GEYA GRD9L-R Auto Recloser Instruction Manual

Model: GRD9L-R | Brand: GEYA

1. Introduction

The GEYA GRD9L-R Auto Recloser is designed to automatically reclose a Residual Current Circuit Breaker (RCCB) or Miniature Circuit Breaker (MCB) in case of an unexpected trip due to an electrical fault. This device eliminates the need for manual intervention, reducing maintenance costs and improving system efficiency. It is suitable for a wide range of applications including power grid terminal lines, meter boxes, new energy circuit management, PV solar control boxes, smart electricity systems, smart homes, and new energy vehicle charging piles.

2. Safety Information

  • Installation and maintenance should only be performed by qualified electricians.
  • All electrical connections must comply with appropriate safety standards and local regulations.
  • Ensure the power supply is disconnected before any installation, wiring, or maintenance work.
  • Verify that the product specifications (voltage, current, etc.) match your electrical system requirements.
  • Do not operate the device if it appears damaged.

3. Product Overview

The GRD9L-R Auto Recloser features a manual/automatic selector switch, mechanical/electronic double locking function, and an LED indicator for work status. It is designed to be combined with an RCCB or MCB.

3.1. Panel Diagram

Panel Diagram of GEYA GRD9L-R Auto Recloser

This diagram illustrates the front panel of the GRD9L-R, showing the status indicators (PWR, Trip times, AUX), mode selection switch (AUTO, MANU, LOCK), closing lock, and operation handle.

3.2. Wiring Diagram

Wiring Diagram for GEYA GRD9L-R Auto Recloser

This diagram provides a typical wiring example for the GRD9L-R, including connections for the main circuit (L, N), control voltage (A1, A2), and auxiliary contacts (COM, NO) for an alarm lamp.

4. Installation

The GRD9L-R is designed for DIN rail mounting (EN/IEC 60715).

4.1. Mounting the Recloser

  • Mount the GRD9L-R unit onto a standard DIN rail.
  • Connect the RCCB/MCB to the GRD9L-R unit as shown in the 'Cooperate with RCCB/MCB' diagrams. Ensure proper alignment and secure fastening.
Installation diagrams for GEYA GRD9L-R with RCCB/MCB and accessories

The image above shows how to cooperate with an RCCB (left) or MCB (right), and how to install accessories.

4.2. Electrical Connections

  • Connect the main power lines (L and N) to the RCCB/MCB terminals.
  • Connect the control voltage to terminals A1 and A2 on the GRD9L-R. The recloser voltage range can be DC12V, DC24-48V, or AC220V, depending on the model.
  • If using auxiliary contacts for an alarm or other indication, connect them to the COM and NO terminals.
  • Ensure all connections are tight and secure. The maximum cable size for solid wire is 1x2.5 mm² or 2x1.5 mm² (AWG 12) with sleeves.

5. Operating Instructions

5.1. Mode Selection

The GRD9L-R features a mode selection switch with two positions: AUTO and MANU.

  • AUTO Mode: In this mode, the automatic reclosing function is active. If the connected RCCB/MCB trips, the GRD9L-R will attempt to reclose it automatically.
  • MANU Mode: In this mode, the automatic reclosing function is disabled. The connected RCCB/MCB can only be opened and closed manually.

5.2. LED Indicators

The device has an LED indicator for its work status:

  • When powered on, the green indicator will flash for 2 seconds to allow the power supply to stabilize.
  • If the MCB/RCCB/RCBO does not trip, the green light will stay on.
  • If the MCB/RCCB/RCBO trips, the red indicator light will be on.
  • During the automatic reclosing delay, the red light will flash. After the delay, the device will switch on automatically, and the green light will turn on.

5.3. Automatic Reclosing Logic

Diagram of Functions and Auto Mode Logic

The diagram illustrates the automatic reclosing sequence. The GRD9L-R has 3 built-in reclosing attempts. The reclosing interval times are 10 seconds, 60 seconds, and 300 seconds. If continuous closing failures occur within 15 minutes, an alarm can be sent through the auxiliary contact.

To manually clear closing times, switch from AUTO to MANU and then back to AUTO.

6. Technical Specifications

ParameterSpecification (GRD9L-R)
Control ModeAuto Reclosing
Supply TerminalsA1-A2
Voltage RangeDC12V, DC24-48V, AC220V (50-60Hz)
Voltage Tolerance±10%
Power Consumption (DC)Max. 1W (standby), Max. 20W (action)
Power Consumption (AC)Max. 1VA (standby), Max. 20VA (action)
Action Time≤1s
Auto Reclosing Times3
Auto Reclosing Interval10s-60s-300s
Reset ConditionNo trip or manual reset within 15 minutes after successful closing
Mechanical Life10,000 cycles
Electrical Life (AC1)Refer to MCB/RCCB/RCBO catalog
Operating Temperature-20°C to +55°C (-4°F to 131°F)
Storage Temperature-35°C to +75°C (-22°F to 167°F)
MountingDIN rail EN/IEC 60715
Protection DegreeIP20
Operating PositionAny
Overvoltage CategoryIII
Pollution Degree2
Max. Cable SizeSolid wire max. 1x2.5 mm² or 2x1.5 mm² with sleeve max. 1x2.5 mm² (AWG 12)

6.1. Dimensions (mm)

Dimensions of GEYA GRD9L-R 2P and 4P models

The image above provides detailed dimensions for various configurations of the GRD9L-R, including 2-pole and 4-pole versions, and combinations with other GEYA products.

7. Troubleshooting

Fault DescriptionResolution
Unable to close or open
  • Confirm the power supply voltage is normal.
  • Confirm the operating mode is set to AUTO mode.
  • Confirm the closing of the electrical operation mechanism and MCB/RCCB.
Immediate trip after closing
  • Check the circuit for overload, short circuit, or earth leakage fault at the lower end of the MCB/RCCB.
  • Verify if the circuit breaker is damaged or has slipped.

8. Maintenance

The GEYA GRD9L-R Auto Recloser is designed for reliable operation with minimal maintenance. Regular checks should be part of your electrical system's overall maintenance schedule.

  • Periodically inspect the device and its connections for any signs of wear, damage, or loose wiring.
  • Ensure the operating environment is within the specified temperature and humidity ranges.
  • Keep the device clean and free from dust and debris.
  • Test the reclosing function periodically by simulating a trip (if safely possible and recommended by the connected RCCB/MCB manufacturer).

9. User Tips

  • Control Voltage Connection: Ensure the control voltage (A1, A2 terminals) is correctly connected with phase and neutral, as improper connection can prevent the auto-recloser from functioning.
  • Reclosing Attempts: The device performs 3 reclosing attempts. If the fault persists after these attempts, the device will remain open and signal an alarm via auxiliary contacts, indicating a persistent issue that requires manual inspection.
  • Device Type: This device is an RCCB (Residual Current Circuit Breaker) recloser, primarily for earth leakage protection, not a magnetothermal breaker.
  • Reliability: Users have reported good material quality and reliable performance over multiple uses.

10. Disposal

All electrical waste products must be disposed of in accordance with applicable WEEE (Waste Electrical and Electronic Equipment) regulations. Do not dispose of this product with general household waste.

11. Additional Resources

11.1. Product Video

This video provides an overview of GEYA Electrical Co., Ltd., showcasing their manufacturing processes, product range, and commitment to quality and innovation.

11.2. Other GEYA Recloser Types

Different GEYA Recloser Types

GEYA offers various recloser types, including GRD9L-C (Switch Input Remote Control), GRD9L-D (Switch Input with Auto Reclose), GRD9L-R (Auto Reclose - this model), and GRD9L-S (RS485 Control). Each type is designed for specific control modes and applications.