TECNR K205-16DR K205-16DT

Contents

Kinco K205-16DR/K205-16DT PLC CPU Module User Manual

Programmable Logic Controller for Industrial Applications

1. Introduction

This manual provides detailed instructions for the installation, operation, and maintenance of the Kinco K205-16DR and K205-16DT PLC CPU modules. These modules are part of the K2 series, designed as cost-effective and compact programmable logic controllers for various industrial automation tasks. They feature a DC24V power supply, 16 I/O points (including 6 Digital Inputs, 6 Digital Outputs, and 4 Digital Input/Output points), and two RS485 communication ports.

The K2 series PLCs are known for their convenience, offering a USB programming port that also allows for USB debugging power. The patented DIO reuse technology enhances application flexibility, allowing the same physical points to function as either inputs or outputs without complex configuration.

2. Safety Information

Please read and understand all safety instructions before installing, operating, or performing maintenance on the Kinco K205 PLC module. Failure to follow these instructions may result in personal injury, equipment damage, or improper operation.

  • Ensure the power supply is disconnected before performing any wiring or maintenance.
  • Only qualified personnel should install and service this equipment.
  • Verify correct wiring connections to prevent damage to the PLC or connected devices.
  • Do not operate the PLC in environments exceeding its specified temperature, humidity, or vibration limits.
  • Protect the device from moisture, dust, and corrosive gases.
  • Use appropriate personal protective equipment (PPE) during installation and troubleshooting.

3. Product Overview

The Kinco K205 PLC CPU module is a compact and versatile controller. Below are key features and visual representations of the device.

3.1 Key Features

  • USB Programming Port: MicroUSB port for programming and debugging, compatible with standard mobile phone data cables. Can also power the module for debugging.
  • DIO Reuse Technology: Patented technology allowing certain I/O points to be configured as either Digital Inputs (DI) or Digital Outputs (DO) without complex wiring changes.
  • High-Speed Counting Input: Four channels for high-speed counting, supporting single-phase, double-phase (Up/Down), and AB phase (1x/4x frequency) counting. Max frequency for CPU205 is 50KHz.
  • High-Speed Pulse Output: Three channels (Q0.0, Q0.1, Q0.4) supporting PTO (Pulse Train Output) and PWM (Pulse Width Modulation) modes. Max output frequency for CPU205 is 50KHz.
  • RS485 Communication: Two RS485 serial communication ports (PORT1 and PORT2) with baud rates up to 115.2kbps. PORT1 supports programming, Modbus RTU slave, and free communication. PORT2 supports Modbus RTU master/slave and free communication.
  • Real-Time Clock: Integrated real-time clock for time-based operations.
  • Compact Design: Space-saving form factor for easy installation in control cabinets.

3.2 Module Views

Front view of the Kinco K205-16DT PLC CPU module
Figure 1: Front view of the Kinco K205-16DT PLC CPU module, showing status indicators (Run, Stop, Com, Err) and I/O terminals.
Top view of the Kinco K205-16DT PLC
Figure 2: Top view of the Kinco K205-16DT PLC, showing the I/O terminals and ventilation slots.
Bottom view of the Kinco K205-16DT PLC
Figure 3: Bottom view of the Kinco K205-16DT PLC, displaying model number, power source (24VDC 5W MAX), and certifications (CE, RoHS).
Side view of the Kinco K205-16DT PLC
Figure 4: Side view of the Kinco K205-16DT PLC, highlighting its compact form factor and mounting points.

4. Specifications

4.1 Technical Specifications

Technical Specifications table for Kinco CPU205, CPU204, and CPU209 series
Figure 5: Technical Specifications table for Kinco CPU205, CPU204, and CPU209 series, detailing supply voltage, DI/DO/DIO/AI/AO points, high-speed counter, high-speed output, port types, and installation size.

For the K205-16DR and K205-16DT models, refer to the CPU205 column in the table above. Key specifications include:

  • Supply Voltage: DC24V
  • Digital Inputs (DI): 6 points
  • Digital Outputs (DO): 6 points (K205-16DR: Relay, K205-16DT: Transistor)
  • Digital Input/Output (DIO): 4 points
  • Analog Inputs (AI): None
  • Analog Outputs (AO): None
  • High-Speed Counter: Single phase, 2*Max 50KHz, 2*Max 20KHz; Two phase, 2*Max 50KHz, 2*Max 10KHz.
  • High-Speed Output: None
  • Ports: 2*RS485, Max 115.2kbps

4.2 Mechanical Dimensions

Mechanical dimensions diagram for the CPU205 series PLC
Figure 6: Mechanical dimensions diagram for the CPU205 series PLC, showing front, side, and top views with measurements in millimeters.
  • Installation Size (L×W×H): 90 × 97 × 70 mm

4.3 Package Information

  • Package Length: 10 cm
  • Package Width: 23 cm
  • Package Height: 10 cm
  • Package Weight: 0.32 kg

5. Installation

Proper installation is crucial for the reliable operation of the PLC module. Follow these steps carefully:

5.1 Mounting

  • The K205 PLC is designed for DIN rail mounting. Ensure the DIN rail is securely fastened within the control cabinet.
  • Mount the PLC vertically to allow for proper heat dissipation through the ventilation slots.
  • Maintain adequate clearance around the module for air circulation and ease of wiring.

5.2 Wiring

All wiring should be performed with the power supply disconnected. Use appropriate wire gauges for power and I/O connections.

5.2.1 Power Supply Wiring

  • Connect a stable DC24V power supply to the designated power terminals (24V and 0V) on the PLC module.
  • Ensure the power supply can provide sufficient current for the PLC and any connected loads.

5.2.2 Digital I/O Wiring (K205-16DT - Transistor Output)

Wiring diagram for the Kinco K205-16DT PLC
Figure 7: Wiring diagram for the Kinco K205-16DT PLC, illustrating connections for RS485 (PORT1, PORT2), DC24V power, digital inputs (DI), and digital outputs (DIO). Solid lines indicate source input; Dotted lines indicate sink input.
  • Digital Inputs (DI): Connect input devices (e.g., sensors, switches) to the 'I' terminals (0.0 to 1.1). The diagram shows both source and sink input configurations.
  • Digital Outputs (DO/DIO): Connect output devices (e.g., relays, indicators) to the 'Q' terminals (0.0 to 1.1). The K205-16DT uses transistor outputs. The DIO points can be used as DI or DO based on wiring.

5.2.3 Digital I/O Wiring (K205-16DR - Relay Output)

Wiring diagram for the Kinco K205-16DR PLC
Figure 8: Wiring diagram for the Kinco K205-16DR PLC, illustrating connections for RS485 (PORT1, PORT2), DC24V power, digital inputs (DI), and digital outputs (DIO). Solid lines indicate source input; Dotted lines indicate sink input.
  • Digital Inputs (DI): Similar to K205-16DT, connect input devices to 'I' terminals.
  • Digital Outputs (DO/DIO): Connect output devices to 'Q' terminals. The K205-16DR uses relay outputs, suitable for higher current loads. The DIO points can be used as DI or DO based on wiring.

5.2.4 RS485 Communication Wiring

  • Connect RS485 devices to PORT1 (A, B) and PORT2 (A, B, GND) terminals as shown in the wiring diagrams (Figure 7 and Figure 8).
  • Ensure correct polarity (A to A, B to B) for communication.
  • For long-distance communication, consider using shielded twisted-pair cables and proper termination resistors.

6. Initial Setup and Programming

After physical installation and wiring, the PLC needs to be configured and programmed.

6.1 Software Installation

  • Install the Kinco PLC programming software (e.g., KincoBuilder) on your computer. Refer to the software's documentation for installation instructions.
  • Ensure the necessary USB drivers are installed for communication with the PLC.

6.2 Connecting to the PLC

  • Connect your computer to the PLC's MicroUSB programming port using a compatible USB cable.
  • The PLC can be powered via the USB port for debugging purposes, or by its DC24V power supply.
  • Open the programming software and establish a connection with the PLC. Select the correct COM port if prompted.

6.3 Programming Basics

  • Create a new project in the programming software and select the K205 series PLC model.
  • Develop your control logic using Ladder Diagram (LD) or other supported programming languages.
  • Configure I/O points, timers, counters, and other functions as required by your application.
  • For DIO points, their function (DI or DO) is determined by the wiring and how they are used in the program.
  • Configure high-speed counters and pulse outputs according to your application's needs, specifying modes (single-phase, two-phase, AB phase) and frequencies.
  • Set up RS485 communication parameters (baud rate, data bits, stop bits, parity, protocol type - Modbus RTU master/slave or free communication) for each port.
  • Download the compiled program to the PLC.

7. Operating Instructions

Once programmed, the PLC operates autonomously based on the loaded control logic.

7.1 PLC Status Indicators

The front panel of the PLC features LED indicators:

  • Run: Lit when the PLC is in Run mode and executing the program.
  • Stop: Lit when the PLC is in Stop mode.
  • Com: Flashes during active communication via the serial ports.
  • Err: Lit or flashes to indicate a system error or program error. Refer to the programming software for detailed error codes.

7.2 Modes of Operation

  • Run Mode: The PLC executes the loaded program, reads inputs, processes logic, and updates outputs.
  • Stop Mode: The PLC halts program execution. Outputs are typically de-energized or held in a safe state. This mode is used for programming, debugging, or maintenance.

7.3 High-Speed Functions

  • High-Speed Counter: Monitor and count pulses from encoders or other high-frequency sensors. The programming software allows configuration of counting modes and interrupt triggers.
  • High-Speed Pulse Output: Generate precise pulse trains for controlling stepper motors, servo drives, or other devices requiring high-frequency signals. Use PTO for positioning control and PWM for speed or intensity control.

7.4 Serial Communication

  • The RS485 ports enable communication with other industrial devices (e.g., HMIs, VFDs, sensors) using protocols like Modbus RTU.
  • Ensure the communication parameters (baud rate, address) match between the PLC and the connected devices.

8. Maintenance

Regular maintenance helps ensure the longevity and reliable operation of your Kinco K205 PLC module.

  • Cleaning: Periodically clean the exterior of the PLC module with a soft, dry cloth. Do not use solvents or abrasive cleaners. Ensure ventilation slots are free from dust and debris.
  • Environmental Conditions: Verify that the operating environment remains within the specified temperature and humidity ranges. Avoid exposure to direct sunlight, excessive vibration, and corrosive atmospheres.
  • Wiring Inspection: Periodically check all wiring connections for tightness and signs of damage or corrosion. Loose connections can lead to intermittent operation or failures.
  • Firmware Updates: Check the Kinco website for any available firmware updates for your PLC model. Follow the provided instructions carefully when performing updates.
  • Backup Programs: Regularly back up your PLC programs to prevent data loss in case of module replacement or system failure.

9. Troubleshooting

This section provides solutions to common issues you might encounter with your Kinco K205 PLC module.

Problem Possible Cause Solution
PLC does not power on (no LEDs lit)
  • No power supply
  • Incorrect wiring
  • Faulty power supply
  • Check DC24V power connection.
  • Verify power wiring polarity.
  • Test power supply voltage.
ERR LED is lit or flashing
  • Program error
  • Hardware fault
  • Configuration error
  • Connect to programming software to read error code and diagnose.
  • Check for short circuits or overloads on outputs.
  • Review program logic and hardware configuration.
Cannot connect to PLC via USB
  • Incorrect USB cable
  • Missing/outdated USB drivers
  • Incorrect COM port selection
  • Use a standard MicroUSB data cable.
  • Install/update Kinco USB drivers.
  • Check Device Manager for correct COM port and select it in software.
RS485 communication failure
  • Incorrect wiring (A/B polarity)
  • Mismatched communication parameters
  • Device address conflict
  • Verify A/B connections.
  • Ensure baud rate, data bits, stop bits, parity match all devices.
  • Check for unique device addresses on the network.

10. User Tips

  • When using the USB port for debugging, ensure your computer's USB port can supply sufficient power, especially if the PLC is not connected to its main DC24V supply.
  • Take advantage of the DIO reuse feature to simplify wiring and reduce the number of different module types needed for your application.
  • For high-speed counting and pulse output, always refer to the specific programming software documentation for detailed configuration examples and best practices.
  • Consider using a dedicated industrial-grade USB cable for programming in noisy environments to ensure stable communication.

11. Warranty and Support

For warranty information, technical support, or service inquiries, please contact your authorized Kinco distributor or the seller directly. Keep your purchase receipt and product serial number handy when contacting support.

This product is certified with CE, indicating compliance with European safety, health, and environmental protection requirements.

© 2023 Kinco. All rights reserved.