LCTC LC108 Digital PID Temperature Controller User Manual

Model: LC108 | Brand: LCTC

1. Introduction and Overview

The LCTC LC108 is a versatile 48x48mm LCD digital intelligent PID temperature controller designed for industrial applications. It supports multiple input types including Thermocouple (TC) and Resistance Temperature Detector (RTD), and offers various output options such as SSR, Relay, 4-20mA, and 0-10V. This controller also features RS485 Modbus communication for integration into larger control systems. Its segment LCD with high brightness backlight ensures clear readability across a wide viewing angle.

Front view of the LCTC LC108 digital PID temperature controller
Front view of the LCTC LC108 digital PID temperature controller, highlighting its multi-input and multi-output capabilities.

2. Key Features

  • Universal Input: Supports TC (K, J, E, T, S) and RTD (PT100, Cu100, Cu50) inputs, configurable via menu.
  • Multiple Output Options: Available with Relay, SSR, 0-10V, or 4-20mA control outputs.
  • Advanced Control: Features PID control (including double PID for heating/cooling), programmer control with up to 32 segments, and soft start function.
  • Display: Segment LCD with high brightness backlight and wide viewing angle.
  • High Accuracy: 0.2% F.S. (Full Scale) measurement accuracy.
  • Communication: Optional RS485 Modbus communication protocol.
  • Alarm Functions: Supports up to 2 configurable alarms.
  • Operational Modes: Manual/automatic control switching and working status indicators.
  • Analog Transmission: Optional PV: 4-20mA or PV: 0-10VDC transmission output.
Front display of LC108 showing various indicators
Front display of the LC108 controller with indicators for OP1, OP2, AU1, AU2, MAN, ATU, COM, PRG.

3. Specifications

ParameterValue
Model NumberLC108
Brand NameLCTC
Panel Size48mm x 48mm
Power Supply85~265VAC, 50~60Hz
Input TypeTC (K, E, J, T, B, S, N, R), RTD (PT100, CU50) - Multi-input
Output TypeSSR, Relay, 4-20mA, 0-10V
Alarm Output1 or 2 Alarms (configurable)
CommunicationRS485 (optional)
Transmission OutputPV: 4-20mA, PV: 0-10VDC (optional)
Accuracy0.2% F.S.
Sampling Time0.5 seconds
Display TypeDIGITAL LCD
Display Size1.9 Inches & Under
Max Measuring Temperature0-400°C (for K-type thermocouple, specific range depends on input type)
Operating Environment0-50°C, non-condensing, Humidity: <85%
CertificationCE
UseIndustrial
Diagram showing various panel sizes for temperature controllers
Panel size diagrams, including the 48x48mm dimension for the LC108.

4. Setup

4.1. Installation

The LC108 controller is designed for embedded panel mounting with a standard 48x48mm cutout. Ensure adequate space for wiring and ventilation around the unit. Secure the controller using the provided mounting brackets.

4.2. Wiring

Proper wiring is crucial for safe and correct operation. Always refer to the specific wiring diagram printed on the side of your controller for the most accurate connection details, as configurations may vary slightly based on the ordered output and communication options. The following diagrams provide general guidance.

Back view of LC108-802 controller with terminal labels
Back view of the LC108-802 model, showing terminal labels for power, input (INP1:K), and output (OP1:DC0-10V).
General connection diagram for the temperature controller
General connection diagram illustrating output relay, alarm relay, analog output, and SSR drive connections. Always refer to the sticker on your specific controller for exact details.
Detailed wiring diagrams for various controller sizes
Detailed wiring diagrams for 48x48mm, 72x72mm, and 48x96mm controllers. Note that INP2 is used for remote SV or position feedback.

Important Wiring Notes:

  • Connect the power supply (85-265VAC) to the designated terminals.
  • Connect your TC/RTD sensor to the input terminals (e.g., A, B, B+ for RTD; A, B for TC).
  • Connect your control output device (e.g., SSR, Relay, 4-20mA, 0-10V) to the corresponding output terminals.
  • If equipped with RS485, connect A+ and B- terminals to your communication network.
  • Ensure all connections are secure and correctly polarized.
  • INP2 is typically used for remote Set Value (SV) input or position feedback.

5. Operating Instructions

The LC108 controller operates primarily in PID mode for precise temperature control. Basic operation involves setting the desired temperature (Set Value, SV) and monitoring the current process temperature (Process Value, PV).

5.1. Basic Operation

  • Power On: Once wired correctly, apply power to the controller. The display will light up, showing the PV and SV.
  • SET Button: Used to enter parameter setting menus.
  • F1, F2, F3 Buttons: Typically used for navigation, increasing/decreasing values, or specific function calls depending on the menu context.
  • PV Display: Shows the current measured temperature.
  • SV Display: Shows the target temperature or set point.
LC108 display showing 26 degrees Celsius
The LC108 display showing a Process Value (PV) of 26°C and a Set Value (SV) of 0.

5.2. Advanced Functions and Configuration

The LC108 supports various advanced functions such as input type selection, output mode configuration (Relay, SSR, etc.), alarm settings, and PID parameter tuning. These functions are accessed and configured through the controller's menu system.

For detailed instructions on parameter setting, PID tuning, alarm configuration, and RS485 communication setup, please refer to the comprehensive digital manual:

Note that the controller is typically shipped in a normal PID mode. If you require specific advanced functions like Fuzzy control, Autotuning, Transmission, Remote control, LED BAR display, Motor valve control, Heat & Cool modes, Programmable segments, or Ramp & Sock functions, these may require specific configurations or models. Please ensure your ordered product supports these features and configure them as per the detailed manual.

6. Maintenance

To ensure the longevity and optimal performance of your LCTC LC108 temperature controller, follow these maintenance guidelines:

  • Cleaning: Keep the controller's front panel clean and free from dust and debris. Use a soft, dry cloth for cleaning. Avoid abrasive cleaners or solvents.
  • Environmental Conditions: Ensure the operating environment remains within the specified temperature (0-50°C) and humidity (<85%, non-condensing) ranges.
  • Connection Checks: Periodically inspect all wiring connections to ensure they are secure and free from corrosion. Loose connections can lead to erratic behavior or damage.
  • Ventilation: Ensure that the ventilation slots on the controller are not obstructed to prevent overheating.

7. Troubleshooting

If you encounter issues with your LC108 temperature controller, consider the following basic troubleshooting steps:

  • No Power/Display: Check the power supply connections and ensure the voltage is within the specified 85-265VAC range.
  • Incorrect Temperature Reading (PV): Verify that the sensor is correctly connected and that the input type configured in the controller matches your sensor (TC or RTD type). Check for damaged sensor wires.
  • No Control Output: Ensure the output type is correctly configured (e.g., Relay, SSR) and that the control parameters (SV, PID settings) are appropriate for your application. Check the wiring to the controlled device.
  • Communication Issues (RS485): Verify RS485 wiring (A+, B-), communication parameters (baud rate, parity, address), and ensure the RS485 option is enabled and correctly configured in the controller.
  • Erratic Behavior: Check for electrical noise in the environment. Ensure proper grounding and shielding of sensor and output wires.

For more detailed troubleshooting and error codes, please consult the full user manual linked in the Operating Instructions section.

8. User Tips

  • Consult the Manual: Many common questions regarding setup and advanced features are answered in the detailed user manual. It is highly recommended to download and review it for comprehensive understanding.
  • Verify Default Modes: The controller ships with a default PID mode. If you need specialized functions (e.g., Fuzzy, Autotuning, specific transmission outputs), confirm that your purchased model supports them and configure them accordingly. If you are unsure, contact customer service before making assumptions about functionality.
  • Check Wiring Carefully: Double-check all wiring against the diagram on your specific unit and the provided manual. Incorrect wiring is a frequent cause of operational problems.

9. Warranty and Support

For any technical assistance, questions regarding specific functions, or issues not covered in this manual, please contact LCTC customer support. Ensure you have your product model (LC108) and any relevant purchase information ready when contacting support.