1. Introduction
The GEYA GRT8-2T is a double delay on time relay designed for various industrial and home automation applications. It features two independent time relays (t1 and t2) within a single module, allowing for precise control of electrical circuits. This manual provides essential information for the safe and effective installation, operation, and maintenance of your GRT8-2T relay.
2. Safety Information
Always observe the following safety precautions to prevent injury and damage to the device:
- Ensure power is disconnected before installation, wiring, or maintenance.
- Installation should be performed by qualified personnel in accordance with local electrical codes.
- Do not exceed the specified voltage and current ratings.
- Avoid exposing the device to moisture, extreme temperatures, or corrosive environments.
- This device operates with low voltage (below 50Vac or 75Vdc) for certain models, but always treat electrical connections with caution.
3. Product Overview
The GRT8-2T is a 1-MODULE DIN rail mountable time relay. It features two independently adjustable delay-on timers (t1 and t2) and provides 2 SPDT (Single Pole Double Throw) output contacts. The relay status is indicated by green and red LEDs.
3.1. Key Features
- Function: Double Delay ON (two time relays in one module).
- Time Ranges: 0.1s - 10 days, divided into 10 selectable ranges (0.1s-1s, 1s-10s, 0.1min-1min, 1min-10min, 0.1h-1h, 1h-10hrs, 0.1 day-1 day, 1 day-10 days, ON, OFF).
- Adjustability: Times t1 and t2 are independently adjustable via potentiometers.
- Output: 2 x SPDT (Single Pole Double Throw) contacts, rated 16A/AC1.
- Voltage Options: Available in AC230V or AC/DC12-240V.
- Indicators: Green LED for supply indication (Un), Red LED for output indication (R).
- Mounting: DIN rail type (EN/IEC 60715).
- Certifications: CE, CB, CCC, ROHS.
3.2. Component Identification

- A1, S, A2: Supply Terminals, Trigger Terminal
- Un (Green LED): Supply Indication
- R (Red LED): Output Indication
- t1 Time Range Setting: Knob for setting the first delay time (0.1s-10days, ON, OFF).
- Time Percentage Setting: Knob for fine-tuning the percentage of t1.
- t2 Time Range Setting: Knob for setting the second delay time (0.1s-10days, ON, OFF).
- Time Percentage Setting: Knob for fine-tuning the percentage of t2.
- Model No: GRT8-2T
- 15, 16, 18: First Changeover Contact (16A/AC1)
- 25, 26, 28: Second Changeover Contact (16A/AC1)
4. Technical Specifications

| Parameter | GRT8-2T (AC/DC 12-240V) | GRT8-2T (AC230V) |
|---|---|---|
| Function | 2x Delay ON | |
| Supply terminals | A1-A2 | |
| Voltage range | AC/DC 12-240V (50-60Hz) | AC 230V (50-60Hz) |
| Burden | AC 0.09-3VA / DC 0.05-1.7W | |
| Power input | AC max.6VA / 1.9W | |
| Supply voltage tolerance | -15%; +10% | |
| Supply indication | Green LED | |
| Time ranges | 0.1s-10days, ON, OFF | |
| Time setting | Potentiometer | |
| Time deviation | 10% - mechanical setting | |
| Repeat accuracy | 0.2% - set value stability | |
| Temperature coefficient | 0.05%/°C, at=20°C (0.05%°F, at=68°F) | |
| Output | 2 x SPDT | |
| Current rating | 16A / AC1 | |
| Switching voltage | 250VAC / 24VDC | |
| Min. breaking capacity DC | 500mW | |
| Output indication | Red LED | |
| Mechanical life | 1 x 107 | |
| Electrical life (AC1) | 1 x 105 | |
| Reset time | max. 200ms | |
| Operating temperature | -20°C to +55°C (-4°F to 131°F) | |
| Storage temperature | -35°C to +75°C (-22°F to 158°F) | |
| Mounting | Din rail EN/IEC 60715 | |
| Protection degree | IP40 for front panel / IP20 terminals | |
| Operating position | Any | |
| Overvoltage category | III. | |
| Pollution degree | 2 | |
| Max. cable size (mm2) | Solid wire max.1x2.5 or 2x1.5 / with sleeve max.1x2.5 (AWG 12) | |
| Dimensions | 90 x 18 x 64mm | |
5. Setup and Installation
5.1. Mounting
The GRT8-2T relay is designed for DIN rail mounting (EN/IEC 60715). Simply clip the device onto a standard 35mm DIN rail in your electrical enclosure.
5.2. Wiring
Ensure all power is disconnected before proceeding with wiring. Use appropriate wire gauges for the rated current (max. 1x2.5mm² solid wire or 2x1.5mm² with sleeve). Tighten terminals securely.



Terminal Connections:
- A1, A2: Supply voltage input.
- S: Trigger input (for some functions, this may be used to initiate the timing sequence).
- 15, 16, 18: Output contacts for the first relay (Common, Normally Closed, Normally Open).
- 25, 26, 28: Output contacts for the second relay (Common, Normally Closed, Normally Open).
6. Operating Instructions
6.1. Time Setting
The GRT8-2T features two sets of rotary potentiometers for setting the time ranges (t1 and t2) and their respective percentages. Each time range knob allows selection from 0.1s to 10 days, including ON and OFF modes. The percentage knob provides fine-tuning within the selected range.
To set the time:
- Select the desired time range (e.g., 1s-10s, 1min-10min) using the upper (t1) and lower (t2) range selector knobs.
- Adjust the corresponding percentage knob (0-100%) to achieve the precise delay time within the selected range.
6.2. LED Indicators
- Green LED (Un): Illuminates when the supply voltage is present.
- Red LED (R): Illuminates when the output relay is activated (contacts 15-18 and 25-28 are closed).
6.3. Function Description (Double Delay ON)
When the supply voltage is connected to terminals A1-A2, both timers t1 and t2 start simultaneously. After the set time t1 has elapsed, the first output relay (15-18) activates. After the set time t2 has elapsed, the second output relay (25-28) activates. Both relays remain activated as long as the supply voltage is present.
7. Maintenance
The GEYA GRT8-2T is designed for long-term, reliable operation with minimal maintenance. However, regular checks can help ensure optimal performance:
- Periodically inspect the terminals for secure connections.
- Ensure the device is free from dust and debris.
- Check for any signs of overheating or physical damage.
- Verify that the LED indicators are functioning correctly.
Always disconnect power before performing any maintenance.
8. Troubleshooting
| Problem | Possible Cause | Solution |
|---|---|---|
| Green LED (Un) not lit | No supply voltage or incorrect wiring. | Check power supply and wiring connections to A1-A2. |
| Red LED (R) not lit after delay | Incorrect time setting, faulty load, or open circuit in load. | Verify time settings. Check the load and its wiring. Test the relay output contacts. |
| Inaccurate timing | Incorrect time range/percentage setting. | Re-adjust time range and percentage knobs carefully. Refer to specifications for accuracy. |
| Relay clicks but load doesn't activate | Faulty load or wiring to load. | Check the load device and its connections to the relay output terminals (15-18, 25-28). |
9. User Tips
- For applications requiring precise timing, consider testing the set delay times with a stopwatch before final deployment.
- When replacing an old relay, ensure the new GRT8-2T model matches the voltage and contact configuration of the original unit.
- Keep the device in a well-ventilated area to prevent overheating, especially in enclosed panels.
10. Warranty and Support
For warranty information, technical support, or service inquiries, please contact your retailer or the manufacturer directly. Ensure you have your product model and purchase details available.
An official user manual in PDF format is available for download: GEYA GRT8-2T User Manual (PDF)
11. Company Overview Video
Learn more about GEYA Electrical Co., Ltd. and their manufacturing processes: