Advantage Controls H21 Mega Tron Controller
Advantage Controls
4700 Harold-Abitz Dr.
Muskogee, OK 74403
- Phone: 800-743-7431
- Fax: 888-686-6212
- www.advantagecontrols.com
- email: support@advantagecontrols.com
BACnet Introduction
The MegaTron controller is capable of connecting to the WebAdvantage Server and most Building Management Systems. The WebAdvantage service requires a gateway to the internet with firewall and security rules in place. The Building Management System needs to be on the same subnet to properly receive traffic from the MegaTron. This may require some advanced routing of network traffic within the network wiring or programming of advanced switching equipment. The datatraffic for both is provided via the same Ethernet cable coming from the MegaTron. The BACnet protocol allows interfacing with more customizable PC applications using HMI/SCADA and stand-alone HMI systems
BACnet Overview
BACnet is an American National Standard. The BACnet protocol allows the creation of an automation and controls system which may interoperate with other BACnet systems. In BACnet terms, interoperate means that two or more BACnet-speaking computer systems may share the same communications networks, and ask each other to perform various functions on a peer-to-peer basis. BACnet’s flexibility has two important benefits: vendor-independence and forward-compatibility with future generations of systems. This is accomplished using an object-oriented approach for representing all information within each controller. Since BACnet is based on standards, it provides maximum benefits for both the vendor who designs BACnet systems, and the specifier or owner of those systems.
Protocal Implementation Conformance Summary (Annex-A)
- Applications Software Version: JA.12.1 and higher
- Firmware Revision: JA.12.1 and higher
- BACnet Protocol Revision: 6
- BACnet Standardized Device Profile (Annex L): BACnet Application Specific Controller (B-ASC)
- BACnet Interoperability Building Blocks Supported (Annex K):
- DS-RP-B
- DM-DDB-B
- DM-DCC-B
- DM-RD-B
- Standard Object Types Supported: See table 3-1 “Object/Property Support Matrix”.
- Data Link Layer Options: BACnet IP, (Annex J)
- Character Set Supported: ANSI X3.4
Connecting to BACnet enabled MegaTron
This guide is designed to help with connecting a BACnet enabled MegaTron to a local BMS.
Note: Screens may vary slightly between models.
BACnet Setup
Step 1:
Press Setup/Run, CONFIGURE, NETWORK, SETTINGS.
(See figures 1, 2, 3 and 4. H25 dual cards add figure 3B. H25 only available for MegaTron MT.)
Step 2:
Press BAC.
(See figure 4.)
Note: If these options are not visible, the dual network card needs to be enabled. See enabling dual network card to continue setup.
Step 3:
Enter the DEVICE INSTANCE and PORT. Press Enter to accept on each.
(See figure 6.)
Step 4:
Press RESET and then press Enter to accept. The communications card will reset after a short countdown.
(See figures 7 and 8.)
Step 5:
After the communications card has been reset cycle power to the controller.
MegaTron XS Setup
The MegaTron XS will be a “device object” on the particular BACnet network. Each device object (your MegaTron XS) must have an object identifier that is unique network wide. The device object instance number is normally configured on site after the device is installed. The device object instance number range is between 0 and 4194303. Note that 4194303 is known as “unconfigured” and is not really a valid device instance number. All devices are required to respond with their own Device object instance number when 4194303 is requested. To enter your device object identifier, go to the Configure menu in the MegaTron XS and select the Network settings. Then select BAC.
Object Definitions
Object / Property Support Matrix (Table 1-1)
Property | Object Type | |||||
Device | Binary Input | Binary Value | Analog Input | Analog Value | Multi-State Value | |
Object Identifier | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ |
Object Name | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ |
Object Type | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ |
Description | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ |
System Status | ✓ | |||||
Vendor Name | ✓ | |||||
Vendor Identifier | ✓ | |||||
Model Name | ✓ | |||||
Firmware Revision | ✓ | |||||
App. Software Revision | ✓ | |||||
Protocol Version | ✓ | |||||
Protocol Revision | ✓ |
Services Supported | ✓ | |||||
Object Types Supported | ✓ | |||||
Object List | ✓ | |||||
Max APDU Length | ✓ | |||||
Segmentation Support | ✓ | |||||
APDU Timeout | ✓ | |||||
Number APDU Retries | ✓ | |||||
Database Revision | ✓ | |||||
Present Value | ✓ | ✓ | ✓ | ✓ | ✓ | |
Status Flags | ✓ | ✓ | ✓ | ✓ | ✓ | |
Event State | ✓ | ✓ | ✓ | ✓ | ✓ | |
Out-of-Service | ✓ | ✓ | ✓ | ✓ | ✓ | |
Units | ✓ | ✓ | ||||
Polarity | ✓ | ✓ | ||||
Number of States | ✓ | |||||
State Text | ✓ |
Binary Input Object Instance Summary (Table 1-2)
Instance ID | Object Name | Purpose | Present Value – Access |
0 | BI-000 | System #1 – Flow Switch | Read Only |
1 | BI-001 | System #2 – Flow Switch | Read Only |
2 | BI-002 | System #3 – Flow Switch | Read Only |
3 | BI-003 | System #4 – Flow Switch | Read Only |
Binary Value Object Instance Summary (Table 1-3)
Instance ID | Object Name | Purpose | Present Value – Access |
12 | BV-012 | System #1 – Conductivity High Alarm | Read Only |
13 | BV-013 | System #1 – Conductivity Low Alarm | Read Only |
14 | BV-014 | System #1 – Conductivity Limit Alarm | Read Only |
15 | BV-015 | System #1 – pH High Alarm | Read Only |
16 | BV-016 | System #1 – pH Low Alarm | Read Only |
17 | BV-017 | System #1 – pH Limit Alarm | Read Only |
18 | BV-018 | System #1 – ORP High Alarm | Read Only |
19 | BV-019 | System #1 – ORP Low Alarm | Read Only |
20 | BV-020 | System #1 – ORP Limit Alarm | Read Only |
21 | BV-021 | System #1 – S. Temp High Alarm | Read Only |
22 | BV-022 | System #1 – S. Temp Low Alarm | Read Only |
23 | BV-023 | System #1 – M. Temp High Alarm | Read Only |
24 | BV-024 | System #1 – M. Temp Low Alarm | Read Only |
25 | BV-025 | System #1 – D. Temp High Alarm | Read Only |
26 | BV-026 | System #1 – D. Temp Low Alarm | Read Only |
27 | BV-027 | System #1 – No Flow Alarm | Read Only |
28 | BV-028 | System #1 – Digital Input 1 Alarm | Read Only |
29 | BV-029 | System #1 – Digital Input 2 Alarm | Read Only |
30 | BV-030 | System #1 – Digital Input 3 Alarm | Read Only |
31 | BV-031 | System #1 – Digital Input 4 Alarm | Read Only |
32 | BV-032 | System #1 – Digital Input 5 Alarm | Read Only |
34 | BV-034 | System #1 – M. Conductivity High Alarm | Read Only |
35 | BV-035 | System #1 – M. Conductivity Low Alarm | Read Only |
36 | BV-036 | System #1 – M. Conductivity Limit Alarm | Read Only |
37 | BV-037 | System #1 – Notepad 1 High Alarm | Read Only |
38 | BV-038 | System #1 – Notepad 2 High Alarm | Read Only |
39 | BV-039 | System #1 – Notepad 3 High Alarm | Read Only |
40 | BV-040 | System #1 – Notepad 4 High Alarm | Read Only |
41 | BV-041 | System #1 – Notepad 5 High Alarm | Read Only |
42 | BV-042 | System #1 – Notepad 6 High Alarm | Read Only |
43 | BV-043 | System #1 – Notepad 7 High Alarm | Read Only |
44 | BV-044 | System #1 – Notepad 8 High Alarm | Read Only |
45 | BV-045 | System #1 – Notepad 9 High Alarm | Read Only |
46 | BV-046 | System #1 – Notepad 10 High Alarm | Read Only |
47 | BV-047 | System #1 – Notepad 1 Low Alarm | Read Only |
48 | BV-048 | System #1 – Notepad 2 Low Alarm | Read Only |
49 | BV-049 | System #1 – Notepad 3 Low Alarm | Read Only |
50 | BV-050 | System #1 – Notepad 4 Low Alarm | Read Only |
51 | BV-051 | System #1 – Notepad 5 Low Alarm | Read Only |
52 | BV-052 | System #1 – Notepad 6 Low Alarm | Read Only |
53 | BV-053 | System #1 – Notepad 7 Low Alarm | Read Only |
54 | BV-054 | System #1 – Notepad 8 Low Alarm | Read Only |
55 | BV-055 | System #1 – Notepad 9 Low Alarm | Read Only |
56 | BV-056 | System #1 – Notepad 10 Low Alarm | Read Only |
57 | BV-057 | System #1 – Notepad 1 Time Alarm | Read Only |
58 | BV-058 | System #1 – Notepad 2 Time Alarm | Read Only |
59 | BV-059 | System #1 – Notepad 3 Time Alarm | Read Only |
60 | BV-060 | System #1 – Notepad 4 Time Alarm | Read Only |
61 | BV-061 | System #1 – Notepad 5 Time Alarm | Read Only |
62 | BV-062 | System #1 – Notepad 6 Time Alarm | Read Only |
63 | BV-063 | System #1 – Notepad 7 Time Alarm | Read Only |
64 | BV-064 | System #1 – Notepad 8 Time Alarm | Read Only |
65 | BV-065 | System #1 – Notepad 9 Time Alarm | Read Only |
66 | BV-066 | System #1 – Notepad 10 Time Alarm | Read Only |
81 | BV-081 | System #2 – Conductivity High Alarm | Read Only |
82 | BV-082 | System #2 – Conductivity Low Alarm | Read Only |
83 | BV-083 | System #2 – Conductivity Limit Alarm | Read Only |
84 | BV-084 | System #2 – pH High Alarm | Read Only |
85 | BV-085 | System #2 – pH Low Alarm | Read Only |
86 | BV-086 | System #2 – pH Limit Alarm | Read Only |
87 | BV-087 | System #2 – ORP High Alarm | Read Only |
88 | BV-088 | System #2 – ORP Low Alarm | Read Only |
89 | BV-089 | System #2 – ORP Limit Alarm | Read Only |
90 | BV-090 | System #2 – S. Temp High Alarm | Read Only |
91 | BV-091 | System #2 – S. Temp Low Alarm | Read Only |
92 | BV-092 | System #2 – M. Temp High Alarm | Read Only |
93 | BV-093 | System #2 – M. Temp Low Alarm | Read Only |
94 | BV-094 | System #2 – D. Temp High Alarm | Read Only |
95 | BV-095 | System #2 – D. Temp Low Alarm | Read Only |
96 | BV-096 | System #2 – No Flow Alarm | Read Only |
97 | BV-097 | System #2 – Digital Input 1 Alarm | Read Only |
98 | BV-098 | System #2 – Digital Input 2 Alarm | Read Only |
99 | BV-099 | System #2 – Digital Input 3 Alarm | Read Only |
100 | BV-100 | System #2 – Digital Input 4 Alarm | Read Only |
101 | BV-101 | System #2 – Digital Input 5 Alarm | Read Only |
103 | BV-103 | System #2 – M. Conductivity High Alarm | Read Only |
104 | BV-104 | System #2 – M. Conductivity Low Alarm | Read Only |
105 | BV-105 | System #2 – M. Conductivity Limit Alarm | Read Only |
106 | BV-106 | System #2 – Notepad 1 High Alarm | Read Only |
107 | BV-107 | System #2 – Notepad 2 High Alarm | Read Only |
108 | BV-108 | System #2 – Notepad 3 High Alarm | Read Only |
109 | BV-109 | System #2 – Notepad 4 High Alarm | Read Only |
110 | BV-110 | System #2 – Notepad 5 High Alarm | Read Only |
111 | BV-111 | System #2 – Notepad 6 High Alarm | Read Only |
112 | BV-112 | System #2 – Notepad 7 High Alarm | Read Only |
113 | BV-113 | System #2 – Notepad 8 High Alarm | Read Only |
114 | BV-114 | System #2 – Notepad 9 High Alarm | Read Only |
115 | BV-115 | System #2 – Notepad 10 High Alarm | Read Only |
116 | BV-116 | System #2 – Notepad 1 Low Alarm | Read Only |
117 | BV-117 | System #2 – Notepad 2 Low Alarm | Read Only |
118 | BV-118 | System #2 – Notepad 3 Low Alarm | Read Only |
119 | BV-119 | System #2 – Notepad 4 Low Alarm | Read Only |
120 | BV-120 | System #2 – Notepad 5 Low Alarm | Read Only |
121 | BV-121 | System #2 – Notepad 6 Low Alarm | Read Only |
122 | BV-122 | System #2 – Notepad 7 Low Alarm | Read Only |
123 | BV-123 | System #2 – Notepad 8 Low Alarm | Read Only |
124 | BV-124 | System #2 – Notepad 9 Low Alarm | Read Only |
125 | BV-125 | System #2 – Notepad 10 Low Alarm | Read Only |
126 | BV-126 | System #2 – Notepad 1 Time Alarm | Read Only |
127 | BV-127 | System #2 – Notepad 2 Time Alarm | Read Only |
128 | BV-128 | System #2 – Notepad 3 Time Alarm | Read Only |
129 | BV-129 | System #2 – Notepad 4 Time Alarm | Read Only |
130 | BV-130 | System #2 – Notepad 5 Time Alarm | Read Only |
131 | BV-131 | System #2 – Notepad 6 Time Alarm | Read Only |
132 | BV-132 | System #2 – Notepad 7 Time Alarm | Read Only |
133 | BV-133 | System #2 – Notepad 8 Time Alarm | Read Only |
134 | BV-134 | System #2 – Notepad 9 Time Alarm | Read Only |
135 | BV-135 | System #2 – Notepad 10 Time Alarm | Read Only |
150 | BV-150 | System #3 – Conductivity High Alarm | Read Only |
151 | BV-151 | System #3 – Conductivity Low Alarm | Read Only |
152 | BV-152 | System #3 – Conductivity Limit Alarm | Read Only |
153 | BV-153 | System #3 – pH High Alarm | Read Only |
154 | BV-154 | System #3 – pH Low Alarm | Read Only |
155 | BV-155 | System #3 – pH Limit Alarm | Read Only |
156 | BV-156 | System #3 – ORP High Alarm | Read Only |
157 | BV-157 | System #3 – ORP Low Alarm | Read Only |
158 | BV-158 | System #3 – ORP Limit Alarm | Read Only |
159 | BV-159 | System #3 – S. Temp High Alarm | Read Only |
160 | BV-160 | System #3 – S. Temp Low Alarm | Read Only |
161 | BV-161 | System #3 – M. Temp High Alarm | Read Only |
162 | BV-162 | System #3 – M. Temp Low Alarm | Read Only |
163 | BV-163 | System #3 – D. Temp High Alarm | Read Only |
164 | BV-164 | System #3 – D. Temp Low Alarm | Read Only |
165 | BV-165 | System #3 – No Flow Alarm | Read Only |
166 | BV-166 | System #3 – Digital Input 1 Alarm | Read Only |
167 | BV-167 | System #3 – Digital Input 2 Alarm | Read Only |
168 | BV-168 | System #3 – Digital Input 3 Alarm | Read Only |
169 | BV-169 | System #3 – Digital Input 4 Alarm | Read Only |
170 | BV-170 | System #3 – Digital Input 5 Alarm | Read Only |
172 | BV-172 | System #3 – M. Conductivity High Alarm | Read Only |
173 | BV-173 | System #3 – M. Conductivity Low Alarm | Read Only |
174 | BV-174 | System #3 – M. Conductivity Limit Alarm | Read Only |
175 | BV-175 | System #3 – Notepad 1 High Alarm | Read Only |
176 | BV-176 | System #3 – Notepad 2 High Alarm | Read Only |
177 | BV-177 | System #3 – Notepad 3 High Alarm | Read Only |
178 | BV-178 | System #3 – Notepad 4 High Alarm | Read Only |
179 | BV-179 | System #3 – Notepad 5 High Alarm | Read Only |
180 | BV-180 | System #3 – Notepad 6 High Alarm | Read Only |
181 | BV-181 | System #3 – Notepad 7 High Alarm | Read Only |
182 | BV-182 | System #3 – Notepad 8 High Alarm | Read Only |
183 | BV-183 | System #3 – Notepad 9 High Alarm | Read Only |
184 | BV-184 | System #3 – Notepad 10 High Alarm | Read Only |
185 | BV-185 | System #3 – Notepad 1 Low Alarm | Read Only |
186 | BV-186 | System #3 – Notepad 2 Low Alarm | Read Only |
187 | BV-187 | System #3 – Notepad 3 Low Alarm | Read Only |
188 | BV-188 | System #3 – Notepad 4 Low Alarm | Read Only |
189 | BV-189 | System #3 – Notepad 5 Low Alarm | Read Only |
190 | BV-190 | System #3 – Notepad 6 Low Alarm | Read Only |
191 | BV-191 | System #3 – Notepad 7 Low Alarm | Read Only |
192 | BV-192 | System #3 – Notepad 8 Low Alarm | Read Only |
193 | BV-193 | System #3 – Notepad 9 Low Alarm | Read Only |
194 | BV-194 | System #3 – Notepad 10 Low Alarm | Read Only |
195 | BV-195 | System #3 – Notepad 1 Time Alarm | Read Only |
196 | BV-196 | System #3 – Notepad 2 Time Alarm | Read Only |
197 | BV-197 | System #3 – Notepad 3 Time Alarm | Read Only |
198 | BV-198 | System #3 – Notepad 4 Time Alarm | Read Only |
199 | BV-199 | System #3 – Notepad 5 Time Alarm | Read Only |
200 | BV-200 | System #3 – Notepad 6 Time Alarm | Read Only |
201 | BV-201 | System #3 – Notepad 7 Time Alarm | Read Only |
202 | BV-202 | System #3 – Notepad 8 Time Alarm | Read Only |
203 | BV-203 | System #3 – Notepad 9 Time Alarm | Read Only |
204 | BV-204 | System #3 – Notepad 10 Time Alarm | Read Only |
219 | BV-219 | System #4 – Conductivity High Alarm | Read Only |
220 | BV-220 | System #4 – Conductivity Low Alarm | Read Only |
221 | BV-221 | System #4 – Conductivity Limit Alarm | Read Only |
222 | BV-222 | System #4 – pH High Alarm | Read Only |
223 | BV-223 | System #4 – pH Low Alarm | Read Only |
224 | BV-224 | System #4 – pH Limit Alarm | Read Only |
225 | BV-225 | System #4 – ORP High Alarm | Read Only |
226 | BV-226 | System #4 – ORP Low Alarm | Read Only |
227 | BV-227 | System #4 – ORP Limit Alarm | Read Only |
228 | BV-228 | System #4 – S. Temp High Alarm | Read Only |
229 | BV-229 | System #4 – S. Temp Low Alarm | Read Only |
230 | BV-230 | System #4 – M. Temp High Alarm | Read Only |
231 | BV-231 | System #4 – M. Temp Low Alarm | Read Only |
232 | BV-232 | System #4 – D. Temp High Alarm | Read Only |
233 | BV-233 | System #4 – D. Temp Low Alarm | Read Only |
234 | BV-234 | System #4 – No Flow Alarm | Read Only |
235 | BV-235 | System #4 – Digital Input 1 Alarm | Read Only |
236 | BV-236 | System #4 – Digital Input 2 Alarm | Read Only |
237 | BV-237 | System #4 – Digital Input 3 Alarm | Read Only |
238 | BV-238 | System #4 – Digital Input 4 Alarm | Read Only |
239 | BV-239 | System #4 – Digital Input 5 Alarm | Read Only |
241 | BV-241 | System #4 – M. Conductivity High Alarm | Read Only |
242 | BV-242 | System #4 – M. Conductivity Low Alarm | Read Only |
243 | BV-243 | System #4 – M. Conductivity Limit Alarm | Read Only |
244 | BV-244 | System #4 – Notepad 1 High Alarm | Read Only |
245 | BV-245 | System #4 – Notepad 2 High Alarm | Read Only |
246 | BV-246 | System #4 – Notepad 3 High Alarm | Read Only |
247 | BV-247 | System #4 – Notepad 4 High Alarm | Read Only |
248 | BV-248 | System #4 – Notepad 5 High Alarm | Read Only |
249 | BV-249 | System #4 – Notepad 6 High Alarm | Read Only |
250 | BV-250 | System #4 – Notepad 7 High Alarm | Read Only |
251 | BV-251 | System #4 – Notepad 8 High Alarm | Read Only |
252 | BV-252 | System #4 – Notepad 9 High Alarm | Read Only |
253 | BV-253 | System #4 – Notepad 10 High Alarm | Read Only |
254 | BV-254 | System #4 – Notepad 1 Low Alarm | Read Only |
255 | BV-255 | System #4 – Notepad 2 Low Alarm | Read Only |
256 | BV-256 | System #4 – Notepad 3 Low Alarm | Read Only |
257 | BV-257 | System #4 – Notepad 4 Low Alarm | Read Only |
258 | BV-258 | System #4 – Notepad 5 Low Alarm | Read Only |
259 | BV-259 | System #4 – Notepad 6 Low Alarm | Read Only |
260 | BV-260 | System #4 – Notepad 7 Low Alarm | Read Only |
261 | BV-261 | System #4 – Notepad 8 Low Alarm | Read Only |
262 | BV-262 | System #4 – Notepad 9 Low Alarm | Read Only |
263 | BV-263 | System #4 – Notepad 10 Low Alarm | Read Only |
264 | BV-264 | System #4 – Notepad 1 Time Alarm | Read Only |
265 | BV-265 | System #4 – Notepad 2 Time Alarm | Read Only |
266 | BV-266 | System #4 – Notepad 3 Time Alarm | Read Only |
267 | BV-267 | System #4 – Notepad 4 Time Alarm | Read Only |
268 | BV-268 | System #4 – Notepad 5 Time Alarm | Read Only |
269 | BV-269 | System #4 – Notepad 6 Time Alarm | Read Only |
270 | BV-270 | System #4 – Notepad 7 Time Alarm | Read Only |
271 | BV-271 | System #4 – Notepad 8 Time Alarm | Read Only |
272 | BV-272 | System #4 – Notepad 9 Time Alarm | Read Only |
273 | BV-273 | System #4 – Notepad 10 Time Alarm | Read Only |
277 | BV-277 | ma Input 1 High Alarm | Read Only |
278 | BV-278 | ma Input 1 Low Alarm | Read Only |
280 | BV-280 | ma Input 2 High Alarm | Read Only |
281 | BV-281 | ma Input 2 Low Alarm | Read Only |
283 | BV-283 | ma Input 3 High Alarm | Read Only |
284 | BV-284 | ma Input 3 Low Alarm | Read Only |
286 | BV-286 | ma Input 4 High Alarm | Read Only |
287 | BV-287 | ma Input 4 Low Alarm | Read Only |
289 | BV-289 | ma Input 5 High Alarm | Read Only |
290 | BV-290 | ma Input 5 Low Alarm | Read Only |
292 | BV-292 | ma Input 6 High Alarm | Read Only |
293 | BV-293 | ma Input 6 Low Alarm | Read Only |
295 | BV-295 | ma Input 7 High Alarm | Read Only |
296 | BV-296 | ma Input 7 Low Alarm | Read Only |
298 | BV-298 | ma Input 8 High Alarm | Read Only |
299 | BV-299 | ma Input 8 Low Alarm | Read Only |
302 | BV-302 | Flow Meter 1 Flow Alarm | Read Only |
303 | BV-303 | Flow Meter 1 Flow Verify Alarm | Read Only |
304 | BV-304 | Flow Meter 1 Volume Alarm | Read Only |
305 | BV-305 | Flow Meter 2 Flow Alarm | Read Only |
306 | BV-306 | Flow Meter 2 Flow Verify Alarm | Read Only |
307 | BV-307 | Flow Meter 2 Volume Alarm | Read Only |
308 | BV-308 | Flow Meter 3 Flow Alarm | Read Only |
309 | BV-309 | Flow Meter 3 Flow Verify Alarm | Read Only |
310 | BV-310 | Flow Meter 3 Volume Alarm | Read Only |
311 | BV-311 | Flow Meter 4 Flow Alarm | Read Only |
312 | BV-312 | Flow Meter 4 Flow Verify Alarm | Read Only |
313 | BV-313 | Flow Meter 4 Volume Alarm | Read Only |
314 | BV-314 | Flow Meter 5 Flow Alarm | Read Only |
315 | BV-315 | Flow Meter 5 Flow Verify Alarm | Read Only |
316 | BV-216 | Flow Meter 5 Volume Alarm | Read Only |
317 | BV-317 | Flow Meter 6 Flow Alarm | Read Only |
318 | BV-318 | Flow Meter 6 Flow Verify Alarm | Read Only |
319 | BV-319 | Flow Meter 6 Volume Alarm | Read Only |
320 | BV-320 | Flow Meter 7 Flow Alarm | Read Only |
321 | BV-321 | Flow Meter 7 Flow Verify Alarm | Read Only |
322 | BV-322 | Flow Meter 7 Volume Alarm | Read Only |
323 | BV-323 | Flow Meter 8 Flow Alarm | Read Only |
324 | BV-324 | Flow Meter 8 Flow Verify Alarm | Read Only |
325 | BV-325 | Flow Meter 8 Volume Alarm | Read Only |
326 | BV-326 | Flow Meter 9 Flow Alarm | Read Only |
327 | BV-327 | Flow Meter 9 Flow Verify Alarm | Read Only |
328 | BV-328 | Flow Meter 9 Volume Alarm | Read Only |
329 | BV-329 | Flow Meter 10 Flow Alarm | Read Only |
330 | BV-330 | Flow Meter 10 Flow Verify Alarm | Read Only |
331 | BV-331 | Flow Meter 10 Volume Alarm | Read Only |
332 | BV-332 | Relay 1 Max Hours | Read Only |
333 | BV-333 | Relay 2 Max Hours | Read Only |
334 | BV-334 | Relay 3 Max Hours | Read Only |
335 | BV-335 | Relay 4 Max Hours | Read Only |
336 | BV-336 | Relay 5 Max Hours | Read Only |
337 | BV-337 | Relay 6 Max Hours | Read Only |
338 | BV-338 | Relay 7 Max Hours | Read Only |
339 | BV-339 | Relay 8 Max Hours | Read Only |
340 | BV-340 | Relay 9 Max Hours | Read Only |
341 | BV-341 | Relay 10 Max Hours | Read Only |
342 | BV-342 | Relay 11 Max Hours | Read Only |
343 | BV-343 | Relay 12 Max Hours | Read Only |
344 | BV-344 | Relay 13 Max Hours | Read Only |
345 | BV-345 | Relay 14 Max Hours | Read Only |
346 | BV-346 | Relay 15 Max Hours | Read Only |
347 | BV-347 | Relay 16 Max Hours | Read Only |
348 | Bv-348 | Relay 17 Max Hours | Read Only |
349 | BV-349 | Relay 18 Max Hours | Read Only |
350 | BV-350 | Relay 19 Max Hours | Read Only |
351 | BV-351 | Relay 20 Max Hours | Read Only |
352 | BV-352 | mA Input 1 Limit | Read Only |
353 | BV-353 | mA Input 2 Limit | Read Only |
354 | BV-354 | mA Input 3 Limit | Read Only |
355 | BV-355 | mA Input 4 Limit | Read Only |
356 | BV-356 | mA Input 5 Limit | Read Only |
357 | BV-357 | mA Input 6 Limit | Read Only |
358 | BV-358 | mA Input 7 Limit | Read Only |
359 | BV-359 | mA Input 8 Limit | Read Only |
360 | BV-360 | mA Input 9 Limit Alarm | Read Only |
361 | BV-361 | mA Input 10 Limit Alarm | Read Only |
362 | BV-362 | mA Input 11 Limit Alarm | Read Only |
363 | BV-363 | mA Input 12 Limit Alarm | Read Only |
364 | BV-369 | mA Input 13 Limit Alarm | Read Only |
365 | BV-365 | mA Input 14 Limit Alarm | Read Only |
366 | BV-366 | mA Input 15 Limit Alarm | Read Only |
367 | BV-367 | mA Input 16 Limit Alarm | Read Only |
369 | BV-369 | ma Input 9 High Alarm | Read Only |
370 | BV-370 | ma Input 9 Low Alarm | Read Only |
372 | BV-372 | ma Input 10 High Alarm | Read Only |
373 | BV-373 | ma Input 10 Low Alarm | Read Only |
375 | BV-375 | ma Input 11 High Alarm | Read Only |
376 | BV-376 | ma Input 11 Low Alarm | Read Only |
378 | BV-378 | ma Input 12 High Alarm | Read Only |
379 | BV-379 | ma Input 12 Low Alarm | Read Only |
381 | BV-381 | ma Input 13 High Alarm | Read Only |
382 | BV-382 | ma Input 13 Low Alarm | Read Only |
384 | BV-384 | ma Input 14 High Alarm | Read Only |
385 | BV-385 | ma Input 14 Low Alarm | Read Only |
387 | BV-387 | ma Input 15 High Alarm | Read Only |
388 | BV-388 | ma Input 15 Low Alarm | Read Only |
390 | BV-390 | ma Input 16 High Alarm | Read Only |
391 | BV-391 | ma Input 16 Low Alarm | Read Only |
Analog Input Object Instance Summary (Table 1-4)
Instance ID | Object Name | Purpose | Present Value – Access |
0 | AI-000 | System #1 – Conductivity | Read Only |
1 | AI-001 | System #2 – Conductivity | Read Only |
2 | AI-002 | System #3 – Conductivity | Read Only |
3 | AI-003 | System #4 – Conductivity | Read Only |
4 | AI-004 | System #1 – M. Conductivity | Read Only |
5 | AI-005 | System #2 – M. Conductivity | Read Only |
6 | AI-006 | System #3 – M. Conductivity | Read Only |
7 | AI-007 | System #4 – M. Conductivity | Read Only |
8 | AI-008 | System #1 – pH | Read Only |
9 | AI-009 | System #2 – pH | Read Only |
10 | AI-010 | System #3 – pH | Read Only |
11 | AI-011 | System #4 – pH | Read Only |
12 | AI-012 | System #1 – ORP | Read Only |
13 | AI-013 | System #2 – ORP | Read Only |
14 | AI-014 | System #3 – ORP | Read Only |
15 | AI-015 | System #4 – ORP | Read Only |
16 | AI-016 | System #1 – S. Temp | Read Only |
17 | AI-017 | System #2 – S. Temp | Read Only |
18 | AI-018 | System #3 – S. Temp | Read Only |
19 | AI-019 | System #4 – S. Temp | Read Only |
20 | AI-020 | System #1 – M. Temp | Read Only |
21 | AI-021 | System #2 – M. Temp | Read Only |
22 | AI-022 | System #3 – M. Temp | Read Only |
23 | AI-023 | System #4 – M. Temp | Read Only |
24 | AI-024 | Sys #1 – Water Meter #1 – Total Value | Read Only |
25 | AI-025 | Sys #2 – Water Meter #1 – Total Value | Read Only |
26 | AI-026 | Sys #3 – Water Meter #1 – Total Value | Read Only |
27 | AI-027 | Sys #4 – Water Meter #1 – Total Value | Read Only |
28 | AI-028 | Sys #1 – Water Meter #2 – Total Value | Read Only |
29 | AI-029 | Sys #2 – Water Meter #2 – Total Value | Read Only |
30 | AI-030 | Sys #3 – Water Meter #2 – Total Value | Read Only |
31 | AI-031 | Sys #4 – Water Meter #2 – Total Value | Read Only |
32 | AI-032 | System #1 – M.Cycles | Read Only |
33 | AI-033 | System #2 – M.Cycles | Read Only |
34 | AI-034 | System #3 – M.Cycles | Read Only |
35 | AI-035 | System #4 – M.Cycles | Read Only |
36 | AI-036 | 4-20 mA / 0-5V Input #1 – Value | Read Only |
37 | AI-037 | 4-20 mA / 0-5V Input #2 – Value | Read Only |
38 | AI-038 | 4-20 mA / 0-5V Input #3 – Value | Read Only |
39 | AI-039 | 4-20 mA / 0-5V Input #4 – Value | Read Only |
40 | AI-040 | 4-20 mA / 0-5V Input #5 – Value | Read Only |
41 | AI-041 | 4-20 mA / 0-5V Input #6 – Value | Read Only |
42 | AI-042 | 4-20 mA / 0-5V Input #7 – Value | Read Only |
43 | AI-043 | 4-20 mA / 0-5V Input #8 – Value | Read Only |
44 | AI-044 | Flow Meter #1 – Total Value | Read Only |
45 | AI-045 | Flow Meter #2 – Contact Value | Read Only |
46 | AI-046 | Flow Meter #3 – Contact Value | Read Only |
47 | AI-047 | Flow Meter #4 – Contact Value | Read Only |
48 | AI-048 | Flow Meter #5 – Contact Value | Read Only |
49 | AI-049 | Flow Meter #6 – Contact Value | Read Only |
50 | AI-050 | Flow Meter #7 – Contact Value | Read Only |
51 | AI-051 | Flow Meter #8 – Contact Value | Read Only |
52 | AI-052 | Flow Meter #9 – Contact Value | Read Only |
53 | AI-053 | Flow Meter #10 – Contact Value | Read Only |
54 | AI-054 | Flow Meter #1 – Flow Rate (per MIN) | Read Only |
55 | AI-055 | Flow Meter #2 – Flow Rate (per MIN) | Read Only |
56 | AI-056 | Flow Meter #3 – Flow Rate (per MIN) | Read Only |
57 | AI-057 | Flow Meter #4 – Flow Rate (per MIN) | Read Only |
58 | AI-058 | Flow Meter #5 – Flow Rate (per MIN) | Read Only |
59 | AI-059 | Flow Meter #6 – Flow Rate (per MIN) | Read Only |
60 | AI-060 | Flow Meter #7 – Flow Rate (per MIN) | Read Only |
61 | AI-061 | Flow Meter #8 – Flow Rate (per MIN) | Read Only |
62 | AI-062 | Flow Meter #9 – Flow Rate (per MIN) | Read Only |
63 | AI-063 | Flow Meter #10 – Flow Rate (per MIN) | Read Only |
64 | AI-064 | 4-20 mA / 0-5V Input #9 – Value | Read Only |
65 | AI-065 | 4-20 mA / 0-5V Input #10 – Value | Read Only |
66 | AI-066 | 4-20 mA / 0-5V Input #11 – Value | Read Only |
67 | AI-067 | 4-20 mA / 0-5V Input #12 – Value | Read Only |
68 | AI-068 | 4-20 mA / 0-5V Input #13 – Value | Read Only |
69 | AI-069 | 4-20 mA / 0-5V Input #14 – Value | Read Only |
70 | AI-070 | 4-20 mA / 0-5V Input #15 – Value | Read Only |
71 | AI-071 | 4-20 mA / 0-5V Input #16 – Value | Read Only |
Analog Value Object Instance Summary (Table 1-5)
Instance ID | Object Name | Purpose | Present Value – Access |
0 | AV-000 | System #1 – Conductivity Setpoint #1 | Read Only |
1 | AV-001 | System #2 – Conductivity Setpoint #1 | Read Only |
2 | AV-002 | System #3 – Conductivity Setpoint #1 | Read Only |
3 | AV-003 | System #4 – Conductivity Setpoint #1 | Read Only |
4 | AV-004 | System #1 – Conductivity Setpoint #2 | Read Only |
5 | AV-005 | System #2 – Conductivity Setpoint #2 | Read Only |
6 | AV-006 | System #3 – Conductivity Setpoint #2 | Read Only |
7 | AV-007 | System #4 – Conductivity Setpoint #2 | Read Only |
8 | AV-008 | System #1 – Conductivity High Alarm | Read Only |
9 | AV-009 | System #2 – Conductivity High Alarm | Read Only |
10 | AV-010 | System #3 – Conductivity High Alarm | Read Only |
11 | AV-011 | System #4 – Conductivity High Alarm | Read Only |
12 | AV-012 | System #1 – Conductivity Low Alarm | Read Only |
13 | AV-013 | System #2 – Conductivity Low Alarm | Read Only |
14 | AV-014 | System #3 – Conductivity Low Alarm | Read Only |
15 | AV-015 | System #4 – Conductivity Low Alarm | Read Only |
16 | AV-016 | System #1 – M. Conductivity Setpoint | Read Only |
17 | AV-017 | System #2 – M. Conductivity Setpoint | Read Only |
18 | AV-018 | System #3 – M. Conductivity Setpoint | Read Only |
19 | AV-019 | System #4 – M. Conductivity Setpoint | Read Only |
20 | AV-020 | System #1 – M. Conductivity High Alarm | Read Only |
21 | AV-021 | System #2 – M. Conductivity High Alarm | Read Only |
22 | AV-022 | System #3 – M. Conductivity High Alarm | Read Only |
23 | AV-023 | System #4 – M. Conductivity High Alarm | Read Only |
24 | AV-024 | System #1 – M. Conductivity Low Alarm | Read Only |
25 | AV-025 | System #2 – M. Conductivity Low Alarm | Read Only |
26 | AV-026 | System #3 – M. Conductivity Low Alarm | Read Only |
27 | AV-027 | System #4 – M. Conductivity Low Alarm | Read Only |
28 | AV-028 | System #1 – pH Setpoint #1 | Read Only |
29 | AV-029 | System #2 – pH Setpoint #1 | Read Only |
30 | AV-030 | System #3 – pH Setpoint #1 | Read Only |
31 | AV-031 | System #4 – pH Setpoint #1 | Read Only |
32 | AV-032 | System #1 – pH Setpoint #2 | Read Only |
33 | AV-033 | System #2 – pH Setpoint #2 | Read Only |
34 | AV-034 | System #3 – pH Setpoint #2 | Read Only |
35 | AV-035 | System #4 – pH Setpoint #2 | Read Only |
36 | AV-036 | System #1 – pH High Alarm | Read Only |
37 | AV-037 | System #2 – pH High Alarm | Read Only |
38 | AV-038 | System #3 – pH High Alarm | Read Only |
39 | AV-039 | System #4 – pH High Alarm | Read Only |
40 | AV-040 | System #1 – pH Low Alarm | Read Only |
41 | AV-041 | System #2 – pH Low Alarm | Read Only |
42 | AV-042 | System #3 – pH Low Alarm | Read Only |
43 | AV-043 | System #4 – pH Low Alarm | Read Only |
44 | AV-044 | System #1 – ORP Setpoint #1 | Read Only |
45 | AV-045 | System #2 – ORP Setpoint #1 | Read Only |
46 | AV-046 | System #3 – ORP Setpoint #1 | Read Only |
47 | AV-047 | System #4 – ORP Setpoint #1 | Read Only |
48 | AV-048 | System #1 – ORP Setpoint #2 | Read Only |
49 | AV-049 | System #2 – ORP Setpoint #2 | Read Only |
50 | AV-050 | System #3 – ORP Setpoint #2 | Read Only |
51 | AV-051 | System #4 – ORP Setpoint #2 | Read Only |
52 | AV-052 | System #1 – ORP High Alarm | Read Only |
53 | AV-053 | System #2 – ORP High Alarm | Read Only |
54 | AV-054 | System #3 – ORP High Alarm | Read Only |
55 | AV-055 | System #4 – ORP High Alarm | Read Only |
56 | AV-056 | System #1 – ORP Low Alarm | Read Only |
57 | AV-057 | System #2 – ORP Low Alarm | Read Only |
58 | AV-058 | System #3 – ORP Low Alarm | Read Only |
59 | AV-059 | System #4 – ORP Low Alarm | Read Only |
60 | AV-060 | System #1 – S. Temp Setpoint | Read Only |
61 | AV-061 | System #2 – S. Temp Setpoint | Read Only |
62 | AV-062 | System #3 – S. Temp Setpoint | Read Only |
63 | AV-063 | System #4 – S. Temp Setpoint | Read Only |
64 | AV-064 | System #1 – S. Temp High Alarm | Read Only |
65 | AV-065 | System #2 – S. Temp High Alarm | Read Only |
66 | AV-066 | System #3 – S. Temp High Alarm | Read Only |
67 | AV-067 | System #4 – S. Temp High Alarm | Read Only |
68 | AV-068 | System #1 – S. Temp Low Alarm | Read Only |
69 | AV-069 | System #2 – S. Temp Low Alarm | Read Only |
70 | AV-070 | System #3 – S. Temp Low Alarm | Read Only |
71 | AV-071 | System #4 – S. Temp Low Alarm | Read Only |
72 | AV-072 | System #1 – M. Temp Setpoint | Read Only |
73 | AV-073 | System #2 – M. Temp Setpoint | Read Only |
74 | AV-074 | System #3 – M. Temp Setpoint | Read Only |
75 | AV-075 | System #4 – M. Temp Setpoint | Read Only |
76 | AV-076 | System #1 – M. Temp High Alarm | Read Only |
77 | AV-077 | System #2 – M. Temp High Alarm | Read Only |
78 | AV-078 | System #3 – M. Temp High Alarm | Read Only |
79 | AV-079 | System #4 – M. Temp High Alarm | Read Only |
80 | AV-080 | System #1 – M. Temp Low Alarm | Read Only |
81 | AV-081 | System #2 – M. Temp Low Alarm | Read Only |
82 | AV-082 | System #3 – M. Temp Low Alarm | Read Only |
83 | AV-083 | System #4 – M. Temp Low Alarm | Read Only |
84 | AV-084 | System #1 – D. Temp Setpoint | Read Only |
85 | AV-085 | System #2 – D. Temp Setpoint | Read Only |
86 | AV-086 | System #3 – D. Temp Setpoint | Read Only |
87 | AV-087 | System #4 – D. Temp Setpoint | Read Only |
88 | AV-088 | System #1 – D. Temp High Alarm | Read Only |
89 | AV-089 | System #2 – D. Temp High Alarm | Read Only |
90 | AV-090 | System #3 – D. Temp High Alarm | Read Only |
91 | AV-091 | System #4 – D. Temp High Alarm | Read Only |
92 | AV-092 | System #1 – D. Temp Low Alarm | Read Only |
93 | AV-093 | System #2 – D. Temp Low Alarm | Read Only |
94 | AV-094 | System #3 – D. Temp Low Alarm | Read Only |
95 | AV-095 | System #4 – D. Temp Low Alarm | Read Only |
96 | AV-096 | System #1 – Flow Switch Conf. | Read Only |
97 | AV-097 | System #2 – Flow Switch Conf. | Read Only |
98 | AV-098 | System #3 – Flow Switch Conf. | Read Only |
99 | AV-099 | System #4 – Flow Switch Conf. | Read Only |
100 | AV-100 | mA 1 – Output Value | Read Only |
101 | AV-101 | mA 2 – Output Value | Read Only |
102 | AV-102 | mA 3 – Output Value | Read Only |
103 | AV-103 | mA 4 – Output Value | Read Only |
104 | AV-104 | mA 5 – Output Value | Read Only |
105 | AV-105 | mA 6 – Output Value | Read Only |
106 | AV-106 | System #1 – Timer #1 – Run Time | Read Only |
107 | AV-107 | System #1 – Timer #2 – Run Time | Read Only |
108 | AV-108 | System #1 – Timer #3 – Run Time | Read Only |
109 | AV-109 | System #1 – Timer #4 – Run Time | Read Only |
110 | AV-110 | System #1 – Timer #5 – Run Time | Read Only |
111 | AV-111 | System #2 – Timer #1 – Run Time | Read Only |
112 | AV-112 | System #2 – Timer #2 – Run Time | Read Only |
113 | AV-113 | System #2 – Timer #3 – Run Time | Read Only |
114 | AV-114 | System #2 – Timer #4 – Run Time | Read Only |
115 | AV-115 | System #2 – Timer #5 – Run Time | Read Only |
116 | AV-116 | System #3 – Timer #1 – Run Time | Read Only |
117 | AV-117 | System #3 – Timer #2 – Run Time | Read Only |
118 | AV-118 | System #3 – Timer #3 – Run Time | Read Only |
119 | AV-119 | System #3 – Timer #4 – Run Time | Read Only |
120 | AV-120 | System #3 – Timer #5 – Run Time | Read Only |
121 | AV-121 | System #4 – Timer #1 – Run Time | Read Only |
122 | AV-122 | System #4 – Timer #2 – Run Time | Read Only |
123 | AV-123 | System #4 – Timer #3 – Run Time | Read Only |
124 | AV-124 | System #4 – Timer #4 – Run Time | Read Only |
125 | AV-125 | System #4 – Timer #5 – Run Time | Read Only |
126 | AV-126 | Read-Only | Read Only |
Multi-State Value Object Instance Summary (Table 1-6)
Note #1 1=H-OFF 2=H-ON 3=OFF 4=ON
Instance ID | Object Name | Purpose | Present Value – Access |
0 | MSV-000 | Relay 1 – State | Read Only |
1 | MSV-001 | Relay 2 – State | Read Only |
2 | MSV-002 | Relay 3 – State | Read Only |
3 | MSV-003 | Relay 4 – State | Read Only |
4 | MSV-004 | Relay 5 – State | Read Only |
5 | MSV-005 | Relay 6 – State | Read Only |
6 | MSV-006 | Relay 7 – State | Read Only |
7 | MSV-007 | Relay 8 – State | Read Only |
8 | MSV-008 | Relay 9 – State | Read Only |
9 | MSV-009 | Relay 10 – State | Read Only |
10 | MSV-010 | Relay 11 – State | Read Only |
11 | MSV-011 | Relay 12 – State | Read Only |
12 | MSV-012 | Relay 13 – State | Read Only |
13 | MSV-013 | Relay 14 – State | Read Only |
14 | MSV-014 | Relay 15 – State | Read Only |
15 | MSV-015 | Relay 16 – State | Read Only |
16 | MSV-016 | Relay 17 – State | Read Only |
17 | MSV-017 | Relay 18 – State | Read Only |
18 | MSV-018 | Relay 19 – State | Read Only |
19 | MSV-019 | Relay 20 – State | Read Only |
Get the Advantage in Water Treatment Equipment
Advantage Controls can give you the Advantage in products, knowledge and support on all of your water treatment equipment needs.
- Cooling Tower Controllers
- Boiler Blow Down Controllers
- Blow Down Valve Packages
- Solenoid Valves
- Water Meters
- Chemical Metering Pumps
- Corrosion Coupon Racks
- Chemical Solution Tanks
- Solid Feed Systems
- Feed Timers
- Filter Equipment