1. Introduction
The TOMZN TOVPD1-63-VA is an advanced protective device designed to safeguard electrical appliances and circuits from voltage and current anomalies. This device features a dual digital display for real-time monitoring of voltage and current, along with adjustable protection parameters for over-voltage, under-voltage, and over-current conditions. It is designed for easy installation on a 35mm DIN rail and offers automatic recovery after a fault condition is cleared.

2. Safety Information
- Always disconnect power before installation or maintenance.
- Installation should be performed by a qualified electrician to ensure compliance with local electrical codes and safety standards.
- Do not operate the device if it appears damaged or malfunctioning.
- Ensure proper grounding where required.
- Avoid touching live terminals.
- The device is designed for indoor use in dry conditions.
3. Product Overview
3.1 Key Features
- Dual Digital Display: Real-time display of voltage (V) and current (A).
- Multi-Protection: Provides protection against over-voltage, under-voltage, and over-current.
- Adjustable Parameters: All protection values and recovery times are adjustable to meet specific requirements.
- Automatic Recovery: The device automatically restores power once the fault condition returns to normal.
- Magnetic Latching Relay: Built-in 63A magnetic latching relay ensures durability and resistance to high current impact.
- DIN Rail Mounting: Standard 35mm DIN rail installation for easy integration into electrical panels.
- Voltage Calibration: Allows for fine-tuning of voltage readings (A13 setting).
3.2 Components and Indicators

- Volt Display: Shows the current voltage.
- Current Display: Shows the current amperage.
- Set Button: Used to enter and exit setting mode, and to confirm selections.
- Adjustment Keys (Up/Down Arrows): Used to navigate through settings and adjust values.
- Over Voltage LED (>V): Illuminates when an over-voltage condition is detected.
- Under Voltage LED (<V): Illuminates when an under-voltage condition is detected.
- Over Current LED (>A): Illuminates when an over-current condition is detected.
- Power Indicator (POWER): Illuminates when the device is powered on.
4. Installation and Setup
4.1 Mounting
The TOVPD1-63-VA is designed for 35mm standard DIN rail installation. Ensure the rail is securely mounted in your electrical panel. The installation and disassembly process is simple and convenient.

4.2 Wiring
Connect the device according to the wiring diagram below. The input (IN) terminals are for the incoming power line (L and N), and the output (OUT) terminals connect to the load. When connecting the power line, ensure to screw down to penetrate the insulating layer of the power lines for a secure connection. The wiring configuration is "Over-entering down-out".

Ensure all connections are tight and secure to prevent loose contacts and potential hazards.
5. Operation
Once correctly installed and powered on, the device will display the real-time voltage and current. The green POWER indicator will illuminate. If an over-voltage, under-voltage, or over-current condition occurs, the corresponding red LED indicator will light up, and the device will automatically cut off the power supply to protect connected appliances. After the fault condition is resolved and the system returns to normal parameters, the device will automatically restore power after the set recovery delay time.

6. Product Settings
The device allows for adjustment of various protection parameters. Use the "SET" button to enter and exit the setting mode, and the "Up" and "Down" arrow keys to navigate and change values. Press "SET" again to confirm a value and move to the next setting.

Setting Parameters:
- Voltage Display (230): Current voltage reading.
- Current Display (63.0): Current amperage reading.
- A1: Power-on Delay Time (S): Range 1-500 seconds.
- A2: Over-voltage Protection Value (V): Range 230-300V.
- A3: Over-voltage Recovery Value (V): Range 225-295V.
- A4: Over-voltage Recovery Delay Time (S): Range 1-500 seconds.
- A5: Over-voltage Protection Action Time (S): Range 0.1-30 seconds.
- A6: Under-voltage Protection Value (V): Range 140-210V.
- A7: Under-voltage Recovery Value (V): Range 145-215V.
- A8: Under-voltage Recovery Delay Time (S): Range 1-500 seconds.
- A9: Under-voltage Protection Action Time (S): Range 0.1-30 seconds.
- A10: Over-current Protection Value (A): Range 0.5-40A (for 40A model) or 0.5-63A (for 63A model).
- A11: Over-current Recovery Delay Time (S): Range 1-500 seconds.
- A12: Over-current Protection Action Time (S): Range 0.1-30 seconds.
- OFF: Manual Switch: Press the SET key to turn off the protection function.
- A13: Voltage Calibration: Adjusts voltage reading by +/-9.5% if not correct.
To exit settings, press the SET key after adjusting the last parameter (A12 or A13).
7. Maintenance
The TOMZN TOVPD1-63-VA is designed for long-term, maintenance-free operation. However, periodic checks are recommended:
- Ensure the device and its connections are clean and free from dust or debris.
- Verify that all wiring connections remain tight and secure.
- Check the display for proper functionality and accurate readings.
- In case of frequent tripping, investigate the cause in your electrical system rather than adjusting protection values excessively.
8. Troubleshooting
If the device is not functioning as expected, consider the following:
- No Display/No Power: Check the incoming power supply and wiring connections. Ensure the device is receiving 230VAC.
- Frequent Tripping: Review your set protection values (over-voltage, under-voltage, over-current) against your actual electrical load and supply stability. High sensitivity settings or unstable power can cause frequent trips.
- Incorrect Readings: If voltage or current readings appear inaccurate, use the A13 voltage calibration setting to adjust the voltage. For current, ensure the load is within the device's rated capacity.
- Device Not Recovering: Check the recovery delay time settings (A4, A8, A11). Ensure the fault condition has genuinely cleared.
9. Specifications
| Function | Technical Parameter | Function | Technical Parameter |
|---|---|---|---|
| Input voltage | AC 140-300V | Power-on delay time | 1-500s (default 3s) |
| Over-voltage protection value | 230-300V (default 250V) | Over-voltage recovery value | 220-295V (default 230V) |
| Under-voltage protection value | 140-210V (default 170V) | Under-voltage recovery value | 175-215V (default 210V) |
| Over-current protection value | 40A: 0.5-40A (default 20A) 63A: 0.5-63A (default 40A) | Over-current recovery value | 0-39.5A (for 40A) 0-62.5A (for 63A) |
| Recovery delay time | 1-500s (default 30s) | Action time | 0.1-30s (default 1s) |
| Power consumption | ≤2W | Electrical and mechanical life | ≥100000 cycles |
| Boundary dimension | 86 × 38 × 68 MM | Wiring | Over-entering down-out |
| Installation | 35mm DIN rail | Certification | CE |

10. User Tips
- Understanding Action Time: The "Action time" (A5, A9, A12) refers to how quickly the device will cut off power once a fault condition is detected. A shorter time provides faster protection but might lead to nuisance tripping in very unstable power environments. A longer time offers more tolerance but slightly delayed protection. Adjust this based on the sensitivity of your connected appliances and the stability of your power supply.
- Voltage Calibration (A13): If you have a calibrated multimeter and notice a discrepancy in the voltage displayed by the protector, use the A13 setting to fine-tune the reading for accuracy.