AT HG140

Contents

HG140 Industrial Cabinet Heater Instruction Manual

Model: HG140 Series

1. Introduction

The HG140 Series Semiconductor Heaters are designed for use in electrical enclosures and control cabinets. Their primary function is to prevent damage caused by condensation and to ensure that the internal temperature does not fall below a critical minimum value. The heater features an anodized aluminum profile body that utilizes a chimney effect for even heat distribution. Its pressure clamp connectors are designed for quick and simplified installation.

Two HG140 semiconductor heaters, one vertical and one horizontal, showcasing their design.
Figure 1: HG140 Semiconductor Heater units.

2. Safety Instructions

Please read these safety instructions carefully before installation and operation. Failure to comply may result in injury or damage to the product.

  • Installation and maintenance should only be performed by qualified personnel.
  • Ensure the power supply is disconnected before any installation or maintenance work.
  • The heater must be earthed (Protection Class I).
  • Do not operate the heater in environments with explosive gases or vapors.
  • Ensure proper ventilation around the heater to prevent overheating.
  • Do not touch the heater surface during operation, as it can reach high temperatures.
  • Use appropriate wire sizes and terminals as specified in the technical data.

3. Technical Specifications

FeatureSpecification
Operating Voltage120-240V AC/DC (min. 110V, max. 265V)
Heating ElementPTC resistor, self-regulating and temperature limiting
Heater BodyExtruded aluminum profile, anodized
Connection3 pressure clamps for stranded wire 0.5-1.5mm² (with wire end ferrule) and rigid wire 0.5-2.5mm²
Connection CasingPlastic according to UL94 V-0, black
MountingClip for 35mm DIN rail, EN 50022
Fitting PositionVertical
Operating/Storage Temperature-45 to +70 °C (-49 to +158 °F)
Protection Type/ClassIP20 / I (earthed)
CertificationsCE, FCC, RoHS, VDE + UL File No. E150057

Model Variants and Performance

Art. No.Heating CapacityInrush Current Max.Length (L)Weight (approx.)
14000.0-0015W1.5A65mm0.30kg
14001.0-0030W3.0A65mm0.30kg
14003.0-0045W3.5A65mm0.30kg
14005.0-0060W2.5A140mm0.40kg
14006.0-0075W4.0A140mm0.50kg
14007.0-00100W4.5A140mm0.50kg
14008.0-00150W9.0A220mm0.70kg

*Operating with voltages below 140V AC/DC reduces heating performance by approximately 10%.

*Heating capacity measured at 20°C (68°F) ambient temperature.

Dimensional drawing of the HG140 heater with measurements in millimeters.
Figure 2: HG140 Heater Dimensions (all measurements in mm).

4. Installation

4.1 Mounting

The HG140 heater is designed for quick and secure installation on a 35mm DIN rail (EN 50022). It must be installed in a vertical position to ensure optimal heat distribution via the chimney effect.

  • Ensure the mounting surface is stable and can support the heater's weight.
  • Snap the heater onto the 35mm DIN rail using the integrated clip fixing mechanism.
  • Verify that the heater is securely fastened and oriented vertically.
Close-up of the DIN rail mounting groove and snap spring mechanism on the heater.
Figure 3: Rail mounting groove with snap spring for secure installation.

4.2 Electrical Connection

The heater uses 3 pressure clamp connectors for electrical wiring.

  • Before connecting, ensure the power supply is completely off.
  • Use stranded wires of 0.5-1.5mm² (with wire end ferrule) or rigid wires of 0.5-2.5mm².
  • Press the terminal to insert the wire, ensuring a strong and secure connection.
  • Connect the Line (L), Neutral (N), and Ground (PE) wires according to the wiring diagram.
Close-up of the heater's terminal block with instructions to press the terminal for stronger wiring.
Figure 4: Pressure clamp terminals for electrical connection.
Wiring diagram showing the connection of the HG140 heater to a thermostat. L (Line), N (Neutral), and Ground connections are indicated.
Figure 5: Example wiring diagram for the HG140 heater with an external thermostat.

5. Operation

The HG140 heater utilizes PTC (Positive Temperature Coefficient) heating technology, which provides self-regulating and temperature-limiting properties. This means the heater will dynamically adjust its power output to maintain a stable temperature, preventing overheating and ensuring energy efficiency.

  • Once correctly installed and wired, apply power to the circuit.
  • The heater will begin to warm up, distributing heat evenly within the enclosure.
  • For precise temperature control, it is recommended to use an external thermostat (as shown in the wiring diagram).
  • The heater operates within a wide voltage range of 120-240V AC/DC.
Graphic illustrating PTC heating with an upward arrow and temperature symbols, indicating high temperature protection.
Figure 6: PTC heating with high temperature protection.

6. Maintenance

The HG140 heater is designed for low maintenance. However, periodic checks are recommended to ensure optimal performance and longevity.

  • Power Disconnection: Always disconnect power before performing any maintenance.
  • Cleaning: Periodically clean the aluminum profile to ensure efficient heat dissipation. Use a soft, dry cloth. Do not use abrasive cleaners or solvents.
  • Connection Check: Inspect electrical connections for tightness and signs of wear or corrosion. Re-tighten if necessary.
  • Visual Inspection: Check the heater body for any physical damage.
  • Ventilation: Ensure that the air circulation around the heater is not obstructed.

7. Troubleshooting

ProblemPossible CauseSolution
Heater not warming upNo power supply; Loose electrical connection; Faulty heater.Check power source and circuit breaker; Verify all connections are secure; Test heater with a multimeter (if qualified) or replace.
Insufficient heatingAmbient temperature too low for heater wattage; Heater wattage too low for enclosure size; Operating voltage below 140V AC/DC.Ensure correct wattage for application; Consider a higher wattage model; Verify operating voltage.
Heater overheatingObstructed ventilation; Incorrect installation position.Clear any obstructions around the heater; Ensure vertical installation and adequate spacing.

If the problem persists after attempting these solutions, please contact customer support.

8. User Tips

  • Energy Efficiency: The PTC heating element is self-regulating, which helps save energy by only drawing the necessary power to maintain the set temperature.
  • Quick Installation: The DIN rail clip fixing and pressure clamp connectors are designed for rapid and straightforward setup, minimizing installation time.
  • Condensation Control: For optimal condensation prevention, ensure the heater is sized correctly for your enclosure volume and humidity levels.
  • Thermostat Integration: Pairing the heater with an external thermostat allows for precise temperature management and further energy savings.

9. Warranty and Support

This product is covered by a standard manufacturer's warranty against defects in materials and workmanship. For warranty claims or technical support, please contact your point of purchase or the manufacturer directly. Keep your purchase receipt as proof of purchase.

For further assistance, please refer to the contact information provided by the seller or manufacturer.

Documents and downloads

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.