ActronAir GW100K BMS Gateway Controller
Specifications
- Product Name: BMS Gateway Controller
- Model: GW100K
- Compatibility: Advance, Aires, Classic Series 2, and VCC product ranges
- Communication Protocols: Modbus RTU, BACnet/IP, Modbus TCP/IP, BACnet MSTP
- Maximum Connected Systems: Up to 10 Actron systems per unit
Product Usage Instructions
Introduction
Congratulations on your purchase of the ActronAir BMS Gateway Controller kit. This Gateway allows communication between Modbus RTU protocol and BACnet/IP, Modbus TCP/IP, or BACnet MSTP. It is compatible with various ActronAir product ranges.
Parts Included In the BMS Gateway Controller Kit (GW100K)
When unpacking the kit, ensure all parts are included as listed in the manual.
BMS Gateway (GW100)
The BMS Gateway facilitates control of air-cooled packaged units and split ducted systems by Building Management Systems. It allows up to 10 Actron systems to connect via ICUNO-MOD per unit.
Other Specifications
Refer to the manual for additional specifications such as connection diagram, maximum cable length, and ICUNO-MOD connection details.
Connection Diagram
Follow the schematic diagram provided in the manual for proper connection of the Gateway. Ensure adherence to the maximum cable length and ICUNO-MOD connection and addressing guidelines.
Installation and Configuration BMS Gateway
Install and configure the BMS Gateway as per the instructions provided in the manual to ensure proper functionality.
BMS Menu and Navigation
Explore the programming menu tree to navigate through the BMS Gateway settings effectively.
Screens Available
Familiarize yourself with the available screens on the Gateway for monitoring and control purposes.
Troubleshooting
Refer to the troubleshooting section for guidance on resolving common issues. Learn how to restore default values and access the register table if needed.
IMPORTANT NOTE:
Please read this manual carefully before installing the Gateway on to the Building Management System.
BMS GATEWAY CONTROLLER INSTALLATION AND COMMISSIONING GUIDE
Introduction
- CONGRATULATIONS on your purchase of an ActronAir BMS Gateway Controller kit. This Gateway translates Modbus RTU protocol communication to a choice of the following: BACnet/IP, Modbus TCP/IP or BACnet MSTP. It will be compatible with the Advance, Aires, Classic Series 2 and VCC product ranges.
- The Gateway will allow up to 10 Actron systems to connect it via ICUNO-MOD per unit (ICUNO-MOD are purchased separately). This will allow air-cooled packaged units and split ducted systems to be controlled by Building Management Systems (BMS).
- The procedures outlined in this manual are provided to correctly and safely install the ActronAir Gateway kit to control appropriate ActronAir Air Conditioner units.
- Failure to follow these procedures may result in personal injury, damage to the control kit or incorrect operation of the Air Conditioner unit. Such failure could render your warranty null and void.
Items to Consider
- Carefully unpack the ActronAir BMS Gateway Controller kit from its packaging and ensure that all parts are included.
- Check the contents of your kit against the content list upon receiving your shipment. Inspect the components and accessories for any sign of shipping damage. If there is any damage to the contents, contact ActronAir Customer Care immediately on: 1300 522 722.
- Take time to thoroughly read the installation and commissioning instructions before proceeding with the installation.
Safety Instructions
Safety instructions and warnings provided in this installation manual are non-exhaustive and given as a guide only. Prevailing WH&S regulations should be observed and will take precedence to the safety instructions contained in this manual. Safe work practices and environment should be of paramount importance in the performance of all service procedures.
- Read all instructions in this manual before operating the system. Failure to do so may result in damage to the unit and controllers that may void your warranty.
- Turn-Off power from mains supply by removing the fuse or switching the circuit breaker to the OFF position before performing the installation procedures.
- Follow sound LOCK-OUT/TAG-OUT (LOTO) procedures to ensure that power supply is not re-energized accidentally.
- Ensure that all safety work procedures and instructions are adhered to at all times in order to prevent personal injury or damage to the equipment.
- Only licensed technicians are allowed to perform the procedures described in this guide.
- The ActronAir BMS Gateway Controller kit is NOT FOR OUTDOOR USE. Install the kit away from excessive dust, heat and moisture.
- The air conditioning electrical panel and the ActronAir BMS Gateway Controller kit contain static sensitive electronic components. Careful handling and correct anti-static procedures should be followed to prevent damage of the equipment. Failure to protect the electronic components from static electricity may cause unrepairable damage, that is NOT COVERED for replacement under Warranty.
- The instructions herein refer to work involving a Computer CPU Chip and Electronic CPU Board. Please ensure all Instructions are followed accurately so as to prevent damage to these fragile and delicate components.
Codes, Regulations and Standards
The installer and/or contractor assumes responsibility to ensure that ActronAir BMS Gateway Controller kit installation and commissioning comply with the relevant Council, State / Federal Codes, regulations and building code standards. All electrical wiring should be in accordance with current electrical authority regulations and all wiring connections to be as per electrical diagram provided with the unit.
Waste Electrical and Electronic Equipment Disposal Guidelines
- Do not dispose of the waste electrical and electronic equipment with local council waste. These should be disposed through the appropriate council designated waste disposal facilities.
- The equipment may contain hazardous substances. Improper or incorrect disposal may have a negative effect on human health and on the environment.
Parts Included In the BMS Gateway Controller kit (GW100K)
Part Number | Items | Images | Quantity |
GW100 |
BMS Gateway |
![]() |
1 |
2020-184 | Main Controller Connector | ![]() |
1 |
20245-1 |
Switched-Mode Power Supply (SMPS) (240VAC/ 21.6-29VDC 15W) |
![]() |
1 |
Note:
ICUNO-MOD needs to be purchased separately. One ICUNO-MOD controller will be needed for every system connected to the BMS Gateway
BMS Gateway (GW100)
The BMS Gateway (GW100) is a microprocessor-based controller designed to connect up to 10 ActronAir ICUNO-MOD compatible systems. It translates Modbus RS485 output from these systems into BACnet/IP, BACnet MS/TP, or Modbus TCP/IP, enabling communication with a Building Management System (BMS). This functionality allows for easy integration and remote management of multiple ActronAir systems.
Structure/Terminal Connections
The front panel displays the pLAN address (01) when power is on.
Items | Label | Description |
A | J1 | Power connector [G(+), G0(-)] 24 Vac +10%/-15% 50/60 Hz or 28 to 36 Vdc ±10% |
B | J2 | U1 | Network default reset (U1-GND on power on) |
C | J2 | U2-U10 | Programable Universal inputs/outputs |
D | J9 | Vdc power supply to active probes +5V power supply to ratiometric probes |
E | ![]() |
MAC address label |
F | ![]() |
Ethernet Port – BACnet/IP and Modbus TCP/IP |
G | J4 FBus | RS485 Network to ActronAir ICUNO-MOD cards |
H | J3 Disp | RS485 Network to BMS – BACnet MS/TP |
I | J10 -J12 | Relay outputs (J12 BMS gateway Fault) |
J | ![]() |
Display pLAN address |
K | ![]() |
Micro USB (Manufacturer Use Only) |
- For U2-U5, U7-U10, these are the programable inputs
- Programable Analogue inputs:
- NTC (10K@25)
- NTC (50K@25K)
- PTC1000
- 0-10 Vdc signals *
- 4 to 20 mA signals **
- Ratiometric probes ***
- Programable Digital inputs:
- voltage-free contacts (not optically-isolated)
- voltage-free Alarm contacts (not optically-isolated)
- Powered Externally
- Max 2 powered by controller. Max 4 powered Externally
- Max 2
Reference | Terminal | Label | Extended desc. |
A |
J1-1 | G | Power supply at Voltage A: 24 Vac or 28…36 Vdc |
J1-2 | G0 | Power reference | |
J1-3 | Vbat | Not Used | |
B |
J2-1 | U1 | Network Reset |
J2-2 | U2 | Universal input 1 | |
J2-3 | U3 | Universal input 3 | |
J2-4 | GND | Common for universal inputs 1, 2, 3 | |
J2-5 | U4 | Universal input 4 | |
J2-6 | U5 | Universal input 5 | |
J2-7 | U6 | Analogue output, 0 to 10 V | |
J2-8 | GND | Common for universal inputs/outputs 4, 5, 6 | |
J2-9 | U7 | Universal input 7 | |
J2-10 | U8 | Universal input 8 | |
J2-11 | U9 | Universal input 9 | |
J2-12 | U10 | Universal input 10 | |
J2-13 | GND | Common for universal inputs 7, 8, 9, 10 | |
C |
J9-1 | +5 VREF | Power supply to 0-5 V ratiometric probes |
J9-2 | GND | Common for power supply | |
J9-3 | +Vdc | Power supply to active probes | |
D |
J10-1 | NO1 | Relay 1, normally open contact |
J10-2 | C1/2 | Common for relays 1, 2 | |
J10-3 | NO2 | Relay 2, normally open contact | |
E |
J11-1 | NO3 | Relay 3, normally open contact |
J11-2 | C3/4/5 | Common for relays 3,4,5 | |
J11-3 | NO4 | Relay 4, normally open contact | |
J11-4 | C3/4/5 | Common for relays 3,4,5 | |
J11-5 | NO5 | Relay 5, normally open contact | |
F |
J12-1 | NO6 | Gateway Alarm normally open contact |
J12-2 | NC6 | Gateway Alarm normally closed contact | |
J12-3 | C6 | Common for relay 6 | |
G |
J3-1 | +Vterm | Not Used |
J3-2 | Tx-/Rx- | Terminal port RS485 Tx-/Rx- | |
J3-3 | Tx+/Rx+ | Terminal port RS485 Tx+/Rx+ | |
J3-4 | GND | GND for RS485 port | |
H |
J4-1 | Tx-/Rx- | Fieldbus port RS485 Tx-/Rx- |
J4-2 | Tx+/Rx+ | Fieldbus port RS485 Tx+/Rx+ | |
J4-3 | GND | Fieldbus port RS485 GND | |
I | TxL/RxL | Ethernet Port |
Mounting and Dimensions
- Dimensions: DIN rail modules, 70 x 110 x 60 mm (in accordance with DIN 43880 CEI EN 50022).
- Mounting: fitted on DIN rail. P Gateway on t ss it down get will snap into place and lock the controller.
- Removing: lift the tabs using a screwdriver applied to their release slots. The tabs are kept in place by springs.
Controller Electrical and Physical
Power Supply(should only be connected between G and G0)
Power supply to the product between G and G0 (J1) | 24 Vac +10% / -15% 50/60 Hz, 24 to 36 Vdc ±10% |
Basic model maximum power consumption | 15 VA |
Insulation | Reinforced insulation between main power supply and controller guaranteed by the safety power transformer (IEC61558-2-6) |
Protection against short-circuits | Fuse (250VAC 2A) |
Maximum connector voltage (NO1…C6) | 250 VAC |
Minimum size of digital output wires | 1.5 mm2 |
Minimum size of all other connector wires | 0.5 mm2 |
Removable Connectors Kit
Connector kit code | 2020-184 |
Tightening torque | 0.2 N⋅m for 3.81 mm connectors |
Tightening torque | 0.4 N⋅m for 5.08 mm connectors |
Electrical Installation
- Important: before servicing the equipment, isolate the controller from mains power.
- Ensure the system is installed with a power disconnector conforming to regulations. Use cable lugs that are suitable for the terminals used. The maximum allowable length of the connections to the analogue/digital inputs and to the analogue outputs is 100 m other than temperature sensor; temperature sensor maximum length is only 50 m. After making the connection, gently pull on the cables to ensure they are sufficiently tight.
Note:
- Secure the cables connected to the controller with clamps placed at 3 cm from the connectors.
- Ensure the earth conductor is bonded to the conductor that is connected to the terminal from J1. Important:
- To avoid damage to the device, terminate wires to all connectors prior to plugging connectors to controller.
- Using a supply voltage other than specified can seriously damage the system and void the warranty.
- The controller should only be installed, serviced and inspected by qualified personnel and in compliance with national and local regulations.
- All the extra low voltage connections should have reinforced or double insulation from the power mains.
- Avoid touching the electronic components to avoid electrostatic discharges from the operator to the components, which may cause considerable damage.
- Do not press the screwdriver on the connectors with excessive force, to avoid damaging the controller.
- Using the device in any way other than specified by the manufacturer can compromise its protection.
- Only connectors supplied with the kit shall be used.
Power Supply
- Only use the SMPS-1 240VAC/21.6-29VDC 15W Switch Mode Power Supply that is supplied with the kit.
Important:
- Using a supply voltage other than specified can seriously damage the controller.
- Make sure that the earth conductor is connected to terminal GND. Proper grounding should be applies to all the devices connected to the GW100.
- The power supply to GW100 should be kept separate from the power supply to the other electrical devices.
Note: When the controller is powered, the seven segment LED lights up to show 01.
Operating Conditions
- Storage: -40 To 90 °C, 90% RH non-condensing
- Operation: -40 To 90 °C, 90% RH non-condensing
Network Communications
Ethernet Network Connections and Connectors
- It is recommend to use Cat5e UTP or above Ethernet Cable (IEC11801 and EIA/TIA 568 Compliant).
- The maximum length of an Ethernet connection is 100 m between consecutive devices.
RS-485 Network
- To improve the controller immunity against electromagnetic interference, the serial connection cable should be a shielded twisted pair cable, 2 core twisted pair shielded or 4 core two twisted pair shielded depending on the isolation of the serial connection.
- The following rule applies:
- The serial port (J3 Disp) is isolated (functionally) from the power supply. A third wire is required in the serial cable to act as a common reference for the controllers. The serial port (J4 FBus) is not optically isolated and the common reference is already present, no third wire is required.
- For the RS-485 network, use a shielded twisted pair cable. The maximum allowable total cumulative data cable length between all devices is 500 m.
- Note: Enable the 120Ω, 1/2W terminating resistors on the ICUNO-MOD board first and last devices in the network. See ICUNO-MOD Installation and Commissioning Guide (9590-3013) for details. Important: Any Earth connections made to any controllers shall be from a common main earth point.
Procedure for Earthing the Shield
- The shield of the cable of the J4 FBus terminal on the BMS Gateway (GW100) should be earthed. Earth only one end of the serial cable shield (shield connected to every second device).
Universal Inputs/Outputs
- Universal inputs/outputs are distinguished by the letter U.
- U1 is designated as a digital input for network parameter reset.
- U6 has been designated as a 0-10VDC output, drivable by BMS.
- U2-U5 and U7-U10 can be configured to accept the following to be monitored by the BMS for site specific purposes:
Analogue Inputs
- NTC (10K@25)
- NTC (50K@25K)
- PTC1000
- 0-10 Vdc signals *
- 4 to 20 mA signals **
- Ratiometric probes ***
Digital inputs (not optically-isolated)
- voltage-free contacts (not optically-isolated)
- voltage-free Alarm contacts (not optically-isolated)
- Powered Externally
- Max 2 powered by controller. Max 4 powered Externally
- Max 2
Important: Important:
- The universal inputs/outputs cannot be used as digital outputs.
Digital Outputs
Digital Outputs are distinguished by the letter NO and NC.
- NO6 (J12) is designated as the BMS Gateway general alarm.
- NO1-NO5 (J10, J11) are available to be controlled via BMS input for site specific purposes.
Note:
- Group 1 (R1, R2); Group 2 (R3, R4, R5): NO EN 60730-1 Maximum Switchable Load: 250VAC/2A resistive Group 3 (J6): NO EN 60730-1 Maximum Switchable Load: 250VAC/1A resistive
- Between J10 and J11 terminals there is basic insulation.
- J12 has reinforced insulation from the two other terminals (J10 and 11). Consequently a different power supply can be used.
Other Specifications
Environmental pollution | Level 3 |
Front panel ingress protection
(with USB port closed) |
IP40 front panel, IP10 remaining parts |
Class of protection against electric shock | To be integrated into Class I and/or II appliances |
Material | Technopolymer |
Flammability | V2 (UL94) and
850 °C (in accordance with IEC 60695-2-11) |
PTI of the PCB insulating materials | PTI 250 |
Insulating material | PTI 175 |
Colour | White RAL 9016 |
Ball pressure test temperature | 125 °C |
Period of stress across the insulating parts | Long |
Type of action digital output | 1C |
Type of disconnection or microswitching | Microswitching |
Heat and fire resistance category | Category D (UL94 – V2) |
Overvoltage category | Category III |
Software class and structure | Class A |
Do not touch or tamper with the device when powered. |
Connection Diagram
NOTE
- Ports available for this are Ethernet or RS485. However, only one port can be used and set as the network connection at a time.
Maximum Cable Length
MAXIMUM CABLE LENGTH BETWEEN DEVICES
Connection | Cable Type | Maximum Length |
Gateway Power Supply toBMS Gateway | Power Cable | 12m for 1.5mm² / 8m for 1.0mm² |
BMS Gateway to Customer BMS Master | Data Cable | 500m |
BMS Gateway to first Intermediate Device | Signal Cable | 500m |
Customer BMS Master to Last Device | Data Cable | 1000m total cummulative length |
Note: Effective distance may vary depending on noise in the network surrounding. |
ICUNO-MOD Connection and Addressing
- The BMS Gateway Controller System connects to individual ActronAir units through an ActronAir ICUNO-MOD module. During installation and commissioning, each ICUNO-MOD must be assigned an address that corresponds to the connected unit’s number, and the baud rate must be set. The BMS Gateway can support up to 10 ICUNO-MOD modules.
- To assign an address, adjust the DIP switches on each ICUNO-MOD to match the desired unit number. The GW100 Gateway is configured to automatically detect each module’s assigned address.
- For detailed installation and configuration instructions, please refer to the ICUNO-MOD Installation and Commissioning Guide (Document 9590-3013).
Installation and Configuration BMS Gateway
- Step 1. Install BMS Gateway and the SMPS (included in the kit) in the desired locations.
- Step 2. Adjust the SMPS power output to 28VDC.
- Step 3. Connect 240VAC to SMPS.
- Step 4. Connect 28VDC from SMPS to the BMS gateway.
- Step 5. Install ICUNO-MOD cards (refer to ICUNO manual).
- Step 6. Set DIP switches according to unit number (listed in BMS gateway manual).
- Step 7. Run fieldbus cable between ICUNO-MOD cards and J4 on the BMS gateway.
- Step 8. Power BMS Gateway.
Menu Navigation
- Press the Up(
) or Down(
) arrow to go the previous or next line. When cursor is in a variable character, this will toggle the value or increment/decrease the set value.
- Press Enter (
) to into the menu (see Menu Tree Section for guide). When cursor is in a variable character, this will select he value currently displayed.
- Press Esc (
) to go back to main screen.
Complete programming menu tree
Below is the complete menu tree of the configuration menu.
Menu | Screen
Reference |
Parameter | Settings | Menu Description | Menu
Type |
|
Input/ Output |
Test – Device 01 – 10 |
Aa01 |
Unit On/Off | 0 – 1 | Read and Write the ON/OFF command – ICUNO-MOD
holding register 1 |
U |
Master Set Point | 16.0 – 30.0 | Read and Write the Master Set Point – ICUNO-MOD holding
register 102 |
||||
Indoor Coil
Temperature |
Returns Indoor Coil Temperature – ICUNO-MOD holding
register 1301 |
|||||
OD Firmware | Returns OD Firmware – ICUNO-MOD holding register 1001 | |||||
Subsequent screens are replicated for Device 02 – 10: Aa02 – A10 | ||||||
Device 11 – Onboard | Aa11 | Input/Output 01-05 | Status of U1-U5 | U | ||
Device 11 – Onboard | Aa12 | Input/Output 06-10 | Status of U6-U10 | U | ||
Device 11 – Onboard | Aa13 | Relay 01-06 | Status of relay 01-06 | U | ||
Output Override | Aa14 | Relay 01-06 | Auto – On – Off | Override output relay 01-06 | S | |
Output Overide | Aa15 | Reset Overides | No – Yes | Resets the status of the relay overides | S | |
Info | Info | Ab01 – 07 | Info | System Information (SW version, OS version, Device
information) |
S | |
Input Config |
Universal Input U02 | Ad01 | Refer to 03.07.04 | Universal Input U02 configuration | S | |
Universal Input U03 | Ad02 | Refer to 03.07.04 | Universal Input U03 configuration | S | ||
Universal Input U04 | Ad03 | Refer to 03.07.04 | Universal Input U04 configuration | S | ||
Universal Input U05 | Ad04 | Refer to 03.07.04 | Universal Input U05 configuration | S | ||
Universal Input U07 | Ad05 | Refer to 03.07.04 | Universal Input U07 configuration | S | ||
Universal Input U08 | Ad06 | Refer to 03.07.04 | Universal Input U08 configuration | S | ||
Universal Input U09 | Ad07 | Refer to 03.07.04 | Universal Input U09 configuration | S | ||
Universal Input U10 | Ad08 | Refer to 03.07.04 | Universal Input U10 configuration | S | ||
Unit Config |
Unit Configuration |
Ae00 | Number of Devices | 1-10 | Sets the number of connected devices | S |
Disable Device | Y – N | Enable/Disable the device in from communication | ||||
Ae01A |
Device 01 | Y – N | Enable additional variables |
S |
||
Ana_01 reg#: | 1-9999 | R – R/W | Set ICUNO-MOD holding register and read type –
Additional Analogue Variables |
||||
Ana_02 reg#: | 1-9999 | R – R/W | Set ICUNO-MOD holding register and read type –
Additional Analogue Variables |
||||
Ana_03 reg#: | 1-9999 | R – R/W | Set ICUNO-MOD holding register and read type –
Additional Analogue Variables |
||||
Ana_04 reg#: | 1-9999 | R – R/W | Set ICUNO-MOD holding register and read type –
Additional Analogue Variables |
||||
Ana_05 reg#: | 1-9999 | R – R/W | Set ICUNO-MOD holding register and read type –
Additional Analogue Variables |
||||
Ae01D |
Device 01 | Y – N | Enable additional variables |
S |
||
Dig_01 reg#: | 1-9999 | R – R/W | Set ICUNO-MOD holding register and read type –
Additional Digital Variables |
||||
Dig_02 reg#: | 1-9999 | R – R/W | Set ICUNO-MOD holding register and read type –
Additional Digital Variables |
||||
Dig_03 reg#: | 1-9999 | R – R/W | Set ICUNO-MOD holding register and read type –
Additional Digital Variables |
||||
Dig_04 reg#: | 1-9999 | R – R/W | Set ICUNO-MOD holding register and read type –
Additional Digital Variables |
||||
Dig_05 reg#: | 1-9999 | R – R/W | Set ICUNO-MOD holding register and read type –
Additional Digital Variables |
||||
Unit Configuration |
Ae01I |
Device 01 | Y – N | Enable additional variables |
S |
|
Int_01 reg#: | 1-9999 | R – R/W | Set ICUNO-MOD holding register and read type –
Additional Integer Variables |
||||
Int_02 reg#: | 1-9999 | R – R/W | Set ICUNO-MOD holding register and read type –
Additional Integer Variables |
||||
Int_03 reg#: | 1-9999 | R – R/W | Set ICUNO-MOD holding register and read type –
Additional Integer Variables |
||||
Int_04 reg#: | 1-9999 | R – R/W | Set ICUNO-MOD holding register and read type –
Additional Integer Variables |
||||
Int_05 reg#: | 1-9999 | R – R/W | Set ICUNO-MOD holding register and read type –
Additional Integer Variables |
||||
Subsequent screens are replicated for Device 02-10: Ae02A – Ae10A, Ae02D – Ae10D, Ae02I – Ae10I |
Menu | Screen
Reference |
Parameter | Settings | Menu Description | Menu
Type |
|
Unit Config |
Parameter Import/ Export |
Ae11 |
Import/Export | Import – Export | Set choice to Import or Export configuration file |
S |
Memory Type | Internal –
External |
Select location to Import from or Export to configuration file | ||||
File Name | 00 – 99 | Select the configuration file name for Import/Export | ||||
Confirm | Yes – No | Confirm Import/Export request | ||||
Alarm Export |
Ae12 |
Memory Type | Internal – USB | Set the location for alarm log to be exported |
S |
|
File Name | 00 – 99 | Select the Alarm log file name for export | ||||
Confirm | Yes – No | Confirm Export request | ||||
Alarm
Logs |
Data Logger | View the Alarm history | U | |||
Settings |
Date/Time |
Ba01 |
Format | DD-MM-YYYY | Set the Date format |
U |
Date | DD-MM-YYYY | Set the Date | ||||
Hour | HH-MM-SS | Set the Time | ||||
Day | Monday-Sunday | Set the Day | ||||
Ba02 | Time Zone | UTC | Sets the Time Zone | U | ||
UoM | Bb01 | User interface UoM | Sets the User interface Unit of Measure | U | ||
Language |
Language | English | Sets the user interface language |
U |
||
Enter to Change, Esc to
confirm |
Enter – Esc | Changes and confirms the set language | ||||
Network |
Bc01 |
Baud Rate | 1200 – 375000 | Sets the Baud rate speed for communication to ActronAir
ICUNO-MOD cards |
S |
|
Stopbits | 1 – 2 | Sets the Stop bits | ||||
Parity | Even – Odd –
None |
Sets the Parity | ||||
Bc02 |
Port | Ethernet – RS485 | Selects the BMS output port |
S |
||
Device Instance | 1 – 99999 | Sets the Device instance | ||||
Offline Delay | 3000ms | Sets the BMS offline delay | ||||
Detect Timeout | 1500ms | Sets the BMS detect Timeout | S | |||
Bc03 |
Station Address | 1 | Sets the unique station address of the gateway on the RS-
485 bus |
S |
||
Max. Master | 127 | Specifies the address of the network Master with the
highest station address |
||||
Max. Info/Frame | 10 | Sets the maximum number of packages that can be
exchanged |
||||
Bc04 |
Baud rate | 19200 | Sets the BACnet data transfer speed |
S |
||
Stopbits | 1 | Sets the Stop bits | ||||
Parity | None | Sets the Parity | ||||
Bc05 | Net Configuration | Enter | Enter the network configuration screen | S | ||
Ca01/2 |
Enable | Static – Off –
DHCP |
Set the unit’s IP address for the Ethernet connection. Set
DHCP, subnet mask, gateway, DNS. |
S |
||
IP | 192.168.0.1 | Set the IP address | ||||
Mask | 255.255.255.0 | Set the Subnet Mask | ||||
GW | 0.0.0.0 | Set the Gateway | ||||
DNS | 0.0.0. | Set the DNS | ||||
Ca02/2 | Update Config? | Yes – No | Set the “Update?” parameter to “YES” to update the network
settings |
S | ||
Password Change |
User: | 0 |
Change the password (User, Service, Installer) |
U |
||
Service | 7378 | |||||
Manufacturer | 6268 | |||||
Initialisation |
Delete alarm logs | Yes – No | Deletes the internal gateway alarm logs |
M |
||
Clear AutoReset
counters |
Yes – No | Clears the AutoReset counters | ||||
Enable Buzzer | Yes – No | Sets the function of the internal alarm buzzer | ||||
Default Installation | Wipe Memory | Yes – No | Unit factory reset. Important: resetting the model will cancel
all of the control settings and load the default values |
M | ||
Logout | Logout | Enter to logout | Enter | Information on the type of login performed. Provides option
to logout of that user access |
U |
Screens Available
- When the BMS Gateway is installed in the system, the Customer BMS Master could access and navigate the setting of the network.
Home Screen: Device Status
- This shows the connected devices.
- X = Device has been set up but no communication
= Device has been set up and communication is established.
- – = Device is set up and has been disabled in the unit configuration menu
Alarm Screen and Data Logger:
- Below screen shows when the upper left corner button (
) is pressed.
- Press the Enter button(
) until the screen below appears.
- Use the Up(
) or Down(
) arrows to navigate through the devices, as shown below:
- Use the Up(
) or Down(
) arrows to navigate through the devices, as shown below:
Main Menu
- To access the main menu, press the (
) button on the left side of the display. Entering the main menu will prompt a log in screen where an access password will be required to be entered. See 08.01.04.
- This screen will show when the middle button, Menu (
) on the left is pressed.
- Press the Up(
) or Down(
) arrow until the sub menu required appears. Press the Enter button
to enter that menu.
Login Screen
- Press the Up(
) or Down(
) arrow until the number required appears. Press the Enter button(
)to accept the value. Repeat until all numbers are set.
Password
- User: 0000
- Service: 7378
- If you are logged in under USER and try to access a SERVICE restricted menu, it will be disallowed. You will need to log out as USER and log back in using the SERVICE password.
LogOut Screen
- To go to the Log Out screen, go to the Main Menu, press the Up(
) or Down(
) arrow until Logout is highlighted. Press the Enter button(
)to select.
- The screen will show as below. Press the Enter button
to log out.
Input / Output Menu
- The Input/Output menu provides viewing and testing of pre-set variables for the purpose of verifying communication between the BMS gateway and the connected ActronAir system. Press the Up(
) or Down(
) arrow to select desired setting to change. Press the Enter button(
) to select the setting. Press the Up(
) or Down(
) arrow to chage the parameter.
- There is a different input/output screen for each Device enabled.
NOTE
- Unit On/Off – ICUNO-MOD register 1 – Read/Writable
- Master Set Point – ICUNO-MOD register 102 – Read/Writable Indoor Coil Temperature – ICUNO-MOD register 1301 – Read only OD Firmware – ICUNO-MOD register 1001 – Read only
Information Menu
- Provides information on the gateway hardware, firmware and network polling.
- Software code and version will need to be provided when calling Actron Technical Service.
Unit Configuration Menu
- This menu allows for the configuration of the number of devices that the BMS gateway will be connected to.
- If units are not to be configured and commissioned all at the same time, and was allocated a Device number in the BMS Gateway, these devices can be disabled to prevent alarm generation from the Gateway.
- As an example, if three units (1, 2, and 3) are to be connected, but only units 1 and 3 will be commissioned at startup, set device 2 to ‘N.’ This will prevent the BMS Gateway from triggering an alarm when it cannot detect device 2.
Additional Variables
- This allows the configuration of additional ICUNO-MOD variables that are not currently mapped in the gateway.
- Each device connected to the BMS Gateway have the ability to configure an additional 5 Analog, 5 Integer, and 5 Digital variables, allowing for a maximum of 15 additional variables per device. The register entered will correspond to the holding register provided by the ICUNO-MOD. The read/write status can be set for each variable.
NOTE
- Ask for Actron Technical Support for further assistance on this.
Unit Configuration File This allows the export or import of configuration file.
Field Network Configuration
- Fieldbus 1 is the communication from the BMS gateway to the ICUNO-MOD devices. Default parameters are:
- Protocol: ActronAir Modbus (not changeable)
- Baudrate: 19200
- Stopbits: 1
- Parity: Even
NOTE
- These values must correspond with the configuration of all connected ICUNO-MOD cards.
BMS Network Connection
- Ports available for this are Ethernet or RS485. However, only one port can be used and set as the network connection at a time.
Ethernet
Ethernet is the default setting. This is used for used for BACnet/IP and Modbus TCP/IP.
NOTE
- If Ethernet is selected, J3 can be used to plug a CP05 or a CP10 terminal display.
- Changing the Port selection requires the BMS gateway to be rebooted to take effect.
RS485
RS485 is selected for BACnet MS/TP (terminal J3). BACnet MS/TP configuration settings
BACnet MS/TP port settings
NOTE
- If RS485 is selected, J3 can only be used for BACnet MS/TP and a display terminal cannot be connected. Changing the Port selection requires the BMS gateway to be rebooted to take effect.
Network Configuration IP Settings This allows access and configuration of the Gateways IP settings.
To save the network configuration, ‘Update Config’ must be set to Yes.
NOTE
- The Net configuration menu is only visible when the BACnet port is set to Ethernet in menu Bc02
Troubleshooting
Restoring the Default values of the BMS Gateway
This provides the ability to physically reset the gateways network address to default:
- IP: 192.168.0.1
- Subnet: 255.255.255.0
- Step 1. Turn-Off power from mains supply by removing the fuse or switching the circuit breaker to the OFF position before performing the installation procedures. Follow sound LOCK-OUT/TAG-OUT (LOTO) procedures to ensure that power supply is not re-energized accidentally.
- Step 2. Bridge U1-GND. Connect ends of the jumper wire to U1 and GND terminals to short.
- Step 3. Power system ON and wait to load.
- Step 4. Remove the jumper wire (connected to the U1 and GND).
- Step 5. Connect to the Gateway using default IP address settings.
- Step 6. Configure desired IP address settings.
Link to the Register Table
There are two options to access the Registry Table.
Website
https://actronair.com.au/bmsgatewayregister/
QR
Once link is accessed, chose either View or Download the register table.
- ©Copyright 2025 Actron Engineering Pty Limited ABN 34 002767240. ®Registered Trade Marks of Actron Engineering Pty Limited.
- ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice.
FAQS
Q: What should I do if I encounter communication issues with the Gateway?
A: Check the cable connections, ensure proper addressing, and verify compatibility with the connected systems.
Q: Can I connect more than 10 Actron systems to a single Gateway unit?
A: No, the Gateway supports a maximum of 10 Actron systems per unit.
Q: How do I reset the Gateway to its default values?
A: Refer to section 09.01 in the manual for instructions on restoring default values.