KKMOON DY517

Contents

DY517 Digital Manifold Gauge HVAC Instruction Manual

Model: DY517

1. Introduction

The DY517 intelligent electronic refrigerant group instrument is an auxiliary tool designed for the installation, testing, and maintenance of refrigeration equipment, including air conditioners and cold storage systems. This instrument features double pressure testing, dual temperature measurement capability (requires separate test clips), digital readout, multi-unit switching, various operational modes, and a built-in refrigerant database. Constructed with high-strength engineering plastics and a flexible non-slip silicone design, the unit is robust and comfortable to handle. It incorporates a 32-bit digital processing unit and a high-accuracy data acquisition unit, ensuring stable and precise data. The large liquid crystal display with backlight support provides clear and easy-to-read data, facilitating operation in various lighting conditions. Its long-life valve switch and 1/4-inch standard interface design ensure durability and versatility.

DY517 Digital Manifold Gauge with application examples

Figure 1: DY517 Digital Manifold Gauge in various HVAC applications.

2. Safety Information

This instrument is designed and produced according to EC/EN61010-1 safety standards. Please read and adhere to the following safety precautions before use:

  • The pressure measured by this digital manifold pressure tester is gauge pressure.
  • Pressure testing ranges from -101 Kpa to 6 Mpa (-0.1 bar to 60 bar).
  • The limit pressure is 10 Mpa (100 bar).
  • The maximum operating pressure of a standard hose is 600 PSI (approximately 4.13 Mpa, 41.3 bar). The limit pressure is 3000 PSI (approximately 20.68 Mpa, 206.8 bar).
  • Always confirm the rated pressure value of the equipment being tested before proceeding. Do not use the instrument if the pressure exceeds its specified range.
  • Do not use or store the instrument in environments with high temperature, high humidity, flammable or explosive atmospheres, or strong electromagnetic fields.
  • Do not attempt to modify the instrument's internal circuitry, as this may cause damage to the instrument or pose a danger to the user.
  • Always wear qualified protective equipment to ensure user safety during testing.
  • Use the instrument in a well-ventilated environment to prevent the inhalation of toxic gases.

3. Product Features

The DY517 Digital Manifold Gauge offers a range of advanced features for comprehensive HVAC system analysis:

  • Dual Measurement: Simultaneously measures double pressure (gauge pressure) and supports dual temperature measurement (with optional test clips).
  • Unit Conversion: Automatic multi-unit pressure conversion (Kpa, Mpa, bar, inHg, PSI) and temperature conversion (°C / °F).
  • Refrigerant Database: Built-in database of 89 types of refrigerant pressure-evaporation temperatures (NIST standard), allowing for direct reading of subcooling and superheat values.
  • Vacuum Measurement: Tests percentage of relative vacuum.
  • Leak Detection: Features pressure leak measurement and records leak time speed.
  • High Accuracy: Built-in 32-bit digital processing unit and high-accuracy data acquisition unit ensure reliable and stable readings.
  • User-Friendly Display: Large LCD with backlight for clear data display and easy readability in various conditions.
DY517 Digital Manifold Gauge product features checklist

Figure 2: Key product features of the DY517 Digital Manifold Gauge.

DY517 Digital Manifold Gauge button function display

Figure 3: Detailed view of the DY517's buttons, display, and ports.

4. Specifications

ParameterValue
Pressure Test TypeGauge Pressure
Pressure Test Range0 Kpa – 6000 Kpa
Pressure Test Resolution1 Kpa
Pressure Test Accuracy+/- 0.5 % + 5dgt
Pressure Overload Limit10000 Kpa (10 Mpa, 100 bar)
Pressure Test UnitsKpa; Mpa; bar; inHg; PSI.
Vacuum Test TypeRelative Vacuum
Vacuum Test Range-101 Kpa – 0 Kpa
Vacuum Test Resolution1 Kpa
Vacuum Test UnitsKpa; Mpa; bar; inHg; PSI.
Temperature Test Units°C (Celsius), °F (Fahrenheit)
Temperature Test Range-40°C – 150°C (-40°F – 302°F)
Temperature Test Resolution0.1°C (-40°C–99.9°C), 1°C (100°C–150°C)
0.1°F (-40°F–99.9°F), 1°F (100°F–302°F)
Temperature Test Accuracy+/- 0.5 °C + 2dgt / +/- 0.9 °F + 2dgt
Built-in Refrigerants89 kinds (according to American NIST standard)
Power Supplies4 x 1.5V AA / LR6 Batteries (not included)
Instrument Size170 x 110 x 50 mm (6.7 x 4.3 x 2.0 in)
Package Weight950g (2.09 lb)
DY517 Digital Manifold Gauge with specifications overlay

Figure 4: DY517 highlighting its high data accuracy and stability.

DY517 Digital Manifold Gauge showing vacuum test range

Figure 5: Vacuum test range and resolution displayed on the DY517.

5. Setup

5.1 Battery Installation

  1. Locate the battery compartment on the back of the unit.
  2. Open the battery cover.
  3. Insert four (4) 1.5V AA/LR6 batteries, ensuring correct polarity.
  4. Close the battery cover securely.
Back view of DY517 showing battery compartment area

Figure 6: Rear view of the DY517, indicating the battery compartment location.

5.2 Connecting Hoses and Probes

Refer to Figure 3 for port locations.

  1. Pressure Hoses: Connect your low-pressure hose to the 1/4 inch low pressure inlet (blue valve) and your high-pressure hose to the 1/4 inch high pressure inlet (red valve).
  2. Refrigerant/Vacuum Pump: Connect the central hose to the refrigerant inlet/vacuum pump inlet.
  3. Temperature Probes (Optional): If performing temperature measurements, connect compatible clamp-on temperature probes to the designated clamp-on temperature probe sockets. Note: Test clips are not included with the standard package.

6. Operating Instructions

6.1 Power On/Off

  • Press the Power button (Power button icon) to turn the unit ON.
  • Press and hold the Power button to turn the unit OFF.

6.2 Unit Selection

  • Press the UNIT button to cycle through pressure units: Kpa, Mpa, bar, inHg, PSI.
  • Press the °C/°F button to switch between Celsius and Fahrenheit for temperature display.

6.3 Zeroing

  • Before taking measurements, ensure all valves are closed and the system is at atmospheric pressure.
  • Press the ZERO button to zero the pressure readings.

6.4 Function Selection

  • Press the FUN button to cycle through different measurement modes (e.g., pressure, vacuum, temperature, subcooling/superheat calculation).

6.5 Refrigerant Type Selection

  • Use the R+ and R- buttons to select the appropriate refrigerant type from the built-in database for accurate subcooling/superheat calculations.

6.6 Backlight

  • Press the Backlit button (Backlight button icon) to turn the LCD backlight ON or OFF.

6.7 Run/Stop Function

  • The Run/Stop button allows you to pause or resume data acquisition, useful for recording stable readings or analyzing specific points in time.
DY517 Digital Manifold Gauge measuring double pressure

Figure 7: The DY517 is capable of measuring double pressure (gauge pressure).

7. Maintenance

7.1 Cleaning

  • Wipe the instrument with a soft, damp cloth. Do not use abrasive cleaners or solvents.
  • Ensure no moisture enters the ports or battery compartment.

7.2 Battery Replacement

  • Replace batteries when the low battery indicator appears on the display or if the unit fails to power on.
  • Always replace all four batteries simultaneously with new ones of the same type (1.5V AA/LR6).
  • Remove batteries if the instrument will not be used for an extended period to prevent leakage.

7.3 Storage

  • Store the instrument in a cool, dry place, away from direct sunlight and extreme temperatures.
  • Avoid storing in high humidity, flammable, explosive, or strong electromagnetic environments.
  • Keep the instrument in its original packaging or a protective case to prevent physical damage.

8. Troubleshooting

ProblemPossible CauseSolution
Instrument does not power onDead or incorrectly installed batteriesReplace batteries with new 1.5V AA/LR6 batteries, ensuring correct polarity.
Inaccurate pressure readingsUnit not zeroed; faulty hose connection; sensor issueEnsure unit is zeroed before measurement. Check hose connections for leaks. If problem persists, contact support.
Temperature readings are incorrect or absentTemperature probes not connected or faulty; incorrect refrigerant selectedEnsure temperature probes are securely connected and functional. Verify the correct refrigerant type is selected using R+/R- buttons.
Display is dim or flickeringLow battery; extreme temperatureReplace batteries. Operate the instrument within its specified temperature range.

9. User Tips

  • Accessory Awareness: Please note that essential accessories such as pressure hoses, temperature clamp sensors, and a protective carrying case are typically sold separately and are not included with the base unit. Plan your purchase accordingly.
  • Temperature Probes: The dual temperature test feature requires separate test clips (temperature probes) which are not included in the standard package. Ensure you acquire these if temperature measurement is critical for your application.
  • Pre-Test Check: Always perform a quick check of hose connections and zero the gauge before starting any measurement to ensure accuracy.

10. Warranty & Support

For warranty information, technical support, or service inquiries, please refer to the documentation provided at the time of purchase or contact the manufacturer/seller directly. Keep your purchase receipt as proof of purchase.

© 2023 KKMOON. All rights reserved.

Documents and downloads

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.