1. Product Overview
The GEYA GPS8 series is a Din Rail mounted protective device designed to safeguard household electrical equipment from overvoltage, undervoltage, and overcurrent conditions. It features true RMS measurement, a digital display for real-time voltage and current values, and LED indicators for fault status. The device is available in two main function types:
- GPS8-01: Provides Overvoltage and Undervoltage Protection.
- GPS8-02: Provides Over Current, Overvoltage, and Undervoltage Protection.
It incorporates a double bus wiring design for enhanced reliability and allows for user-defined settings for protection values and delays.

Figure 1: GEYA GPS8-02 Protective Device with digital display and indicators.
2. Technical Specifications
| Parameter | Specification (GPS8-02) |
|---|---|
| Function | Over voltage, under voltage and over current |
| Rated supply voltage | AC220V (L-N) |
| Rated supply frequency | 45~65Hz |
| Operation voltage range | 80V~400V (L-N) |
| Rated operational current | 32A, 40A, 50A, 63A, 80A (AC1) |
| Burden | AC max. 3VA |
| Over voltage operation value | OFF, 230V~300V |
| Under voltage operation value | 140V~210V, OFF |
| Over/under voltage action delay | 0.1s~10s |
| Over current operation value | 1~32A, 40A, 50A, 63A, 80A |
| Over current action delay | 2s~600s |
| Power-up delay | 2s~600s |
| Reset time | 2s~900s |
| Measurement error | <1% |
| Electrical life (AC1) | 1×104 |
| Mechanical life | 1×106 |
| Operating temperature | -20°C~+60°C |
| Storage temperature | -35°C~+75°C |
| Mounting/DIN rail | Din rail EN/IEC 60715 |
| Protection degree | IP40 for front panel/IP20 terminals |
| Operating position | Any |
| Overvoltage category | III. |
| Pollution degree | 2 |
| Dimensions | 82×36×68mm |
| Weight | 135g |

Figure 2: Device Dimensions.
3. Installation and Wiring
The GEYA GPS8 protective device is designed for DIN rail mounting (EN/IEC 60715). Installation should only be performed by qualified electricians to ensure compliance with appropriate safety standards.
3.1 Wiring Diagram
The device supports two incoming line modes: Upper Incoming Line and Down Incoming Line. Refer to the diagrams below for correct wiring.

Figure 3: Wiring Diagrams for Upper and Down Incoming Lines.
NOTE: This product does not have an isolation function. Always disconnect the superior Miniature Circuit Breaker (MCB) during maintenance to prevent electric shock.
3.2 Example Wiring
An example of connecting multiple GPS8-02 units with MCBs and loads is shown below.

Figure 4: Example Wiring for Multiple Devices.
4. Operating Instructions
4.1 Panel Diagram and Indicators

Figure 5: Device Panel Diagram.
The panel features a dual digital display for voltage (V) and current (A), along with LED indicators:
- >U: Over voltage indicator
- <U: Under voltage indicator
- >I: Over current indicator
- Power open and close indicator: Indicates load status.
Buttons:
- M (Setting Key): Press and hold for 3 seconds to enter/save settings.
- ▲ (Up Arrow): Used to increase parameter values.
- Power Button: Used to decrease parameter values. After exiting settings, it can manually turn the load on or off. If automatic fault reset is off, this button can be used for manual reset after a fault.
4.2 Parameter Setting
To adjust the protection parameters:
- Press and hold the M (Setting) key for 3 seconds to enter the setting mode.
- Use the ▲ (Up Arrow) and Power Button (Down Arrow) to adjust the desired parameter value.
- Press and hold the M key for 3 seconds again to save the settings and exit.
- If no operation is performed for 60 seconds in setting mode, the device will automatically exit without saving changes.
Parameter Setting Table (Factory Defaults):
| Parameter | Range | Step value | Factory settings |
|---|---|---|---|
| Over voltage value | OFF, 230V~300V | 1V | 275V |
| Over voltage recovery value | 225V~295V | 1V | 265V |
| Under voltage value | 140V~210V, OFF | 1V | 175V |
| Under voltage recovery value | 145V~215V | 1V | 180V |
| Voltage fault action time | 0.1s~10s | 0.1s | 0.5s |
| Over current value | OFF, 1A~32/40/50/63A | 0.1A | 32A/40A/50A/63A |
| Over current action delay | 2s~600s | 1s | 5s |
| Power on delay time | 2s~600s | 1s | 5s |
| Reset time | 2s~900s | 1s | 30s |
| Fault reset | ON-OFF | — | ON |
4.3 Manual Operation
In normal operation, the load can be switched on or off manually by pressing the Power button for 0.5 seconds.
4.4 Power-on and Reset Delay
During power-on or after a fault, the device will display a countdown according to the set delay time before entering the running state.
5. Maintenance and Troubleshooting
The GEYA GPS8 protective device is designed for reliable operation with minimal maintenance. Regular visual inspection for any physical damage or loose connections is recommended.
WARNING: Always disconnect power from the superior MCB before performing any maintenance or inspection on the device.
5.1 Troubleshooting
- Device not powering on: Check the incoming power supply and ensure connections are secure.
- Device trips frequently: Review the set overvoltage, undervoltage, and overcurrent parameters. Ensure they are appropriate for your connected load and supply conditions. Check for actual faults in the electrical system.
- Display not working: Verify power supply. If power is present and the display remains off, contact support.
6. User Tips
- Parameter Adjustment: Take your time when adjusting parameters. A short press of the up/down buttons changes values incrementally, while a long press allows for faster adjustment. Remember to save your settings by holding the 'M' button.
- Reliability: Users have noted the consistent quality and reliability of GEYA products. Proper installation and adherence to specifications will ensure long-term performance.
- Value for Money: This product is considered a good investment for its protective capabilities and quality.
7. Environmental Disposal
All electrical waste should be disposed of in compliance with current WEEE (Waste Electrical and Electronic Equipment) regulations. Do not dispose of this product with general household waste.
8. Manufacturer Information and Support
GEYA ELECTRICAL CO.,LTD
Address: Wenzhou Bridge Industrial Zone, Beibaixiang Town, Yueqing, Zhejiang, China 325603
Email: sale@cngeya.com
Website: www.geya.net
For further assistance or inquiries, please contact GEYA directly via the provided contact information.
A user manual in PDF format is available for download from the manufacturer's website: GEYA GPS8 User Manual (PDF)
8.1 GEYA Company Overview Video
Watch this video for an overview of GEYA's manufacturing processes and commitment to quality.
Video 1: GEYA Company Introduction and Manufacturing Process.