1. Introduction
This manual provides essential information for the assembly, installation, operation, and maintenance of your ANERN Hybrid Solar Inverter. Please read it carefully before any installation or operation to ensure safe and efficient use.
1.1 Validity and Scope
This manual is valid for the 5KW, 6.5KW, and 12KW inverter models. It describes the unit's functions and provides guidelines for both qualified personnel and end-users.
1.2 Target Group
This document is intended for qualified persons and end-users. Qualified persons should possess knowledge of inverter operation, electrical device installation, and relevant safety standards.
1.3 Label Description
The inverter and this manual use specific symbols to alert users to important information and potential hazards:
- WARNING!: Indicates a high level of potential danger that could result in death or serious injury.
- CAUTION!: Indicates a moderate or low level of potential danger that could result in moderate or minor injuries.
Danger: High Voltage! Electrical Hazard!
Grounding: The system must be firmly grounded for operator safety.
1.4 Safety Instructions
- Ensure you understand your battery system type (lithium or lead-acid) to avoid malfunction.
- All operations and connections must be performed by professional electrical or mechanical engineers.
- Electrical installations must comply with local electrical safety standards.
- When installing PV modules during the daytime, cover them with opaque materials to prevent high terminal voltage.
- Only charge deep-cycle lead-acid or lithium rechargeable batteries. Other battery types may burst.
- Do not disassemble the unit. Refer to a qualified service center for repairs.
- Disconnect all wiring before maintenance or cleaning.
- NEVER charge a frozen battery.
- Use appropriate cable sizes as specified for optimum operation.
- Exercise caution with metal tools near batteries to prevent short circuits or explosions.
- Strictly follow installation procedures for disconnecting AC or DC terminals.
- The inverter must be connected to a permanent grounded wiring system.
- NEVER short-circuit AC output and DC input. Do NOT connect to mains when DC input is short-circuited.
- Ensure the inverter is completely assembled before operation.
1.5 System Overview
The ANERN Hybrid Solar Inverter is a multifunctional device integrating an MPPT solar charge controller, a high-frequency pure sine wave inverter, and a UPS function module. It is designed for off-grid backup power and self-consumption applications and can operate with or without batteries.
The system requires additional components like PV modules, a generator, or a utility grid for complete functionality. A built-in or plug-and-play WiFi module allows for remote monitoring via mobile app or website.

2. Installation
2.1 Unpacking and Inspection
Upon receiving the product, inspect the outer packaging for any damage. Open the box and check the internal equipment. If any damage is found, contact your local distributor immediately.
2.2 Installation Tools
The following tools are recommended for installation:
- Multi-meter
- Protective gloves
- Insulated anti-smashing shoes
- Safety glasses
- ESD wrist strap
- Hammer drill
- Electric screwdriver
- Cross screwdriver
- Rubber mallet
- Spirit level
- Wire cutter / stripper
- Terminal crimping tool
2.3 Mounting Unit
Choose a solid, non-flammable surface for mounting. Install the inverter at eye level for easy LCD display reading. Ensure the ambient temperature is between -10°C and 60°C. Maintain at least 30cm clearance on all sides for heat dissipation and wiring access.
- Drill holes using an Ø8 drilling bit with 110mm spacing. Insert M6 expansion screws.
- Align the inverter's top screw holes with the expansion screws and fix it to the wall.
- Before connecting wires, remove the bottom cover by unscrewing the four screws.

2.4 AC Input / Output Connection
WARNING! All AC wiring must be performed by qualified personnel and comply with local electrical safety standards. Install a separate AC breaker (recommended 80A) between the inverter and the AC input power source.
CAUTION! Do not mis-connect AC IN, AC OUT1, and AC OUT2 terminals. Ensure correct polarity (L and N wires) to prevent utility short-circuits in parallel operation.
Recommended AC wire gauge:
- AC OUT1 (Max 70A): 6 AWG (13.3 mm²)
- AC OUT2 (Max 40A): 10 AWG (5.26 mm²)
Steps for AC connection:
- Open the AC circuit breaker first.
- Remove 12mm insulation from cable ends, shorten conductor to 10mm, insert into tubular terminal, and crimp tightly.
- Insert AC input cables into terminal blocks according to polarities (PE: yellow-green, L: brown/black, N: blue) and tighten screws. Connect PE protective cable first.
- Ensure all cables are securely connected.
2.5 PV Connection
WARNING! Install a separate DC circuit breaker between the inverter and PV modules. Do not ground positive or negative PV terminals. Exposure to sunlight generates lethal high voltages; adhere to safety precautions. Connect PV terminals to corresponding ports on the inverter; reversing polarity can damage the inverter. All wiring must be performed by qualified personnel.
Recommended PV wire gauge: 10 AWG (5.26 mm²)
PV Module Selection Parameters:
- Max. PV Array Open Circuit Voltage: 500Vdc
- Start-up Voltage: 80Vdc
- PV Array MPPT Voltage Range: 60Vdc~450Vdc
Steps for PV connection:
- Open the DC circuit breaker first.
- Prepare cables as described for AC connection.
- Use a multi-meter to check polarities.
- Insert PV cables into terminal blocks (PV+: red, PV-: black) and tighten screws.
- Ensure cables are securely connected.
- If PV1 and PV2 are connected to the same panel string, set program 62 to enable PV parallel mode.
2.6 Battery Connection
Choose a lead-acid or lithium battery with a nominal voltage of 48V (for 6.5KW/12KW models) or 24V (for 5KW model). For lead-acid batteries, the recommended charge current is 0.3C (C ≤ battery capacity).
WARNING! Install a separate DC over-current protector or disconnect device (recommended 250A) between the battery and inverter. All wiring must be performed by qualified personnel. Ensure AC power is disconnected before connecting the battery.
Recommended battery cable and terminal size: 000 AWG (85 mm²)
Steps for Lead-acid Battery Connection:
- Unscrew pre-fixed screws on battery poles. Prepare 2 DT terminals.
- Prepare cables as described for AC connection.
- Pass battery cable through the installation hole on the bottom shell, connect to battery terminals, and tighten screws. Ensure correct polarity.
- Connect all battery packs as required. A minimum 200Ah capacity battery is suggested.
Steps for Lithium Battery Connection:
- Follow the steps for power cable connection as for lead-acid batteries.
- Connect the RJ45 terminal of the battery communication cable to the BMS communication port of the inverter (RS485 or CAN protocol).
- Insert the other end of the RJ45 cable into the battery's communication port.
Note: If using a lithium battery, ensure the BMS communication cable is connected between the battery and the inverter. Set the battery type to 'LIb' or 'FEL' in Program 17. The inverter BMS port pin assignment is as follows:
| Pin number | BMS port |
|---|---|
| 1 | RS485B |
| 2 | RS485A |
| 3 | - |
| 4 | CANH |
| 5 | CANL |
| 6 | - |
| 7 | - |
| 8 | - |
2.7 Meter Connection
The inverter can be connected to an external meter for accurate grid-tied function. The inverter interface for the meter uses RS485A and RS485B in the BMS interface. Ensure the meter model supports the inverter's communication protocol.
2.8 Final Assembly
After all wiring is complete, reattach the bottom cover by screwing in the four screws.
2.9 Smart Communication Stick Connection (Optional)
Insert the smart communication stick (WiFi) directly into the COMM port for cloud platform connectivity. Refer to the solar APP quick configuration guide for models with built-in WiFi monitoring.

3. Operation
3.1 Power ON/OFF
Once the unit is installed and batteries are connected, press the ON/OFF switch (located on the bottom of the case) to turn on the unit.
Starting Sequence:
- Turn on the battery switch.
- Start the inverter.
- Turn on the PV, mains, and load switches.
Shutdown Sequence:
- Turn off the switches for load, PV, and mains.
- Turn off the inverter.
- Finally, turn off the battery.
Attention: AC and PV inputs can only be turned on after the inverter is working, otherwise, it may be damaged easily.
3.2 Operation and Display Panel
The inverter's front panel features an LCD display, four indicators, and four function keys to show operating status and input/output power information.

LED Indicators:
| LED Indicator | State | Message |
|---|---|---|
| AC Status (Green) | Solid On | Mains power is normal and in operation. |
| Flashing | Mains power is normal, but not yet in operation. | |
| Off | Mains power is abnormal. | |
| Invert Indicator (Yellow) | Solid On | Output is powered by battery or PV. |
| Off | Other states. | |
| Charging Indicator (Yellow) | Solid On | Battery is in float charging. |
| Flashing | Battery is in constant voltage charging. | |
| Off | Other states. | |
| Fault Indicator (Red) | Solid On | Fault occurs in the inverter. |
| Flashing | Warning condition occurs in the inverter. | |
| Off | Inverter is working properly. |
Function Buttons:
| Button | Description |
|---|---|
| ESC | To exit setting mode |
| UP | To go to previous selection |
| DOWN | To go to next selection |
| ENTER | To confirm the selection in setting mode or enter setting mode |
LCD Display Icons:
The LCD displays various icons representing battery information, AC input, PV input, AC output, battery capacity, load capacity, and system status. These icons provide a quick overview of the inverter's operational state.
LCD Settings (Program Mode):
Press and hold the ENTER button for 2 seconds to enter setting mode. Use UP/DOWN to navigate programs and ENTER to confirm. ESC exits the mode.
- Program 01: Output Voltage (Adjustable: 220V, 230V, 240V)
- Program 02: Output Frequency (Adjustable: 50Hz, 60Hz)
- Program 03: Output Source Priority (Grid first, Solar first, PBG priority, MKS)
- Program 04: Input Mode (APP: Appliance, UPS, GEN)
- Program 05: Charger Source Priority (PV and Grid, Only PV, PV first)
- Program 06: Grid Charging Current (Adjustable: 2A to 160A)
- Program 07: Maximum Charging Current (Adjustable: 2A to 160A)
- Program 08: Menu Default (ON/OFF for auto-return to first page)
- Program 09: Auto Restart when Overload Occurs (ON/OFF)
- Program 10: Auto Restart when Over Temperature Occurs (ON/OFF)
- Program 11: Main Input Cut Warning (Enable/Disable Grid or PV loss alarm)
- Program 12: Energy-saving Mode (ON/OFF)
- Program 13: Overload Transfer to Bypass (ON/OFF)
- Program 14: Silent Mode Setting (Enable/Disable buzzer sound)
- Program 15: Battery Return to Grid Voltage Point (Adjustable based on battery type)
- Program 16: Switching Back to Battery Mode Voltage Points (Adjustable based on battery type)
- Program 17: Battery Type (AGM, Flooded, Lithium (Ternary), FEL (Lithium Iron), User-Defined)
- Program 18: Battery Low Voltage Alarm Setting (Adjustable based on battery type)
- Program 19: Battery Shutdown Voltage Point (Adjustable based on battery type)
- Program 20: Constant Voltage Mode Voltage Point Setting (Adjustable based on battery type)
- Program 21: Floating Charge Mode Voltage Point Setting (Adjustable based on battery type)
- Program 22: Grid Low Voltage Point Setting (Adjustable based on input mode)
- Program 23: Grid High Voltage Point Setting (Adjustable based on input mode)
- Program 24: Automatic Turn Off Backlight (ON/OFF)
- Program 25: Inverter Soft Start Setting (ON/OFF)
- Program 26: Reset Factory Setting (ON/OFF)
- Program 29: Battery Disconnection Alarm (Enable/Disable)
- Program 31: Equalization Voltage Point Setting (Adjustable: 48V to 60V)
- Program 32: Equalization Charging Time Setting (Adjustable: 5 to 900 minutes)
- Program 33: Equalization Delay Time Setting (Adjustable: 5 to 900 minutes)
- Program 34: Equalization Interval Time Setting (Adjustable: 1 to 90 days)
- Program 35: Enable Equalization Immediately (ON/OFF)
- Program 36: Grid-tie Inverter Function (Set whether inverter is grid fed or not)
- Program 37: Max Grid Tie Power (Adjustable: 0 to 12.0kW)
- Program 38: Battery Dual Output Low Voltage Shutdown Point (Adjustable: 44V to 60V)
- Program 39: Battery Dual Output Duration (Adjustable: 5 to 900 minutes or FUL for unlimited)
- Program 40: Dual Output Battery Mode Cut-off SOC (Adjustable: 5 to 90%)
- Program 44: BMS Communication Function (Enable/Disable, select protocol)
- Program 45: BMS ID (Set ID number or auto)
- Program 46: Low SOC Shutdown (Adjustable: 5 to 50%)
- Program 47: High SOC to Battery (Adjustable: 10 to 100%)
- Program 48: Low SOC to Grid (Adjustable: 10 to 90%)
- Program 61: Battery Max. Discharge Current (Adjustable: 10A to 220A)
- Program 62: PV Parallel Mode (ON/OFF)
3.3 Display Information
The LCD display cycles through various data points. You can manually switch between displays using the UP or DOWN keys. If no operation occurs for a long time, the daily PV power generation will be displayed.
- P1: Daily power generation from solar.
- P2: Total power generation from solar.
- P3: Lithium battery voltage and current (ERR if BMS communication fails or disabled).
- P4: Lithium battery temperature and SOC (ERR if BMS communication fails or disabled).
- P5: Lithium battery rated capacity and remaining capacity (ERR if BMS communication fails or disabled).
- P6: Lithium battery maximum charging voltage and minimum discharging voltage (ERR if BMS communication fails or disabled).
- P7: Lithium battery maximum charging current and maximum discharging current (ERR if BMS communication fails or disabled).
- P8: Lithium battery alarm and fault information (ERR if BMS communication fails or disabled).
- P9: Inverter firmware version.

4. Maintenance
4.1 Battery Equalization
The equalization function helps reverse the buildup of negative chemical effects like stratification and removes sulfate crystals from battery plates, which can reduce battery capacity. It is recommended to equalize batteries periodically.
Note: Do not activate this mode when using lithium batteries.
How to Apply Equalization Function:
You can enable battery equalization in Program 32 (Charging Time Setting) or choose immediate equalization in Program 35. Then, configure the following settings:
- Set equalization voltage point on Program 31.
- Set equalization charging time on Program 32.
- Set equalization delay time on Program 33.
- Set equalization interval time on Program 34.
- Set immediate equalization mode activation on Program 35.
When to Equalize:
In float stage, when the set equalization interval is reached, or equalization is active immediately, the controller will enter the Equalize stage.
During the Equalize stage, the controller charges the battery until the battery voltage reaches the equalization voltage. It then maintains constant voltage regulation. The battery remains in this stage until the set equalization time is reached.
If the battery equalization time expires and the voltage hasn't reached the set point, the charge controller will extend the time until it reaches the voltage. If the voltage is still below the set point after the extended time, the controller will stop equalization and return to the float stage.
5. Troubleshooting
5.1 Fault Reference Code
When a fault occurs, the fault indicator (red LED) is always on, and the buzzer sounds for 10 seconds then stops. The system attempts to restart automatically. If it fails after six attempts, the machine and LCD will remain in fault status. You must completely power off the unit or wait 15 minutes to restart.
Example Fault Display: EHH 18
| Fault Code | Meaning | Relevant Action | Trigger Conditions | Resume Conditions |
|---|---|---|---|---|
| 1 | Bus boost fail | Turn fault mode | Grid soft start process starts but bus voltage does not reach set value | Restore after reaching the set voltage for 15 seconds |
| 2 | Bus over voltage | Turn fault mode | Bus voltage is higher than set value | Restore after reaching the set voltage for 15 seconds |
| 3 | Bus below voltage | Turn fault mode | Bus voltage is lower than set value | Restore after 15 seconds |
| 4 | Battery over current | Turn fault mode | Battery current is higher than set value | Cannot restore |
| 5 | System over temperature | Turn fault mode | Temperature is higher than set value or fan is not connected | Restore after temperature lower than set value and fan connected for 15 minutes |
| 6 | Battery over voltage | Turn fault mode | Battery voltage is higher than set value | Restore after reaching the set voltage for 15 seconds |
| 7 | Bus soft start failed | Turn fault mode | Battery soft start process starts but the bus voltage has not reached set value | Restore after reaching the set voltage for 15 seconds |
| 8 | Bus short circuit | Turn fault mode | Bus voltage is lower than set value | Cannot restore |
| 9 | Inverter soft start failed | Turn fault mode | Inverter soft start process starts but the inverter voltage has not reached set value | Restore after reaching the set voltage for 15 seconds |
| 11 | Inverter under voltage | Turn fault mode | The inverter voltage is lower than the set value in battery mode | Restore after reaching the set voltage for 15 seconds |
| 12 | Inverter short circuit | Turn fault mode | Inverter voltage is less than the set value and current is higher than the set value | Restore after reaching the set value for 15 seconds |
| 13 | Inverter negative power | Turn fault mode | The inverter power is negative and exceeds the set value for a period of time | Restore after reaching the set value for 15 seconds |
| 14 | Over load | Turn fault mode | The load current is higher than the set value | Restore after reaching the set value for 15 seconds |
| 17 | Program updating | Turn fault mode | Inverter updating or OTA | Restore after updating |
| 18 | PV reverse connection | Turn fault mode | PV reverse connection | Restore after connecting correctly for 15 seconds |
| 26 | BMS fault | Turn fault mode | Error code in BMS message. | Restore after BMS fault resolved |
| 29 | Inverter load abnormal | Turn fault mode | Abnormal inverter load leads to abnormal voltage | Restore after voltage returning normal for 15 seconds |
5.2 Alarm Reference Code
When an alarm occurs, the red LED light flashes, and the LCD displays the alarm code. The inverter does not enter fault mode.
Example Alarm Display: ALA 52
| Alarm Code | Meaning | Relevant Action | Trigger Conditions | Resume Conditions |
|---|---|---|---|---|
| 50 | Battery open | Alarm | Battery disconnected for no more than 10 minutes | Restore after battery connected for 2 minutes |
| 51 | Battery under voltage | Alarm, battery low voltage shutdown or cannot power on | Battery voltage is lower than BAU set value | Restore after the battery voltage exceeding the BAU set value by 2V |
| 52 | Battery low voltage | Alarm | Battery voltage is lower than BAL set value | Restore after the battery voltage exceeding the BAL set value by 2V |
| 53 | Battery charge short circuit | Alarm, battery does not charge | Battery voltage is less than 24V and the charging current exists. | Restore after the short circuit is eliminated. |
| 56 | BMS loss | Alarm | Communication failure after BMS communication function is enabled | Restore after communication function disabled or communication success |
| 58 | Fan error | Alarm, fan operation in full speed | No fan speed signal detected | Restore after fan speed signal detected |
| 59 | EEPROM error | Alarm | EEPROM read/write exception | Can not restore |
| 60 | Overload | Alarm | The mains current/battery discharge current/load power is higher than the rated value. | Restore after the mains current/battery discharge current/load power is less than the rated value. |
| 62 | PV energy weak | Alarm, Turn off the PV output to the load, but keep the PV charging the battery | When the battery is not connected, the bus voltage is lower than the set value | Restore after battery connected or grid connected, or 10 minutes later. |
| 68 | Battery under SOC shutdown | Alarm, turn to standby mode | BMS reports SOC lower than BSU set value | Restore after meeting one of the following three conditions: 1. Disable low SOC shutdown function 2. Disable BMS communication function 3. SOC is higher than the set value by 5% |
| 69 | Battery below SOC warning | Alarm, if it is in standby mode, it will remain in standby mode. | Lithium battery SOC is lower than set value+5% (grid mode or battery mode), lower than set value+10% (standby mode) | Restore after meeting one of the following three conditions: 1. Disable low SOC shutdown function 2. Disable BMS communication function 3. SOC is higher than the set value by 10% |
| 72 | Battery cannot startup | Alarm | During standby, battery voltage is lower than the allowed startup voltage | Restore after the battery voltage is higher than the allowed startup voltage |
| 77 | Grid power is unstable | Alarm | Lost of grid power three times within 5 minutes | Restore after 5 mins |
| 78 | Meter Loss | Alarm | When the grid power is connected and the grid connected inverter function is set to Meter, the meter communication is disconnected | Restore after grid is disconnected, or detection device is not set to Meter, or meter communication restore |
5.3 General Troubleshooting
| Problem | Fault Event | Trigger Conditions | What to do |
|---|---|---|---|
| Unable to start | Utility power | N/A | 1. Check for any short circuits at the mains terminal. 2. Check for wiring errors, such as mistakenly connecting mains input to output. |
| PV | N/A | 1. Check if the PV input voltage is too close to the critical threshold. 2. For low voltage versions, check software version compatibility of the main control. | |
| PV not charging | N/A | N/A | Connecting the wrong battery voltage can damage the auxiliary power supply on the PV side, causing loss of power and inability to communicate with the main control. |
6. Specifications
The following tables detail the specifications for the ANERN Hybrid Solar Inverter models.
6.1 AN-FGI-S12000 Specifications
| AC Input | |
|---|---|
| Rated Input Voltage (VAC) | 220/230/240; L+N+PE |
| Voltage Range (VAC) | 90~280 (APP mode); 170~280 (UPS mode) |
| Frequency (Hz) | 50/60 (Auto Adaptive) |
| AC Output | |
|---|---|
| Rated Capacity (kW) | 12 (Max current of AC output 1 is 70A. Max current of AC output 2 is 40A) |
| Surge Power (kVA) | 24 |
| Voltage (VAC) | 220/230/240 |
| Power Factor (PF) | 1 |
| Frequency (Hz) | 50/60±0.1% |
| Switch Time (ms) | 10 (APP/UPS mode) / 20 (GEN mode) |
| WaveForm | Pure Sine Wave |
| Overload Capacity (Battery Mode) | 1min@102%~125% load, 10s@>125% load |
| Max. Efficiency (Battery Mode) | 94%@48V |
| Charger (PV/AC) | |
|---|---|
| Solar Charger Type | MPPT |
| Max PV Input Current/Power | Single PV Input: 27A/9000W, Dual PV Input: 22.5*2A/15000W |
| MPPT Range@Operating Voltage (VDC) | 60~450 |
| PV Start-up Voltage | 80Vdc |
| Max PV Open Circuit Voltage (VDC) | 500 |
| Max PV Charge Current (A) | 160 |
| Max AC Charge Current (A) | 160 |
| Max. Charge Current (PV+AC) (A) | 160 |
| Battery | |
|---|---|
| Normal Voltage (VDC) | 48 |
| Battery Type | Lithium and Lead-acid |
| General Data | |
|---|---|
| HMI | LCD |
| Interface | RS232/RS485/CAN |
| Monitoring | WiFi (Optional) |
| Ingress Protection | IP21 |
| Operating Temperature | -10°C~60°C |
| Relative Humidity | 5%~95% (Non-condensing) |
| Storage Temperature | -15°C~60°C |
| Max. Operating Altitude | 4000m (Derating above 1000m) |
6.2 AN-FGI-S6500 Specifications
| AC Input | |
|---|---|
| Rated Input Voltage (VAC) | 208/220/230/240; L+N+PE |
| Voltage Range (VAC) | 90~280 (APP mode); 170~280 (UPS mode) |
| Frequency (Hz) | 50/60 (Auto Adaptive) |
| AC Output | |
|---|---|
| Rated Capacity (kW) | 6.5 (Output Power rating will be reduced to 90% when setting the Output Voltage to 208V) |
| Surge Power (kVA) | 12 |
| Voltage (VAC) | 208/220/230/240 |
| Power Factor (PF) | 1 |
| Frequency (Hz) | 50/60±0.1% |
| Switch Time (ms) | 10 (APP/UPS mode) / 20 (GEN mode) |
| WaveForm | Pure Sine Wave |
| Overload Capacity (Battery Mode) | 1min@102%~110% load, 10s@>110% load |
| Max. Efficiency (Battery Mode) | 94%@48V |
| Charger (PV/AC) | |
|---|---|
| Solar Charger Type | MPPT |
| Max PV Input Current/Power | 27A/9000W |
| MPPT Range@Operating Voltage (VDC) | 60~450 |
| PV Start-up Voltage | 80Vdc |
| Max PV Open Circuit Voltage (VDC) | 500 |
| Max PV Charge Current (A) | 120 |
| Max AC Charge Current (A) | 120 |
| Max. Charge Current (PV+AC) (A) | 120 |
| Battery | |
|---|---|
| Normal Voltage (VDC) | 48 |
| Battery Type | Lithium and Lead-acid |
| General Data | |
|---|---|
| HMI | LCD |
| Interface | RS232/RS485/CAN |
| Monitoring | WiFi (Optional) |
| Ingress Protection | IP21 |
| Operating Temperature | -10°C~60°C |
| Relative Humidity | 5%~95% (Non-condensing) |
| Storage Temperature | -15°C~60°C |
| Max. Operating Altitude | 4000m (Derating above 1000m) |
6.3 AN-FGI-S5000 Specifications
| AC Input | |
|---|---|
| Rated Input Voltage (VAC) | 208/220/230/240; L+N+PE |
| Voltage Range (VAC) | 90~280 (APP mode); 170~280 (UPS mode) |
| Frequency (Hz) | 50/60 (Auto Adaptive) |
| AC Output | |
|---|---|
| Rated Capacity (kW) | 5 (Output Power rating will be reduced to 90% when setting the Output Voltage to 208V) |
| Surge Power (kVA) | 10 |
| Voltage (VAC) | 208/220/230/240 |
| Power Factor (PF) | 1 |
| Frequency (Hz) | 50/60±0.1% |
| Switch Time (ms) | 10 (APP/UPS mode) / 20 (GEN mode) |
| WaveForm | Pure Sine Wave |
| Overload Capacity (Battery Mode) | 1min@102%~120% load, 10s@>120% load |
| Max. Efficiency (Battery Mode) | 93.5%@24V |
| Charger (PV/AC) | |
|---|---|
| Solar Charger Type | MPPT |
| Max PV Input Current/Power | 27A/9000W |
| MPPT Range@Operating Voltage (VDC) | 60~450 |
| PV Start-up Voltage | 60Vdc |
| Max PV Open Circuit Voltage (VDC) | 500 |
| Max PV Charge Current (A) | 160 |
| Max AC Charge Current (A) | 160 |
| Max. Charge Current (PV+AC) (A) | 160 |
| Battery | |
|---|---|
| Normal Voltage (VDC) | 24 |
| Battery Type | Lithium and Lead-acid |
| General Data | |
|---|---|
| HMI | LCD |
| Interface | RS232/RS485/CAN |
| Monitoring | WiFi (Optional) |
| Ingress Protection | IP21 |
| Operating Temperature | -10°C~60°C |
| Relative Humidity | 5%~95% (Non-condensing) |
| Storage Temperature | -15°C~60°C |
| Max. Operating Altitude | 4000m (Derating above 1000m) |
7. User Tips
- Inductive Load Considerations: The starting power of inductive load electrical appliances should be at least three times their rated power. Ensure your inverter's power capacity is sufficient for the starting power of connected appliances to prevent damage.
- Batteryless Operation: Yes, the inverter can operate without a battery, powering loads directly from PV or AC sources.
- Grid Feedback: The inverter supports grid-tie functions. Excess solar energy can be fed back into the grid, depending on the selected operating mode (e.g., PGB mode).
- Optimal System Setup: For stable operation and electricity bill savings, connecting a battery is recommended. When the mode is set to SBU (Solar-Battery-Utility), the system prioritizes PV and battery power before drawing from the utility grid.
8. Warranty and Support
For any warranty claims, technical support, or repair services, please contact your local distributor or the manufacturer directly. Ensure you retain your purchase records for warranty validation.
Updates to the content and version of this manual may occur without separate notification. Always refer to the latest official documentation for the most current information.





