BACnet Introduction
The MegaTron controller is capable of connecting to the WebAdvantage Server and most Building Management Systems. The WebAdvantage service requires a gateway to the internet with firewall and security rules in place. The Building Management System needs to be on the same subnet to properly receive traffic from the MegaTron. This may require some advanced routing of network traffic within the network wiring or programming of advanced switching equipment. The datatraffic for both is provided via the same Ethernet cable coming from the MegaTron. The BACnet protocol allows interfacing with more customizable PC applications using HMI/SCADA and stand-alone HMI systems

BACnet Overview
BACnet is an American National Standard. The BACnet protocol allows the creation of an automation and controls system which may interoperate with other BACnet systems. In BACnet terms, interoperate means that two or more BACnet-speaking computer systems may share the same communications networks, and ask each other to perform various functions on a peer-to-peer basis. BACnet’s flexibility has two important benefits: vendor-independence and forward-compatibility with future generations of systems. This is accomplished using an object-oriented approach for representing all information within each controller. Since BACnet is based on standards, it provides maximum benefits for both the vendor who designs BACnet systems, and the specifier or owner of those systems.

Protocal Implementation Conformance Summary (Annex-A)

  • Applications Software Version: JA.12.1 and higher
  • Firmware Revision: JA.12.1 and higher
  • BACnet Protocol Revision: 6
  • BACnet Standardized Device Profile (Annex L): BACnet Application Specific Controller (B-ASC)
  • BACnet Interoperability Building Blocks Supported (Annex K):
    • DS-RP-B
    • DM-DDB-B
    • DM-DCC-B
    • DM-RD-B
  • Standard Object Types Supported: See table 3-1 “Object/Property Support Matrix”.
  • Data Link Layer Options: BACnet IP, (Annex J)
  • Character Set Supported: ANSI X3.4

Connecting to BACnet enabled MegaTron

This guide is designed to help with connecting a BACnet enabled MegaTron to a local BMS.

Note: Screens may vary slightly between models.

BACnet Setup

Step 1:
Press Setup/Run, CONFIGURE, NETWORK, SETTINGS.
(See figures 1, 2, 3 and 4. H25 dual cards add figure 3B. H25 only available for MegaTron MT.)

Step 2:
Press BAC.
(See figure 4.)

Note: If these options are not visible, the dual network card needs to be enabled. See enabling dual network card to continue setup.

Step 3:
Enter the DEVICE INSTANCE and PORT. Press Enter to accept on each.
(See figure 6.)

Step 4:
Press RESET and then press Enter to accept. The communications card will reset after a short countdown.
(See figures 7 and 8.)

Step 5:
After the communications card has been reset cycle power to the controller.

Advantage-Controls-H21-Mega-Tron-Controller-(1)

MegaTron XS Setup

Advantage-Controls-H21-Mega-Tron-Controller-(2)

The MegaTron XS will be a “device object” on the particular BACnet network. Each device object (your MegaTron XS) must have an object identifier that is unique network wide. The device object instance number is normally configured on site after the device is installed. The device object instance number range is between 0 and 4194303. Note that 4194303 is known as “unconfigured” and is not really a valid device instance number. All devices are required to respond with their own Device object instance number when 4194303 is requested. To enter your device object identifier, go to the Configure menu in the MegaTron XS and select the Network settings. Then select BAC.

Object Definitions

Object / Property Support Matrix (Table 1-1)

 Property Object Type
Device Binary Input Binary Value Analog Input Analog Value Multi-State Value
Object Identifier
Object Name
Object Type
Description
System Status
Vendor Name
Vendor Identifier
Model Name
Firmware Revision
App. Software Revision
Protocol Version
Protocol Revision
Services Supported
Object Types Supported
Object List
Max APDU Length
Segmentation Support
APDU Timeout
Number APDU Retries
Database Revision
Present Value
Status Flags
Event State
Out-of-Service
Units
Polarity
Number of States
State Text

Binary Input Object Instance Summary (Table 1-2)

Instance ID Object Name Purpose Present Value – Access
0 BI-000 System #1 – Flow Switch Read Only
1 BI-001 System #2 – Flow Switch Read Only
2 BI-002 System #3 – Flow Switch Read Only
3 BI-003 System #4 – Flow Switch Read Only

Binary Value Object Instance Summary (Table 1-3)

Instance ID Object Name Purpose Present Value – Access
12 BV-012 System #1 – Conductivity High Alarm Read Only
13 BV-013 System #1 – Conductivity Low Alarm Read Only
14 BV-014 System #1 – Conductivity Limit Alarm Read Only
15 BV-015 System #1 – pH High Alarm Read Only
16 BV-016 System #1 – pH Low Alarm Read Only
17 BV-017 System #1 – pH Limit Alarm Read Only
18 BV-018 System #1 – ORP High Alarm Read Only
19 BV-019 System #1 – ORP Low Alarm Read Only
20 BV-020 System #1 – ORP Limit Alarm Read Only
21 BV-021 System #1 – S. Temp High Alarm Read Only
22 BV-022 System #1 – S. Temp Low Alarm Read Only
23 BV-023 System #1 – M. Temp High Alarm Read Only
24 BV-024 System #1 – M. Temp Low Alarm Read Only
25 BV-025 System #1 – D. Temp High Alarm Read Only
26 BV-026 System #1 – D. Temp Low Alarm Read Only
27 BV-027 System #1 – No Flow Alarm Read Only
28 BV-028 System #1 – Digital Input 1 Alarm Read Only
29 BV-029 System #1 – Digital Input 2 Alarm Read Only
30 BV-030 System #1 – Digital Input 3 Alarm Read Only
31 BV-031 System #1 – Digital Input 4 Alarm Read Only
32 BV-032 System #1 – Digital Input 5 Alarm Read Only
34 BV-034 System #1 – M. Conductivity High Alarm Read Only
35 BV-035 System #1 – M. Conductivity Low Alarm Read Only
36 BV-036 System #1 – M. Conductivity Limit Alarm Read Only
37 BV-037 System #1 – Notepad 1 High Alarm Read Only
38 BV-038 System #1 – Notepad 2 High Alarm Read Only
39 BV-039 System #1 – Notepad 3 High Alarm Read Only
40 BV-040 System #1 – Notepad 4 High Alarm Read Only
41 BV-041 System #1 – Notepad 5 High Alarm Read Only
42 BV-042 System #1 – Notepad 6 High Alarm Read Only
43 BV-043 System #1 – Notepad 7 High Alarm Read Only
44 BV-044 System #1 – Notepad 8 High Alarm Read Only
45 BV-045 System #1 – Notepad 9 High Alarm Read Only
46 BV-046 System #1 – Notepad 10 High Alarm Read Only
47 BV-047 System #1 – Notepad 1 Low Alarm Read Only
48 BV-048 System #1 – Notepad 2 Low Alarm Read Only
49 BV-049 System #1 – Notepad 3 Low Alarm Read Only
50 BV-050 System #1 – Notepad 4 Low Alarm Read Only
51 BV-051 System #1 – Notepad 5 Low Alarm Read Only
52 BV-052 System #1 – Notepad 6 Low Alarm Read Only
53 BV-053 System #1 – Notepad 7 Low Alarm Read Only
54 BV-054 System #1 – Notepad 8 Low Alarm Read Only
55 BV-055 System #1 – Notepad 9 Low Alarm Read Only
56 BV-056 System #1 – Notepad 10 Low Alarm Read Only
57 BV-057 System #1 – Notepad 1 Time Alarm Read Only
58 BV-058 System #1 – Notepad 2 Time Alarm Read Only
59 BV-059 System #1 – Notepad 3 Time Alarm Read Only
60 BV-060 System #1 – Notepad 4 Time Alarm Read Only
61 BV-061 System #1 – Notepad 5 Time Alarm Read Only
62 BV-062 System #1 – Notepad 6 Time Alarm Read Only
63 BV-063 System #1 – Notepad 7 Time Alarm Read Only
64 BV-064 System #1 – Notepad 8 Time Alarm Read Only
65 BV-065 System #1 – Notepad 9 Time Alarm Read Only
66 BV-066 System #1 – Notepad 10 Time Alarm Read Only
81 BV-081 System #2 – Conductivity High Alarm Read Only
82 BV-082 System #2 – Conductivity Low Alarm Read Only
83 BV-083 System #2 – Conductivity Limit Alarm Read Only
84 BV-084 System #2 – pH High Alarm Read Only
85 BV-085 System #2 – pH Low Alarm Read Only
86 BV-086 System #2 – pH Limit Alarm Read Only
87 BV-087 System #2 – ORP High Alarm Read Only
88 BV-088 System #2 – ORP Low Alarm Read Only
89 BV-089 System #2 – ORP Limit Alarm Read Only
90 BV-090 System #2 – S. Temp High Alarm Read Only
91 BV-091 System #2 – S. Temp Low Alarm Read Only
92 BV-092 System #2 – M. Temp High Alarm Read Only
93 BV-093 System #2 – M. Temp Low Alarm Read Only
94 BV-094 System #2 – D. Temp High Alarm Read Only
95 BV-095 System #2 – D. Temp Low Alarm Read Only
96 BV-096 System #2 – No Flow Alarm Read Only
97 BV-097 System #2 – Digital Input 1 Alarm Read Only
98 BV-098 System #2 – Digital Input 2 Alarm Read Only
99 BV-099 System #2 – Digital Input 3 Alarm Read Only
100 BV-100 System #2 – Digital Input 4 Alarm Read Only
101 BV-101 System #2 – Digital Input 5 Alarm Read Only
103 BV-103 System #2 – M. Conductivity High Alarm Read Only
104 BV-104 System #2 – M. Conductivity Low Alarm Read Only
105 BV-105 System #2 – M. Conductivity Limit Alarm Read Only
106 BV-106 System #2 – Notepad 1 High Alarm Read Only
107 BV-107 System #2 – Notepad 2 High Alarm Read Only
108 BV-108 System #2 – Notepad 3 High Alarm Read Only
109 BV-109 System #2 – Notepad 4 High Alarm Read Only
110 BV-110 System #2 – Notepad 5 High Alarm Read Only
111 BV-111 System #2 – Notepad 6 High Alarm Read Only
112 BV-112 System #2 – Notepad 7 High Alarm Read Only
113 BV-113 System #2 – Notepad 8 High Alarm Read Only
114 BV-114 System #2 – Notepad 9 High Alarm Read Only
115 BV-115 System #2 – Notepad 10 High Alarm Read Only
116 BV-116 System #2 – Notepad 1 Low Alarm Read Only
117 BV-117 System #2 – Notepad 2 Low Alarm Read Only
118 BV-118 System #2 – Notepad 3 Low Alarm Read Only
119 BV-119 System #2 – Notepad 4 Low Alarm Read Only
120 BV-120 System #2 – Notepad 5 Low Alarm Read Only
121 BV-121 System #2 – Notepad 6 Low Alarm Read Only
122 BV-122 System #2 – Notepad 7 Low Alarm Read Only
123 BV-123 System #2 – Notepad 8 Low Alarm Read Only
124 BV-124 System #2 – Notepad 9 Low Alarm Read Only
125 BV-125 System #2 – Notepad 10 Low Alarm Read Only
126 BV-126 System #2 – Notepad 1 Time Alarm Read Only
127 BV-127 System #2 – Notepad 2 Time Alarm Read Only
128 BV-128 System #2 – Notepad 3 Time Alarm Read Only
129 BV-129 System #2 – Notepad 4 Time Alarm Read Only
130 BV-130 System #2 – Notepad 5 Time Alarm Read Only
131 BV-131 System #2 – Notepad 6 Time Alarm Read Only
132 BV-132 System #2 – Notepad 7 Time Alarm Read Only
133 BV-133 System #2 – Notepad 8 Time Alarm Read Only
134 BV-134 System #2 – Notepad 9 Time Alarm Read Only
135 BV-135 System #2 – Notepad 10 Time Alarm Read Only
150 BV-150 System #3 – Conductivity High Alarm Read Only
151 BV-151 System #3 – Conductivity Low Alarm Read Only
152 BV-152 System #3 – Conductivity Limit Alarm Read Only
153 BV-153 System #3 – pH High Alarm Read Only
154 BV-154 System #3 – pH Low Alarm Read Only
155 BV-155 System #3 – pH Limit Alarm Read Only
156 BV-156 System #3 – ORP High Alarm Read Only
157 BV-157 System #3 – ORP Low Alarm Read Only
158 BV-158 System #3 – ORP Limit Alarm Read Only
159 BV-159 System #3 – S. Temp High Alarm Read Only
160 BV-160 System #3 – S. Temp Low Alarm Read Only
161 BV-161 System #3 – M. Temp High Alarm Read Only
162 BV-162 System #3 – M. Temp Low Alarm Read Only
163 BV-163 System #3 – D. Temp High Alarm Read Only
164 BV-164 System #3 – D. Temp Low Alarm Read Only
165 BV-165 System #3 – No Flow Alarm Read Only
166 BV-166 System #3 – Digital Input 1 Alarm Read Only
167 BV-167 System #3 – Digital Input 2 Alarm Read Only
168 BV-168 System #3 – Digital Input 3 Alarm Read Only
169 BV-169 System #3 – Digital Input 4 Alarm Read Only
170 BV-170 System #3 – Digital Input 5 Alarm Read Only
172 BV-172 System #3 – M. Conductivity High Alarm Read Only
173 BV-173 System #3 – M. Conductivity Low Alarm Read Only
174 BV-174 System #3 – M. Conductivity Limit Alarm Read Only
175 BV-175 System #3 – Notepad 1 High Alarm Read Only
176 BV-176 System #3 – Notepad 2 High Alarm Read Only
177 BV-177 System #3 – Notepad 3 High Alarm Read Only
178 BV-178 System #3 – Notepad 4 High Alarm Read Only
179 BV-179 System #3 – Notepad 5 High Alarm Read Only
180 BV-180 System #3 – Notepad 6 High Alarm Read Only
181 BV-181 System #3 – Notepad 7 High Alarm Read Only
182 BV-182 System #3 – Notepad 8 High Alarm Read Only
183 BV-183 System #3 – Notepad 9 High Alarm Read Only
184 BV-184 System #3 – Notepad 10 High Alarm Read Only
185 BV-185 System #3 – Notepad 1 Low Alarm Read Only
186 BV-186 System #3 – Notepad 2 Low Alarm Read Only
187 BV-187 System #3 – Notepad 3 Low Alarm Read Only
188 BV-188 System #3 – Notepad 4 Low Alarm Read Only
189 BV-189 System #3 – Notepad 5 Low Alarm Read Only
190 BV-190 System #3 – Notepad 6 Low Alarm Read Only
191 BV-191 System #3 – Notepad 7 Low Alarm Read Only
192 BV-192 System #3 – Notepad 8 Low Alarm Read Only
193 BV-193 System #3 – Notepad 9 Low Alarm Read Only
194 BV-194 System #3 – Notepad 10 Low Alarm Read Only
195 BV-195 System #3 – Notepad 1 Time Alarm Read Only
196 BV-196 System #3 – Notepad 2 Time Alarm Read Only
197 BV-197 System #3 – Notepad 3 Time Alarm Read Only
198 BV-198 System #3 – Notepad 4 Time Alarm Read Only
199 BV-199 System #3 – Notepad 5 Time Alarm Read Only
200 BV-200 System #3 – Notepad 6 Time Alarm Read Only
201 BV-201 System #3 – Notepad 7 Time Alarm Read Only
202 BV-202 System #3 – Notepad 8 Time Alarm Read Only
203 BV-203 System #3 – Notepad 9 Time Alarm Read Only
204 BV-204 System #3 – Notepad 10 Time Alarm Read Only
219 BV-219 System #4 – Conductivity High Alarm Read Only
220 BV-220 System #4 – Conductivity Low Alarm Read Only
221 BV-221 System #4 – Conductivity Limit Alarm Read Only
222 BV-222 System #4 – pH High Alarm Read Only
223 BV-223 System #4 – pH Low Alarm Read Only
224 BV-224 System #4 – pH Limit Alarm Read Only
225 BV-225 System #4 – ORP High Alarm Read Only
226 BV-226 System #4 – ORP Low Alarm Read Only
227 BV-227 System #4 – ORP Limit Alarm Read Only
228 BV-228 System #4 – S. Temp High Alarm Read Only
229 BV-229 System #4 – S. Temp Low Alarm Read Only
230 BV-230 System #4 – M. Temp High Alarm Read Only
231 BV-231 System #4 – M. Temp Low Alarm Read Only
232 BV-232 System #4 – D. Temp High Alarm Read Only
233 BV-233 System #4 – D. Temp Low Alarm Read Only
234 BV-234 System #4 – No Flow Alarm Read Only
235 BV-235 System #4 – Digital Input 1 Alarm Read Only
236 BV-236 System #4 – Digital Input 2 Alarm Read Only
237 BV-237 System #4 – Digital Input 3 Alarm Read Only
238 BV-238 System #4 – Digital Input 4 Alarm Read Only
239 BV-239 System #4 – Digital Input 5 Alarm Read Only
241 BV-241 System #4 – M. Conductivity High Alarm Read Only
242 BV-242 System #4 – M. Conductivity Low Alarm Read Only
243 BV-243 System #4 – M. Conductivity Limit Alarm Read Only
244 BV-244 System #4 – Notepad 1 High Alarm Read Only
245 BV-245 System #4 – Notepad 2 High Alarm Read Only
246 BV-246 System #4 – Notepad 3 High Alarm Read Only
247 BV-247 System #4 – Notepad 4 High Alarm Read Only
248 BV-248 System #4 – Notepad 5 High Alarm Read Only
249 BV-249 System #4 – Notepad 6 High Alarm Read Only
250 BV-250 System #4 – Notepad 7 High Alarm Read Only
251 BV-251 System #4 – Notepad 8 High Alarm Read Only
252 BV-252 System #4 – Notepad 9 High Alarm Read Only
253 BV-253 System #4 – Notepad 10 High Alarm Read Only
254 BV-254 System #4 – Notepad 1 Low Alarm Read Only
255 BV-255 System #4 – Notepad 2 Low Alarm Read Only
256 BV-256 System #4 – Notepad 3 Low Alarm Read Only
257 BV-257 System #4 – Notepad 4 Low Alarm Read Only
258 BV-258 System #4 – Notepad 5 Low Alarm Read Only
259 BV-259 System #4 – Notepad 6 Low Alarm Read Only
260 BV-260 System #4 – Notepad 7 Low Alarm Read Only
261 BV-261 System #4 – Notepad 8 Low Alarm Read Only
262 BV-262 System #4 – Notepad 9 Low Alarm Read Only
263 BV-263 System #4 – Notepad 10 Low Alarm Read Only
264 BV-264 System #4 – Notepad 1 Time Alarm Read Only
265 BV-265 System #4 – Notepad 2 Time Alarm Read Only
266 BV-266 System #4 – Notepad 3 Time Alarm Read Only
267 BV-267 System #4 – Notepad 4 Time Alarm Read Only
268 BV-268 System #4 – Notepad 5 Time Alarm Read Only
269 BV-269 System #4 – Notepad 6 Time Alarm Read Only
270 BV-270 System #4 – Notepad 7 Time Alarm Read Only
271 BV-271 System #4 – Notepad 8 Time Alarm Read Only
272 BV-272 System #4 – Notepad 9 Time Alarm Read Only
273 BV-273 System #4 – Notepad 10 Time Alarm Read Only
277 BV-277 ma Input 1 High Alarm Read Only
278 BV-278 ma Input 1 Low Alarm Read Only
280 BV-280 ma Input 2 High Alarm Read Only
281 BV-281 ma Input 2 Low Alarm Read Only
283 BV-283 ma Input 3 High Alarm Read Only
284 BV-284 ma Input 3 Low Alarm Read Only
286 BV-286 ma Input 4 High Alarm Read Only
287 BV-287 ma Input 4 Low Alarm Read Only
289 BV-289 ma Input 5 High Alarm Read Only
290 BV-290 ma Input 5 Low Alarm Read Only
292 BV-292 ma Input 6 High Alarm Read Only
293 BV-293 ma Input 6 Low Alarm Read Only
295 BV-295 ma Input 7 High Alarm Read Only
296 BV-296 ma Input 7 Low Alarm Read Only
298 BV-298 ma Input 8 High Alarm Read Only
299 BV-299 ma Input 8 Low Alarm Read Only
302 BV-302 Flow Meter 1 Flow Alarm Read Only
303 BV-303 Flow Meter 1 Flow Verify Alarm Read Only
304 BV-304 Flow Meter 1 Volume Alarm Read Only
305 BV-305 Flow Meter 2 Flow Alarm Read Only
306 BV-306 Flow Meter 2 Flow Verify Alarm Read Only
307 BV-307 Flow Meter 2 Volume Alarm Read Only
308 BV-308 Flow Meter 3 Flow Alarm Read Only
309 BV-309 Flow Meter 3 Flow Verify Alarm Read Only
310 BV-310 Flow Meter 3 Volume Alarm Read Only
311 BV-311 Flow Meter 4 Flow Alarm Read Only
312 BV-312 Flow Meter 4 Flow Verify Alarm Read Only
313 BV-313 Flow Meter 4 Volume Alarm Read Only
314 BV-314 Flow Meter 5 Flow Alarm Read Only
315 BV-315 Flow Meter 5 Flow Verify Alarm Read Only
316 BV-216 Flow Meter 5 Volume Alarm Read Only
317 BV-317 Flow Meter 6 Flow Alarm Read Only
318 BV-318 Flow Meter 6 Flow Verify Alarm Read Only
319 BV-319 Flow Meter 6 Volume Alarm Read Only
320 BV-320 Flow Meter 7 Flow Alarm Read Only
321 BV-321 Flow Meter 7 Flow Verify Alarm Read Only
322 BV-322 Flow Meter 7 Volume Alarm Read Only
323 BV-323 Flow Meter 8 Flow Alarm Read Only
324 BV-324 Flow Meter 8 Flow Verify Alarm Read Only
325 BV-325 Flow Meter 8 Volume Alarm Read Only
326 BV-326 Flow Meter 9 Flow Alarm Read Only
327 BV-327 Flow Meter 9 Flow Verify Alarm Read Only
328 BV-328 Flow Meter 9 Volume Alarm Read Only
329 BV-329 Flow Meter 10 Flow Alarm Read Only
330 BV-330 Flow Meter 10 Flow Verify Alarm Read Only
331 BV-331 Flow Meter 10 Volume Alarm Read Only
332 BV-332 Relay 1 Max Hours Read Only
333 BV-333 Relay 2 Max Hours Read Only
334 BV-334 Relay 3 Max Hours Read Only
335 BV-335 Relay 4 Max Hours Read Only
336 BV-336 Relay 5 Max Hours Read Only
337 BV-337 Relay 6 Max Hours Read Only
338 BV-338 Relay 7 Max Hours Read Only
339 BV-339 Relay 8 Max Hours Read Only
340 BV-340 Relay 9 Max Hours Read Only
341 BV-341 Relay 10 Max Hours Read Only
342 BV-342 Relay 11 Max Hours Read Only
343 BV-343 Relay 12 Max Hours Read Only
344 BV-344 Relay 13 Max Hours Read Only
345 BV-345 Relay 14 Max Hours Read Only
346 BV-346 Relay 15 Max Hours Read Only
347 BV-347 Relay 16 Max Hours Read Only
348 Bv-348 Relay 17 Max Hours Read Only
349 BV-349 Relay 18 Max Hours Read Only
350 BV-350 Relay 19 Max Hours Read Only
351 BV-351 Relay 20 Max Hours Read Only
352 BV-352 mA Input 1 Limit Read Only
353 BV-353 mA Input 2 Limit Read Only
354 BV-354 mA Input 3 Limit Read Only
355 BV-355 mA Input 4 Limit Read Only
356 BV-356 mA Input 5 Limit Read Only
357 BV-357 mA Input 6 Limit Read Only
358 BV-358 mA Input 7 Limit Read Only
359 BV-359 mA Input 8 Limit Read Only
360 BV-360 mA Input 9 Limit Alarm Read Only
361 BV-361 mA Input 10 Limit Alarm Read Only
362 BV-362 mA Input 11 Limit Alarm Read Only
363 BV-363 mA Input 12 Limit Alarm Read Only
364 BV-369 mA Input 13 Limit Alarm Read Only
365 BV-365 mA Input 14 Limit Alarm Read Only
366 BV-366 mA Input 15 Limit Alarm Read Only
367 BV-367 mA Input 16 Limit Alarm Read Only
369 BV-369 ma Input 9 High Alarm Read Only
370 BV-370 ma Input 9 Low Alarm Read Only
372 BV-372 ma Input 10 High Alarm Read Only
373 BV-373 ma Input 10 Low Alarm Read Only
375 BV-375 ma Input 11 High Alarm Read Only
376 BV-376 ma Input 11 Low Alarm Read Only
378 BV-378 ma Input 12 High Alarm Read Only
379 BV-379 ma Input 12 Low Alarm Read Only
381 BV-381 ma Input 13 High Alarm Read Only
382 BV-382 ma Input 13 Low Alarm Read Only
384 BV-384 ma Input 14 High Alarm Read Only
385 BV-385 ma Input 14 Low Alarm Read Only
387 BV-387 ma Input 15 High Alarm Read Only
388 BV-388 ma Input 15 Low Alarm Read Only
390 BV-390 ma Input 16 High Alarm Read Only
391 BV-391 ma Input 16 Low Alarm Read Only

Analog Input Object Instance Summary (Table 1-4)

Instance ID Object Name Purpose Present Value – Access
0 AI-000 System #1 – Conductivity Read Only
1 AI-001 System #2 – Conductivity Read Only
2 AI-002 System #3 – Conductivity Read Only
3 AI-003 System #4 – Conductivity Read Only
4 AI-004 System #1 – M. Conductivity Read Only
5 AI-005 System #2 – M. Conductivity Read Only
6 AI-006 System #3 – M. Conductivity Read Only
7 AI-007 System #4 – M. Conductivity Read Only
8 AI-008 System #1 – pH Read Only
9 AI-009 System #2 – pH Read Only
10 AI-010 System #3 – pH Read Only
11 AI-011 System #4 – pH Read Only
12 AI-012 System #1 – ORP Read Only
13 AI-013 System #2 – ORP Read Only
14 AI-014 System #3 – ORP Read Only
15 AI-015 System #4 – ORP Read Only
16 AI-016 System #1 – S. Temp Read Only
17 AI-017 System #2 – S. Temp Read Only
18 AI-018 System #3 – S. Temp Read Only
19 AI-019 System #4 – S. Temp Read Only
20 AI-020 System #1 – M. Temp Read Only
21 AI-021 System #2 – M. Temp Read Only
22 AI-022 System #3 – M. Temp Read Only
23 AI-023 System #4 – M. Temp Read Only
24 AI-024 Sys #1 – Water Meter #1 – Total Value Read Only
25 AI-025 Sys #2 – Water Meter #1 – Total Value Read Only
26 AI-026 Sys #3 – Water Meter #1 – Total Value Read Only
27 AI-027 Sys #4 – Water Meter #1 – Total Value Read Only
28 AI-028 Sys #1 – Water Meter #2 – Total Value Read Only
29 AI-029 Sys #2 – Water Meter #2 – Total Value Read Only
30 AI-030 Sys #3 – Water Meter #2 – Total Value Read Only
31 AI-031 Sys #4 – Water Meter #2 – Total Value Read Only
32 AI-032 System #1 – M.Cycles Read Only
33 AI-033 System #2 – M.Cycles Read Only
34 AI-034 System #3 – M.Cycles Read Only
35 AI-035 System #4 – M.Cycles Read Only
36 AI-036 4-20 mA / 0-5V Input #1 – Value Read Only
37 AI-037 4-20 mA / 0-5V Input #2 – Value Read Only
38 AI-038 4-20 mA / 0-5V Input #3 – Value Read Only
39 AI-039 4-20 mA / 0-5V Input #4 – Value Read Only
40 AI-040 4-20 mA / 0-5V Input #5 – Value Read Only
41 AI-041 4-20 mA / 0-5V Input #6 – Value Read Only
42 AI-042 4-20 mA / 0-5V Input #7 – Value Read Only
43 AI-043 4-20 mA / 0-5V Input #8 – Value Read Only
44 AI-044 Flow Meter #1 – Total Value Read Only
45 AI-045 Flow Meter #2 – Contact Value Read Only
46 AI-046 Flow Meter #3 – Contact Value Read Only
47 AI-047 Flow Meter #4 – Contact Value Read Only
48 AI-048 Flow Meter #5 – Contact Value Read Only
49 AI-049 Flow Meter #6 – Contact Value Read Only
50 AI-050 Flow Meter #7 – Contact Value Read Only
51 AI-051 Flow Meter #8 – Contact Value Read Only
52 AI-052 Flow Meter #9 – Contact Value Read Only
53 AI-053 Flow Meter #10 – Contact Value Read Only
54 AI-054 Flow Meter #1 – Flow Rate (per MIN) Read Only
55 AI-055 Flow Meter #2 – Flow Rate (per MIN) Read Only
56 AI-056 Flow Meter #3 – Flow Rate (per MIN) Read Only
57 AI-057 Flow Meter #4 – Flow Rate (per MIN) Read Only
58 AI-058 Flow Meter #5 – Flow Rate (per MIN) Read Only
59 AI-059 Flow Meter #6 – Flow Rate (per MIN) Read Only
60 AI-060 Flow Meter #7 – Flow Rate (per MIN) Read Only
61 AI-061 Flow Meter #8 – Flow Rate (per MIN) Read Only
62 AI-062 Flow Meter #9 – Flow Rate (per MIN) Read Only
63 AI-063 Flow Meter #10 – Flow Rate (per MIN) Read Only
64 AI-064 4-20 mA / 0-5V Input #9 – Value Read Only
65 AI-065 4-20 mA / 0-5V Input #10 – Value Read Only
66 AI-066 4-20 mA / 0-5V Input #11 – Value Read Only
67 AI-067 4-20 mA / 0-5V Input #12 – Value Read Only
68 AI-068 4-20 mA / 0-5V Input #13 – Value Read Only
69 AI-069 4-20 mA / 0-5V Input #14 – Value Read Only
70 AI-070 4-20 mA / 0-5V Input #15 – Value Read Only
71 AI-071 4-20 mA / 0-5V Input #16 – Value Read Only

Analog Value Object Instance Summary (Table 1-5)

Instance ID Object Name Purpose Present Value – Access
0 AV-000 System #1 – Conductivity Setpoint #1 Read Only
1 AV-001 System #2 – Conductivity Setpoint #1 Read Only
2 AV-002 System #3 – Conductivity Setpoint #1 Read Only
3 AV-003 System #4 – Conductivity Setpoint #1 Read Only
4 AV-004 System #1 – Conductivity Setpoint #2 Read Only
5 AV-005 System #2 – Conductivity Setpoint #2 Read Only
6 AV-006 System #3 – Conductivity Setpoint #2 Read Only
7 AV-007 System #4 – Conductivity Setpoint #2 Read Only
8 AV-008 System #1 – Conductivity High Alarm Read Only
9 AV-009 System #2 – Conductivity High Alarm Read Only
10 AV-010 System #3 – Conductivity High Alarm Read Only
11 AV-011 System #4 – Conductivity High Alarm Read Only
12 AV-012 System #1 – Conductivity Low Alarm Read Only
13 AV-013 System #2 – Conductivity Low Alarm Read Only
14 AV-014 System #3 – Conductivity Low Alarm Read Only
15 AV-015 System #4 – Conductivity Low Alarm Read Only
16 AV-016 System #1 – M. Conductivity Setpoint Read Only
17 AV-017 System #2 – M. Conductivity Setpoint Read Only
18 AV-018 System #3 – M. Conductivity Setpoint Read Only
19 AV-019 System #4 – M. Conductivity Setpoint Read Only
20 AV-020 System #1 – M. Conductivity High Alarm Read Only
21 AV-021 System #2 – M. Conductivity High Alarm Read Only
22 AV-022 System #3 – M. Conductivity High Alarm Read Only
23 AV-023 System #4 – M. Conductivity High Alarm Read Only
24 AV-024 System #1 – M. Conductivity Low Alarm Read Only
25 AV-025 System #2 – M. Conductivity Low Alarm Read Only
26 AV-026 System #3 – M. Conductivity Low Alarm Read Only
27 AV-027 System #4 – M. Conductivity Low Alarm Read Only
28 AV-028 System #1 – pH Setpoint #1 Read Only
29 AV-029 System #2 – pH Setpoint #1 Read Only
30 AV-030 System #3 – pH Setpoint #1 Read Only
31 AV-031 System #4 – pH Setpoint #1 Read Only
32 AV-032 System #1 – pH Setpoint #2 Read Only
33 AV-033 System #2 – pH Setpoint #2 Read Only
34 AV-034 System #3 – pH Setpoint #2 Read Only
35 AV-035 System #4 – pH Setpoint #2 Read Only
36 AV-036 System #1 – pH High Alarm Read Only
37 AV-037 System #2 – pH High Alarm Read Only
38 AV-038 System #3 – pH High Alarm Read Only
39 AV-039 System #4 – pH High Alarm Read Only
40 AV-040 System #1 – pH Low Alarm Read Only
41 AV-041 System #2 – pH Low Alarm Read Only
42 AV-042 System #3 – pH Low Alarm Read Only
43 AV-043 System #4 – pH Low Alarm Read Only
44 AV-044 System #1 – ORP Setpoint #1 Read Only
45 AV-045 System #2 – ORP Setpoint #1 Read Only
46 AV-046 System #3 – ORP Setpoint #1 Read Only
47 AV-047 System #4 – ORP Setpoint #1 Read Only
48 AV-048 System #1 – ORP Setpoint #2 Read Only
49 AV-049 System #2 – ORP Setpoint #2 Read Only
50 AV-050 System #3 – ORP Setpoint #2 Read Only
51 AV-051 System #4 – ORP Setpoint #2 Read Only
52 AV-052 System #1 – ORP High Alarm Read Only
53 AV-053 System #2 – ORP High Alarm Read Only
54 AV-054 System #3 – ORP High Alarm Read Only
55 AV-055 System #4 – ORP High Alarm Read Only
56 AV-056 System #1 – ORP Low Alarm Read Only
57 AV-057 System #2 – ORP Low Alarm Read Only
58 AV-058 System #3 – ORP Low Alarm Read Only
59 AV-059 System #4 – ORP Low Alarm Read Only
60 AV-060 System #1 – S. Temp Setpoint Read Only
61 AV-061 System #2 – S. Temp Setpoint Read Only
62 AV-062 System #3 – S. Temp Setpoint Read Only
63 AV-063 System #4 – S. Temp Setpoint Read Only
64 AV-064 System #1 – S. Temp High Alarm Read Only
65 AV-065 System #2 – S. Temp High Alarm Read Only
66 AV-066 System #3 – S. Temp High Alarm Read Only
67 AV-067 System #4 – S. Temp High Alarm Read Only
68 AV-068 System #1 – S. Temp Low Alarm Read Only
69 AV-069 System #2 – S. Temp Low Alarm Read Only
70 AV-070 System #3 – S. Temp Low Alarm Read Only
71 AV-071 System #4 – S. Temp Low Alarm Read Only
72 AV-072 System #1 – M. Temp Setpoint Read Only
73 AV-073 System #2 – M. Temp Setpoint Read Only
74 AV-074 System #3 – M. Temp Setpoint Read Only
75 AV-075 System #4 – M. Temp Setpoint Read Only
76 AV-076 System #1 – M. Temp High Alarm Read Only
77 AV-077 System #2 – M. Temp High Alarm Read Only
78 AV-078 System #3 – M. Temp High Alarm Read Only
79 AV-079 System #4 – M. Temp High Alarm Read Only
80 AV-080 System #1 – M. Temp Low Alarm Read Only
81 AV-081 System #2 – M. Temp Low Alarm Read Only
82 AV-082 System #3 – M. Temp Low Alarm Read Only
83 AV-083 System #4 – M. Temp Low Alarm Read Only
84 AV-084 System #1 – D. Temp Setpoint Read Only
85 AV-085 System #2 – D. Temp Setpoint Read Only
86 AV-086 System #3 – D. Temp Setpoint Read Only
87 AV-087 System #4 – D. Temp Setpoint Read Only
88 AV-088 System #1 – D. Temp High Alarm Read Only
89 AV-089 System #2 – D. Temp High Alarm Read Only
90 AV-090 System #3 – D. Temp High Alarm Read Only
91 AV-091 System #4 – D. Temp High Alarm Read Only
92 AV-092 System #1 – D. Temp Low Alarm Read Only
93 AV-093 System #2 – D. Temp Low Alarm Read Only
94 AV-094 System #3 – D. Temp Low Alarm Read Only
95 AV-095 System #4 – D. Temp Low Alarm Read Only
96 AV-096 System #1 – Flow Switch Conf. Read Only
97 AV-097 System #2 – Flow Switch Conf. Read Only
98 AV-098 System #3 – Flow Switch Conf. Read Only
99 AV-099 System #4 – Flow Switch Conf. Read Only
100 AV-100 mA 1 – Output Value Read Only
101 AV-101 mA 2 – Output Value Read Only
102 AV-102 mA 3 – Output Value Read Only
103 AV-103 mA 4 – Output Value Read Only
104 AV-104 mA 5 – Output Value Read Only
105 AV-105 mA 6 – Output Value Read Only
106 AV-106 System #1 – Timer #1 – Run Time Read Only
107 AV-107 System #1 – Timer #2 – Run Time Read Only
108 AV-108 System #1 – Timer #3 – Run Time Read Only
109 AV-109 System #1 – Timer #4 – Run Time Read Only
110 AV-110 System #1 – Timer #5 – Run Time Read Only
111 AV-111 System #2 – Timer #1 – Run Time Read Only
112 AV-112 System #2 – Timer #2 – Run Time Read Only
113 AV-113 System #2 – Timer #3 – Run Time Read Only
114 AV-114 System #2 – Timer #4 – Run Time Read Only
115 AV-115 System #2 – Timer #5 – Run Time Read Only
116 AV-116 System #3 – Timer #1 – Run Time Read Only
117 AV-117 System #3 – Timer #2 – Run Time Read Only
118 AV-118 System #3 – Timer #3 – Run Time Read Only
119 AV-119 System #3 – Timer #4 – Run Time Read Only
120 AV-120 System #3 – Timer #5 – Run Time Read Only
121 AV-121 System #4 – Timer #1 – Run Time Read Only
122 AV-122 System #4 – Timer #2 – Run Time Read Only
123 AV-123 System #4 – Timer #3 – Run Time Read Only
124 AV-124 System #4 – Timer #4 – Run Time Read Only
125 AV-125 System #4 – Timer #5 – Run Time Read Only
126 AV-126 Read-Only Read Only

Multi-State Value Object Instance Summary (Table 1-6)
Note #1 1=H-OFF 2=H-ON 3=OFF  4=ON

Instance ID Object Name Purpose Present Value – Access
0 MSV-000 Relay 1 – State Read Only
1 MSV-001 Relay 2 – State Read Only
2 MSV-002 Relay 3 – State Read Only
3 MSV-003 Relay 4 – State Read Only
4 MSV-004 Relay 5 – State Read Only
5 MSV-005 Relay 6 – State Read Only
6 MSV-006 Relay 7 – State Read Only
7 MSV-007 Relay 8 – State Read Only
8 MSV-008 Relay 9 – State Read Only
9 MSV-009 Relay 10 – State Read Only
10 MSV-010 Relay 11 – State Read Only
11 MSV-011 Relay 12 – State Read Only
12 MSV-012 Relay 13 – State Read Only
13 MSV-013 Relay 14 – State Read Only
14 MSV-014 Relay 15 – State Read Only
15 MSV-015 Relay 16 – State Read Only
16 MSV-016 Relay 17 – State Read Only
17 MSV-017 Relay 18 – State Read Only
18 MSV-018 Relay 19 – State Read Only
19 MSV-019 Relay 20 – State Read Only

Get the Advantage in Water Treatment Equipment

Advantage Controls can give you the Advantage in products, knowledge and support on all of your water treatment equipment needs.

  • Cooling Tower Controllers
  • Boiler Blow Down Controllers
  • Blow Down Valve Packages
  • Solenoid Valves
  • Water Meters
  • Chemical Metering Pumps
  • Corrosion Coupon Racks
  • Chemical Solution Tanks
  • Solid Feed Systems
  • Feed Timers
  • Filter Equipment
  • Glycol Feed Systems
  • Pre Fabricated Systems

Advantage-Controls-H21-Mega-Tron-Controller-(3)

Advantage-Controls-H21-Mega-Tron-Controller-(4)

Documents / Resources

Advantage Controls H21 Mega Tron Controller [pdf] Instruction Manual
H21, H25, H21 Mega Tron Controller, H21, Mega Tron Controller, Tron Controller, Controller

References

Leave a comment

Your email address will not be published. Required fields are marked *