM6110N / HGM6110NC / HGM6110CAN: These are Automatic Start Modules designed to control the generator's start/stop sequence based on a remote start signal.
- HGM6120N / HGM6120NC / HGM6120CAN: Building upon the HGM6110N series, these models include additional features such as mains AC monitoring and automatic switching control between mains and generator (AMF - Automatic Mains Failure). They are particularly suited for automation systems that integrate both mains power and a genset.
Note on Communication Ports:
- HGM6110NC and HGM6120NC models are equipped with an RS485 communication port.
- HGM6110CAN and HGM6120CAN models feature a CAN communication port.
- The HGM6110N and HGM6120N models do not include RS485 or CAN ports.
3. Installation and Wiring
Proper installation and wiring are crucial for the safe and reliable operation of your Smartgen Genset Controller. Ensure all connections are secure and follow local electrical codes.
3.1 Panel Mounting
The controller is designed for panel mounting. Refer to the "Overall Dimensions" and "Panel Cutout" in the specifications section for precise measurements. Ensure a water-proof gasket is installed between the control panel and the enclosure to maintain the specified IP65 protection level.
3.2 Wiring Diagram
The following diagrams illustrate the typical wiring connections for the HGM6110N and HGM6120N series controllers. It is highly recommended to consult the full product manual for detailed wiring instructions specific to your model and application.

Figure 3.1: Rear view of HGM6110N controller showing terminal connections and inner diagram for wiring.

Figure 3.2: Rear view of HGM6120N controller showing terminal connections and inner diagram for wiring.
Key Wiring Considerations:
- Power Supply: Connect the controller to a stable DC power source within the specified working voltage range (DC8.0V to DC35.0V).
- AC System Connections: Connect the generator and mains AC inputs according to the system configuration (1P2W, 3P3W, 3P4W).
- Sensor Inputs: Connect various sensors such as rotate speed sensor, oil pressure, water temperature, fuel level, etc., to their designated auxiliary inputs.
- Relay Outputs: Connect start relay, fuel relay, and auxiliary relays to control external devices like starters, fuel solenoids, and alarms.
- Communication Ports (for NC/CAN models): If your model has an RS485 or CAN port, ensure proper connection for remote communication and PC configuration.
4. Operation
The Smartgen HGM6100N series controllers feature a user-friendly front panel for easy operation and monitoring.
4.1 Front Panel Overview

Figure 4.1: Front panel layout and indications for HGM6110N and HGM6120N series controllers.
The front panel includes an LCD display, alarm and status lamps, and various control buttons:
- LCD Display: Shows various parameters such as voltage, current, frequency, power, engine speed, and operational status.
- Alarm Lamp: Illuminates to indicate an active alarm condition.
- Status Lamp: Indicates the current operational status of the genset.
- Navigation Buttons (Up/Down/Left/Right/OK): Used to navigate menus, adjust settings, and confirm selections.
- Mode Buttons:
- Auto: Enables automatic operation mode, where the controller manages start/stop based on configured conditions (e.g., remote start signal, mains failure for HGM6120N).
- Manual: Allows manual control of the genset.
- Control Buttons:
- Start (Green): Initiates the genset start sequence in Manual mode.
- Stop (Red): Stops the genset in Manual mode or resets alarms.
- Breaker Control Buttons (Load/Mains/Genset): For models with AMF functionality (HGM6120N series), these buttons control the Load, Mains, and Genset breakers (Close/Open).
4.2 Operating Modes
- Automatic Mode: In this mode, the controller continuously monitors the system. For HGM6110N, it waits for a remote start signal. For HGM6120N, it monitors the mains supply and will automatically start the genset and transfer load upon mains failure, and stop/transfer back when mains power returns.
- Manual Mode: Allows the user to manually start and stop the genset using the dedicated Start and Stop buttons. This mode is typically used for testing or specific operational requirements.
4.3 Parameter Configuration
Parameters such as engine protection thresholds, timers, and operational logic can be configured via the front panel menu system using the navigation buttons. For more advanced configuration and diagnostics, the controller can be connected to a PC using a USB interface or, for NC/CAN models, an RS485 interface.
5. Maintenance
To ensure the longevity and optimal performance of your Smartgen Genset Controller, regular maintenance is recommended.
- Cleaning: Keep the front panel and display clean using a soft, dry cloth. Avoid abrasive cleaners or solvents.
- Connections: Periodically check all wiring connections to ensure they are tight and free from corrosion.
- Firmware Updates: Check the manufacturer's website for any available firmware updates that may improve performance or add new features.
- Environmental Conditions: Ensure the controller operates within its specified working and storage temperature and humidity ranges to prevent damage.
6. Troubleshooting
This section provides general guidance for common issues. For detailed troubleshooting, refer to the comprehensive manual provided by Smartgen.
- Alarm Lamp On: If the alarm lamp is illuminated, check the LCD display for specific alarm messages. Common alarms include low oil pressure, high water temperature, overspeed, underspeed, and emergency stop. Address the underlying cause of the alarm.
- Genset Fails to Start:
- Verify the controller is in the correct operating mode (Auto or Manual).
- Check fuel levels and battery voltage.
- Inspect all wiring connections, especially to the start and fuel relays.
- Ensure no emergency stop button is engaged.
- Incorrect Readings on Display:
- Check sensor connections and ensure they are correctly calibrated in the controller settings.
- Verify AC input connections for voltage and frequency measurements.
- Communication Issues (RS485/CAN models):
- Ensure correct wiring for the RS485 or CAN bus.
- Verify communication parameters (baud rate, parity) are correctly set on both the controller and the connected PC/device.
- Consult the RS485 protocol list for detailed communication specifications.
7. Technical Specifications
The following table outlines the key technical parameters for the Smartgen HGM6100N series controllers.

Figure 7.1: Technical Parameters for HGM6100N Series Controllers.
| Item | Contents |
|---|---|
| Working Voltage | DC8.0V to DC35.0V, continuous |
| Power Consumption | <3W (Standby mode: ≤2W) |
| AC System | |
| 3P4W | AC15V - AC360V (ph-N) |
| 3P3W | AC30V - AC620V (ph-ph) |
| 1P2W | AC15V - AC360V (ph-N) |
| 2P3W | AC15V - AC360V (ph-N) |
| AC Alternator Frequency | 50Hz/60Hz |
| Rotate speed sensor Voltage | 1.0V to 24V (RMS) |
| Rotate speed sensor Frequency | 10,000 Hz (max.) |
| Start Relay Output | 16 A DC28V at supply voltage |
| Fuel Relay Output | 16 A DC28V at supply voltage |
| Auxiliary Relay Output 1 | 7 A DC28V at supply voltage |
| Auxiliary Relay Output 2 | 7 A AC250V volt-free output |
| Auxiliary Relay Output 3 | 16 A AC250V volt-free output |
| Auxiliary Relay Output 4 | 16 A AC250V volt-free output |
| Overall Dimensions | 209mm x 166mm x 45mm |
| Panel Cutout | 186mm x 141mm |
| C.T. Secondary Current | 5A (rated) |
| Working Condition | Temperature: (-25~70)°C, Relative Humidity: (20~93)%RH |
| Storage Condition | Temperature: (-30~+80)°C |
| Protection Level | IP65, when water-proof gasket installed between control panel and enclosure. |
| Insulation Intensity | Apply AC2.2kV voltage between high voltage terminal and low voltage terminal. The leakage current is not more than 3mA within 1min. |
| Weight | 0.56kg |
8. User Tips
Based on common user inquiries and experiences, here are some helpful tips for using your Smartgen Genset Controller:
- Advanced Control via RS485: For users with HGM6110NC or HGM6120NC models, the RS485 port allows for advanced control and monitoring through Modbus. If you require specific function control via Modbus, request the RS485 protocol list from the manufacturer or seller to understand the available commands and data points.
- PC Configuration: Utilize the USB interface (or RS485 for compatible models) to connect the controller to a PC. This allows for easier and more detailed parameter adjustments and diagnostics using the Smartgen configuration software.
- Regular Checks: Perform routine visual inspections of the controller and its connections, especially in harsh environments, to preemptively identify any potential issues.
9. Warranty and Support
For warranty information, technical support, or service inquiries, please contact your authorized Smartgen dealer or the manufacturer directly. Ensure you have your product model number and purchase details available when seeking support.