ActronAir GW100K BMS Gateway Controller

ActronAir-GW100K-BMS-Gateway-Controller-PRODUCT

Specifications

  • Product Name: BMS Gateway Controller
  • Model: GW100K
  • Compatibility: Advance, Aires, Classic Series 2, and VCC product ranges
  • Communication Protocols: Modbus RTU, BACnet/IP, Modbus TCP/IP, BACnet MSTP
  • Maximum Connected Systems: Up to 10 Actron systems per unit

Product Usage Instructions

Introduction
Congratulations on your purchase of the ActronAir BMS Gateway Controller kit. This Gateway allows communication between Modbus RTU protocol and BACnet/IP, Modbus TCP/IP, or BACnet MSTP. It is compatible with various ActronAir product ranges.

Parts Included In the BMS Gateway Controller Kit (GW100K)
When unpacking the kit, ensure all parts are included as listed in the manual.

BMS Gateway (GW100)
The BMS Gateway facilitates control of air-cooled packaged units and split ducted systems by Building Management Systems. It allows up to 10 Actron systems to connect via ICUNO-MOD per unit.

Other Specifications
Refer to the manual for additional specifications such as connection diagram, maximum cable length, and ICUNO-MOD connection details.

Connection Diagram
Follow the schematic diagram provided in the manual for proper connection of the Gateway. Ensure adherence to the maximum cable length and ICUNO-MOD connection and addressing guidelines.

Installation and Configuration BMS Gateway
Install and configure the BMS Gateway as per the instructions provided in the manual to ensure proper functionality.

BMS Menu and Navigation
Explore the programming menu tree to navigate through the BMS Gateway settings effectively.

Screens Available
Familiarize yourself with the available screens on the Gateway for monitoring and control purposes.

Troubleshooting
Refer to the troubleshooting section for guidance on resolving common issues. Learn how to restore default values and access the register table if needed.

IMPORTANT NOTE:
Please read this manual carefully before installing the Gateway on to the Building Management System.

BMS GATEWAY CONTROLLER INSTALLATION AND COMMISSIONING GUIDE

Introduction

  • CONGRATULATIONS on your purchase of an ActronAir BMS Gateway Controller kit. This Gateway translates Modbus RTU protocol communication to a choice of the following: BACnet/IP, Modbus TCP/IP or BACnet MSTP. It will be compatible with the  Advance, Aires, Classic Series 2 and VCC product ranges.
  • The Gateway will allow up to 10 Actron systems to connect it via ICUNO-MOD per unit (ICUNO-MOD are purchased separately). This will allow air-cooled packaged units and split ducted systems to be controlled by Building Management Systems (BMS).
  • The procedures outlined in this manual are provided to correctly and safely install the ActronAir Gateway kit to control appropriate ActronAir Air Conditioner units.
  • Failure to follow these procedures may result in personal injury, damage to the control kit or incorrect operation of the Air Conditioner unit. Such failure could render your warranty null and void.

Items to Consider

  • Carefully unpack the ActronAir BMS Gateway Controller kit from its packaging and ensure that all parts are included.
  • Check the contents of your kit against the content list upon receiving your shipment. Inspect the components and accessories for any sign of shipping damage. If there is any damage to the contents, contact ActronAir Customer Care immediately on: 1300 522  722.
  • Take time to thoroughly read the installation and commissioning instructions before proceeding with the installation.

Safety Instructions 
Safety instructions and warnings provided in this installation manual are non-exhaustive and given as a guide only. Prevailing WH&S regulations should be observed and will take precedence to the safety instructions contained in this manual. Safe work practices and environment should be of paramount importance in the performance of all service procedures.

  • Read all instructions in this manual before operating the system. Failure to do so may result in damage to the unit and controllers that may void your warranty.
  • Turn-Off power from mains supply by removing the fuse or switching the circuit breaker to the OFF position before performing the installation procedures.
  • Follow sound LOCK-OUT/TAG-OUT (LOTO) procedures to ensure that power supply is not re-energized accidentally.
  • Ensure that all safety work procedures and instructions are adhered to at all times in order to prevent personal injury or damage to the equipment.
  • Only licensed technicians are allowed to perform the procedures described in this guide.
  • The ActronAir BMS Gateway Controller kit is NOT FOR OUTDOOR USE. Install the kit away from excessive dust, heat and moisture.
  • The air conditioning electrical panel and the ActronAir BMS Gateway Controller kit contain static sensitive electronic components. Careful handling and correct anti-static procedures should be followed to prevent damage of the equipment. Failure to protect the electronic components from static electricity may cause unrepairable damage, that is NOT COVERED for replacement under Warranty.
  • The instructions herein refer to work involving a Computer CPU Chip and Electronic CPU Board. Please ensure all Instructions are followed accurately so as to prevent damage to these fragile and delicate components.

Codes, Regulations and Standards 
The installer and/or contractor assumes responsibility to ensure that ActronAir BMS Gateway Controller kit installation and commissioning comply with the relevant Council, State / Federal Codes, regulations and building code standards. All electrical wiring should be in accordance with current electrical authority regulations and all wiring connections to be as per electrical diagram provided with the unit.

Waste Electrical and Electronic Equipment Disposal Guidelines

  • Do not dispose of the waste electrical and electronic equipment with local council waste. These should be disposed through the appropriate council designated waste disposal facilities.
  • The equipment may contain hazardous substances. Improper or incorrect disposal may have a negative effect on human health and on the environment.

Parts Included In the BMS Gateway Controller kit (GW100K)

Part Number Items Images Quantity
 

 

 

GW100

 

 

 

BMS Gateway

ActronAir-GW100K-BMS-Gateway-Controller-fIG- (1)
 

 

 

1

2020-184 Main Controller Connector ActronAir-GW100K-BMS-Gateway-Controller-fIG- (2) 1
 

20245-1

 

Switched-Mode Power Supply (SMPS) (240VAC/ 21.6-29VDC 15W)

ActronAir-GW100K-BMS-Gateway-Controller-fIG- (3)  

1

Note:
ICUNO-MOD needs to be purchased separately. One ICUNO-MOD controller will be needed for every system connected to the BMS Gateway

BMS Gateway (GW100)
The BMS Gateway (GW100) is a microprocessor-based controller designed to connect up to 10 ActronAir ICUNO-MOD compatible systems. It translates Modbus RS485 output from these systems into BACnet/IP, BACnet MS/TP, or Modbus TCP/IP, enabling communication with a Building Management System (BMS). This functionality allows for easy integration and remote management of multiple ActronAir systems.

Structure/Terminal Connections
The front panel displays the pLAN address (01) when power is on.

ActronAir-GW100K-BMS-Gateway-Controller-fIG- (4)

Items Label Description
A J1 Power connector [G(+), G0(-)] 24 Vac +10%/-15% 50/60 Hz or  28 to 36 Vdc ±10%
B J2 | U1 Network default reset (U1-GND on power on)
C J2 | U2-U10 Programable Universal inputs/outputs
D J9 Vdc power supply to active probes +5V power supply to ratiometric probes
E ActronAir-GW100K-BMS-Gateway-Controller-fIG- (5) MAC address label
F ActronAir-GW100K-BMS-Gateway-Controller-fIG- (6) Ethernet Port – BACnet/IP and Modbus TCP/IP
G J4 FBus RS485 Network to ActronAir ICUNO-MOD cards
H J3 Disp RS485 Network to BMS – BACnet MS/TP
I J10 -J12 Relay outputs (J12 BMS gateway Fault)
J ActronAir-GW100K-BMS-Gateway-Controller-fIG- (7) Display pLAN address
K ActronAir-GW100K-BMS-Gateway-Controller-fIG- (8) Micro USB (Manufacturer Use Only)

ActronAir-GW100K-BMS-Gateway-Controller-fIG- (9)

  • For U2-U5, U7-U10, these are the programable inputs
  • Programable Analogue inputs:
    • NTC (10K@25)
    • NTC (50K@25K)
    • PTC1000
    • 0-10 Vdc signals *
    • 4 to 20 mA signals **
    • Ratiometric probes ***
  • Programable Digital inputs:
    • voltage-free contacts (not optically-isolated)
    • voltage-free Alarm contacts (not optically-isolated)
  • Powered Externally
  • Max 2 powered by controller. Max 4 powered Externally
  • Max 2
Reference Terminal Label Extended desc.
 

A

J1-1 G Power supply at Voltage A: 24 Vac or 28…36 Vdc
J1-2 G0 Power reference
J1-3 Vbat Not Used
 

 

 

 

B

J2-1 U1 Network Reset
J2-2 U2 Universal input 1
J2-3 U3 Universal input 3
J2-4 GND Common for universal inputs 1, 2, 3
J2-5 U4 Universal input 4
J2-6 U5 Universal input 5
J2-7 U6 Analogue output, 0 to 10 V
J2-8 GND Common for universal inputs/outputs 4, 5, 6
J2-9 U7 Universal input 7
J2-10 U8 Universal input 8
J2-11 U9 Universal input 9
J2-12 U10 Universal input 10
J2-13 GND Common for universal inputs 7, 8, 9, 10
 

C

J9-1 +5 VREF Power supply to 0-5 V ratiometric probes
J9-2 GND Common for power supply
J9-3 +Vdc Power supply to active probes
 

D

J10-1 NO1 Relay 1, normally open contact
J10-2 C1/2 Common for relays 1, 2
J10-3 NO2 Relay 2, normally open contact
 

E

J11-1 NO3 Relay 3, normally open contact
J11-2 C3/4/5 Common for relays 3,4,5
J11-3 NO4 Relay 4, normally open contact
J11-4 C3/4/5 Common for relays 3,4,5
J11-5 NO5 Relay 5, normally open contact
 

F

J12-1 NO6 Gateway Alarm normally open contact
J12-2 NC6 Gateway Alarm normally closed contact
J12-3 C6 Common for relay 6
 

G

J3-1 +Vterm Not Used
J3-2 Tx-/Rx- Terminal port RS485 Tx-/Rx-
J3-3 Tx+/Rx+ Terminal port RS485 Tx+/Rx+
J3-4 GND GND for RS485 port
 

H

J4-1 Tx-/Rx- Fieldbus port RS485 Tx-/Rx-
J4-2 Tx+/Rx+ Fieldbus port RS485 Tx+/Rx+
J4-3 GND Fieldbus port RS485 GND
I   TxL/RxL Ethernet Port

Mounting and Dimensions

  • Dimensions: DIN rail modules, 70 x 110 x 60 mm (in accordance with DIN 43880 CEI EN 50022).
  • Mounting: fitted on DIN rail. P Gateway on t ss it down get will snap into place and lock the controller.
  • Removing: lift the tabs using a screwdriver applied to their release slots. The tabs are kept in place by springs.

ActronAir-GW100K-BMS-Gateway-Controller-fIG- (10)

Controller Electrical and Physical

Power Supply(should only be connected between G and G0)

Power supply to the product between G and G0 (J1) 24 Vac +10% / -15% 50/60 Hz, 24 to 36 Vdc ±10%
Basic model maximum power consumption 15 VA
Insulation Reinforced insulation between main power supply and controller guaranteed by the safety power transformer (IEC61558-2-6)
Protection against short-circuits Fuse (250VAC 2A)
Maximum connector voltage (NO1…C6) 250 VAC
Minimum size of digital output wires 1.5 mm2
Minimum size of all other connector wires 0.5 mm2

Removable Connectors Kit

Connector kit code 2020-184
Tightening torque 0.2 N⋅m for 3.81 mm connectors
Tightening torque 0.4 N⋅m for 5.08 mm connectors

Electrical Installation

  • Important: before servicing the equipment, isolate the controller from mains power.
  • Ensure the system is installed with a power disconnector conforming to regulations. Use cable lugs that are suitable for the terminals used. The maximum allowable length of the connections to the analogue/digital inputs and to the analogue outputs is 100 m  other than temperature sensor; temperature sensor maximum length is only 50 m. After making the connection, gently pull on the cables to ensure they are sufficiently tight.

Note:

  • Secure the cables connected to the controller with clamps placed at 3 cm from the connectors.
  • Ensure the earth conductor is bonded to the conductor that is connected to the terminal from J1. Important:
  • To avoid damage to the device, terminate wires to all connectors prior to plugging connectors to controller.
  • Using a supply voltage other than specified can seriously damage the system and void the warranty.
  • The controller should only be installed, serviced and inspected by qualified personnel and in compliance with national and local regulations.
  • All the extra low voltage connections should have reinforced or double insulation from the power mains.
  • Avoid touching the electronic components to avoid electrostatic discharges from the operator to the components, which may cause considerable damage.
  • Do not press the screwdriver on the connectors with excessive force, to avoid damaging the controller.
  • Using the device in any way other than specified by the manufacturer can compromise its protection.
  • Only connectors supplied with the kit shall be used.

Power Supply

  • Only use the SMPS-1 240VAC/21.6-29VDC 15W Switch Mode Power Supply that is supplied with the kit.

Important:

  • Using a supply voltage other than specified can seriously damage the controller.
  • Make sure that the earth conductor is connected to terminal GND. Proper grounding should be applies to all the devices connected to the GW100.
  • The power supply to GW100 should be kept separate from the power supply to the other electrical devices.

Note: When the controller is powered, the seven segment LED lights up to show 01.

Operating Conditions

  • Storage: -40 To 90 °C, 90% RH non-condensing
  • Operation: -40 To 90 °C, 90% RH non-condensing

Network Communications

Ethernet Network Connections and Connectors

  • It is recommend to use Cat5e UTP or above Ethernet Cable (IEC11801 and EIA/TIA 568 Compliant).
  • The maximum length of an Ethernet connection is 100 m between consecutive devices.

RS-485 Network

  • To improve the controller immunity against electromagnetic interference, the serial connection cable should be a shielded twisted pair cable, 2 core twisted pair shielded or 4 core two twisted pair shielded depending on the isolation of the serial connection.
  • The following rule applies:
  • The serial port (J3 Disp) is isolated (functionally) from the power supply. A third wire is required in the serial cable to act as a common reference for the controllers. The serial port (J4 FBus) is not optically isolated and the common reference is already present,  no third wire is required.
  • For the RS-485 network, use a shielded twisted pair cable. The maximum allowable total cumulative data cable length between all devices is 500 m.
  • Note: Enable the 120Ω, 1/2W terminating resistors on the ICUNO-MOD board first and last devices in the network. See ICUNO-MOD Installation and Commissioning Guide (9590-3013) for details. Important: Any Earth connections made to any controllers shall be from a common main earth point.

Procedure for Earthing the Shield

  • The shield of the cable of the J4 FBus terminal on the BMS Gateway (GW100) should be earthed. Earth only one end of the serial cable shield (shield connected to every second device).

Universal Inputs/Outputs

  • Universal inputs/outputs are distinguished by the letter U.
  • U1 is designated as a digital input for network parameter reset.
  • U6 has been designated as a 0-10VDC output, drivable by BMS.
  • U2-U5 and U7-U10 can be configured to accept the following to be monitored by the BMS for site specific purposes:

Analogue Inputs

  • NTC (10K@25)
  • NTC (50K@25K)
  • PTC1000
  • 0-10 Vdc signals *
  • 4 to 20 mA signals **
  • Ratiometric probes ***

Digital inputs (not optically-isolated)

  • voltage-free contacts (not optically-isolated)
  • voltage-free Alarm contacts (not optically-isolated)
  • Powered Externally
  • Max 2 powered by controller. Max 4 powered Externally
  • Max 2

Important: Important:

  • The universal inputs/outputs cannot be used as digital outputs.

Digital Outputs 
Digital Outputs are distinguished by the letter NO and NC.

  • NO6 (J12) is designated as the BMS Gateway general alarm.
  • NO1-NO5 (J10, J11) are available to be controlled via BMS input for site specific purposes.

Note:

  • Group 1 (R1, R2); Group 2 (R3, R4, R5): NO EN 60730-1 Maximum Switchable Load: 250VAC/2A resistive Group 3 (J6): NO EN 60730-1 Maximum Switchable Load: 250VAC/1A resistive
  • Between J10 and J11 terminals there is basic insulation.
  • J12 has reinforced insulation from the two other terminals (J10 and 11). Consequently a different power supply can be used.

Other Specifications

Environmental pollution Level 3
Front panel ingress protection

(with USB port closed)

IP40 front panel, IP10 remaining parts
Class of protection against electric shock To be integrated into Class I and/or II appliances
Material Technopolymer
Flammability V2 (UL94) and

850 °C (in accordance with IEC 60695-2-11)

PTI of the PCB insulating materials PTI 250
Insulating material PTI 175
Colour White RAL 9016
Ball pressure test temperature 125 °C
Period of stress across the insulating parts Long
Type of action digital output 1C
Type of disconnection or microswitching Microswitching
Heat and fire resistance category Category D (UL94 – V2)
Overvoltage category Category III
Software class and structure Class A
Do not touch or tamper with the device when powered.

Connection Diagram

ActronAir-GW100K-BMS-Gateway-Controller-fIG- (11)

NOTE

  • Ports available for this are Ethernet or RS485. However, only one port can be used and set as the network connection at a time.

ActronAir-GW100K-BMS-Gateway-Controller-fIG- (12)

Maximum Cable Length

MAXIMUM CABLE LENGTH BETWEEN DEVICES 

Connection Cable Type Maximum Length
Gateway Power Supply toBMS Gateway Power Cable 12m for 1.5mm² / 8m for 1.0mm²
BMS Gateway to Customer BMS Master Data Cable 500m
BMS Gateway to first Intermediate Device Signal Cable 500m
Customer BMS Master to Last Device Data Cable 1000m total cummulative length
Note: Effective distance may vary depending on noise in the network surrounding.

ICUNO-MOD Connection and Addressing

  • The BMS Gateway Controller System connects to individual ActronAir units through an ActronAir ICUNO-MOD module. During installation and commissioning, each ICUNO-MOD must be assigned an address that corresponds to the connected unit’s number, and the baud rate must be set. The BMS Gateway can support up to 10 ICUNO-MOD modules.
  • To assign an address, adjust the DIP switches on each ICUNO-MOD to match the desired unit number. The GW100 Gateway is configured to automatically detect each module’s assigned address.
  • For detailed installation and configuration instructions, please refer to the ICUNO-MOD Installation and Commissioning Guide (Document 9590-3013).

ActronAir-GW100K-BMS-Gateway-Controller-fIG- (13)

Installation and Configuration BMS Gateway

  • Step 1. Install BMS Gateway and the SMPS (included in the kit) in the desired locations.
  • Step 2. Adjust the SMPS power output to 28VDC.
  • Step 3. Connect 240VAC to SMPS.
  • Step 4. Connect 28VDC from SMPS to the BMS gateway.
  • Step 5. Install ICUNO-MOD cards (refer to ICUNO manual).
  • Step 6. Set DIP switches according to unit number (listed in BMS gateway manual).
  • Step 7. Run fieldbus cable between ICUNO-MOD cards and J4 on the BMS gateway.
  • Step 8. Power BMS Gateway.

BMS Menu and Navigation

Menu Navigation

  • Press the Up( ActronAir-GW100K-BMS-Gateway-Controller-fIG- (14) ) or Down( ActronAir-GW100K-BMS-Gateway-Controller-fIG- (15)) arrow to go the previous or next line. When cursor is in a variable character, this will toggle the value or increment/decrease the set value.
  • Press Enter (ActronAir-GW100K-BMS-Gateway-Controller-fIG- (16) ) to into the menu (see Menu Tree Section for guide). When cursor is in a variable character, this will select he value currently displayed.
  • Press Esc (ActronAir-GW100K-BMS-Gateway-Controller-fIG- (16) ) to go back to main screen.

Complete programming menu tree
Below is the complete menu tree of the configuration menu.

Menu Screen

Reference

Parameter Settings Menu Description Menu

Type

 

 

 

 

 

Input/ Output

 

 

Test – Device 01 – 10

 

 

Aa01

Unit On/Off 0 – 1 Read and Write the ON/OFF command – ICUNO-MOD

holding register 1

 

 

U

Master Set Point 16.0 – 30.0 Read and Write the Master Set Point – ICUNO-MOD holding

register 102

Indoor Coil

Temperature

  Returns Indoor Coil Temperature – ICUNO-MOD holding

register 1301

OD Firmware   Returns OD Firmware – ICUNO-MOD holding register 1001
  Subsequent screens are replicated for Device 02 – 10: Aa02 – A10
Device 11 – Onboard Aa11 Input/Output 01-05   Status of U1-U5 U
Device 11 – Onboard Aa12 Input/Output 06-10   Status of U6-U10 U
Device 11 – Onboard Aa13 Relay 01-06   Status of relay 01-06 U
Output Override Aa14 Relay 01-06 Auto – On – Off Override output relay 01-06 S
Output Overide Aa15 Reset Overides No – Yes Resets the status of the relay overides S
Info Info Ab01 – 07 Info   System Information (SW version, OS version, Device

information)

S
 

 

 

Input Config

Universal Input U02 Ad01 Refer to 03.07.04   Universal Input U02 configuration S
Universal Input U03 Ad02 Refer to 03.07.04   Universal Input U03 configuration S
Universal Input U04 Ad03 Refer to 03.07.04   Universal Input U04 configuration S
Universal Input U05 Ad04 Refer to 03.07.04   Universal Input U05 configuration S
Universal Input U07 Ad05 Refer to 03.07.04   Universal Input U07 configuration S
Universal Input U08 Ad06 Refer to 03.07.04   Universal Input U08 configuration S
Universal Input U09 Ad07 Refer to 03.07.04   Universal Input U09 configuration S
Universal Input U10 Ad08 Refer to 03.07.04   Universal Input U10 configuration S
 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit Config

 

 

 

 

 

 

 

 

 

Unit Configuration

Ae00 Number of Devices 1-10 Sets the number of connected devices S
Disable Device Y – N Enable/Disable the device in from communication
 

 

 

 

Ae01A

Device 01 Y – N Enable additional variables  

 

 

 

S

Ana_01 reg#: 1-9999 | R – R/W Set ICUNO-MOD holding register and read type –

Additional Analogue Variables

Ana_02 reg#: 1-9999 | R – R/W Set ICUNO-MOD holding register and read type –

Additional Analogue Variables

Ana_03 reg#: 1-9999 | R – R/W Set ICUNO-MOD holding register and read type –

Additional Analogue Variables

Ana_04 reg#: 1-9999 | R – R/W Set ICUNO-MOD holding register and read type –

Additional Analogue Variables

Ana_05 reg#: 1-9999 | R – R/W Set ICUNO-MOD holding register and read type –

Additional Analogue Variables

 

 

 

 

Ae01D

Device 01 Y – N Enable additional variables  

 

 

 

S

Dig_01 reg#: 1-9999 | R – R/W Set ICUNO-MOD holding register and read type –

Additional Digital Variables

Dig_02 reg#: 1-9999 | R – R/W Set ICUNO-MOD holding register and read type –

Additional Digital Variables

Dig_03 reg#: 1-9999 | R – R/W Set ICUNO-MOD holding register and read type –

Additional Digital Variables

Dig_04 reg#: 1-9999 | R – R/W Set ICUNO-MOD holding register and read type –

Additional Digital Variables

Dig_05 reg#: 1-9999 | R – R/W Set ICUNO-MOD holding register and read type –

Additional Digital Variables

 

 

 

 

Unit Configuration

 

 

 

 

Ae01I

Device 01 Y – N Enable additional variables  

 

 

 

S

Int_01 reg#: 1-9999 | R – R/W Set ICUNO-MOD holding register and read type –

Additional Integer Variables

Int_02 reg#: 1-9999 | R – R/W Set ICUNO-MOD holding register and read type –

Additional Integer Variables

Int_03 reg#: 1-9999 | R – R/W Set ICUNO-MOD holding register and read type –

Additional Integer Variables

Int_04 reg#: 1-9999 | R – R/W Set ICUNO-MOD holding register and read type –

Additional Integer Variables

Int_05 reg#: 1-9999 | R – R/W Set ICUNO-MOD holding register and read type –

Additional Integer Variables

  Subsequent screens are replicated for Device 02-10: Ae02A – Ae10A, Ae02D – Ae10D, Ae02I – Ae10I
Menu Screen

Reference

Parameter Settings Menu Description Menu

Type

 

 

 

Unit Config

 

Parameter Import/ Export

 

 

Ae11

Import/Export Import – Export Set choice to Import or Export configuration file  

 

S

Memory Type Internal –

External

Select location to Import from or Export to configuration file
File Name 00 – 99 Select the configuration file name for Import/Export
Confirm Yes – No Confirm Import/Export request
 

Alarm Export

 

Ae12

Memory Type Internal – USB Set the location for alarm log to be exported  

S

File Name 00 – 99 Select the Alarm log file name for export
Confirm Yes – No Confirm Export request
Alarm

Logs

Data Logger       View the Alarm history U
 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Settings

 

 

Date/Time

 

Ba01

Format DD-MM-YYYY Set the Date format  

U

Date DD-MM-YYYY Set the Date
Hour HH-MM-SS Set the Time
Day Monday-Sunday Set the Day
Ba02 Time Zone UTC Sets the Time Zone U
UoM Bb01 User interface UoM   Sets the User interface Unit of Measure U
 

Language

  Language English Sets the user interface language  

U

Enter to Change, Esc to

confirm

Enter – Esc Changes and confirms the set language
 

 

 

 

 

 

 

 

 

 

 

Network

 

Bc01

Baud Rate 1200 – 375000 Sets the Baud rate speed for communication to ActronAir

ICUNO-MOD cards

 

S

Stopbits 1 – 2 Sets the Stop bits
Parity Even – Odd –

None

Sets the Parity
 

Bc02

Port Ethernet – RS485 Selects the BMS output port  

S

Device Instance 1 – 99999 Sets the Device instance
Offline Delay 3000ms Sets the BMS offline delay
Detect Timeout 1500ms Sets the BMS detect Timeout S
 

 

Bc03

Station Address 1 Sets the unique station address of the gateway on the RS-

485 bus

 

 

S

Max. Master 127 Specifies the address of the network Master with the

highest station address

Max. Info/Frame 10 Sets the maximum number of packages that can be

exchanged

 

Bc04

Baud rate 19200 Sets the BACnet data transfer speed  

S

Stopbits 1 Sets the Stop bits
Parity None Sets the Parity
Bc05 Net Configuration Enter Enter the network configuration screen S
 

 

Ca01/2

Enable Static – Off –

DHCP

Set the unit’s IP address for the Ethernet connection. Set

DHCP, subnet mask, gateway, DNS.

 

 

S

IP 192.168.0.1 Set the IP address
Mask 255.255.255.0 Set the Subnet Mask
GW 0.0.0.0 Set the Gateway
DNS 0.0.0. Set the DNS
Ca02/2 Update Config? Yes – No Set the “Update?” parameter to “YES” to update the network

settings

S
 

Password Change

  User: 0  

Change the password (User, Service, Installer)

 

U

Service 7378
Manufacturer 6268
 

Initialisation

  Delete alarm logs Yes – No Deletes the internal gateway alarm logs  

M

Clear AutoReset

counters

Yes – No Clears the AutoReset counters
Enable Buzzer Yes – No Sets the function of the internal alarm buzzer
Default Installation   Wipe Memory Yes – No Unit factory reset. Important: resetting the model will cancel

all of the control settings and load the default values

M
Logout Logout   Enter to logout Enter Information on the type of login performed. Provides option

to logout of that user access

U

Screens Available

  • When the BMS Gateway is installed in the system, the Customer BMS Master could access and navigate the setting of the network.

Home Screen: Device Status

  • This shows the connected devices.

ActronAir-GW100K-BMS-Gateway-Controller-fIG- (17)

  • X = Device has been set up but no communication
  • ActronAir-GW100K-BMS-Gateway-Controller-fIG- 40= Device has been set up and communication is established.
  • – = Device is set up and has been disabled in the unit configuration menu

Alarm Screen and Data Logger:

  • Below screen shows when the upper left corner button (ActronAir-GW100K-BMS-Gateway-Controller-fIG- (18) ) is pressed.

ActronAir-GW100K-BMS-Gateway-Controller-fIG- (19)

  • Press the Enter button(ActronAir-GW100K-BMS-Gateway-Controller-fIG- 41 ) until the screen below appears.
  • Use the Up(ActronAir-GW100K-BMS-Gateway-Controller-fIG- (14) ) or Down( ActronAir-GW100K-BMS-Gateway-Controller-fIG- (15)) arrows to navigate through the devices, as shown below:ActronAir-GW100K-BMS-Gateway-Controller-fIG- (20)
  • Use the Up(ActronAir-GW100K-BMS-Gateway-Controller-fIG- (14) ) or Down( ActronAir-GW100K-BMS-Gateway-Controller-fIG- (15)) arrows to navigate through the devices, as shown below:

Main Menu

  • To access the main menu, press the (ActronAir-GW100K-BMS-Gateway-Controller-fIG- (22) ) button on the left side of the display. Entering the main menu will prompt a log in screen where an access password will be required to be entered. See 08.01.04.
  • This screen will show when the middle button, Menu ( ActronAir-GW100K-BMS-Gateway-Controller-fIG- (22)) on the left is pressed.
  • Press the Up( ActronAir-GW100K-BMS-Gateway-Controller-fIG- (14)) or Down( ActronAir-GW100K-BMS-Gateway-Controller-fIG- (15)) arrow until the sub menu required appears. Press the Enter buttonActronAir-GW100K-BMS-Gateway-Controller-fIG- 41 to enter that menu.ActronAir-GW100K-BMS-Gateway-Controller-fIG- (23)

Login Screen

  • Press the Up(ActronAir-GW100K-BMS-Gateway-Controller-fIG- (14) ) or Down( ActronAir-GW100K-BMS-Gateway-Controller-fIG- (15)) arrow until the number required appears. Press the Enter button(ActronAir-GW100K-BMS-Gateway-Controller-fIG- 41 )to accept the value. Repeat until all numbers are set.

ActronAir-GW100K-BMS-Gateway-Controller-fIG- (24)

Password

  • User: 0000
  • Service: 7378
  • If you are logged in under USER and try to access a SERVICE restricted menu, it will be disallowed. You will need to log out as USER and log back in using the SERVICE password.

LogOut Screen

  • To go to the Log Out screen, go to the Main Menu, press the Up(ActronAir-GW100K-BMS-Gateway-Controller-fIG- (14) ) or Down(ActronAir-GW100K-BMS-Gateway-Controller-fIG- (15) ) arrow until Logout is highlighted. Press the Enter button(ActronAir-GW100K-BMS-Gateway-Controller-fIG- 41 )to select.ActronAir-GW100K-BMS-Gateway-Controller-fIG- (25)
  • The screen will show as below. Press the Enter buttonActronAir-GW100K-BMS-Gateway-Controller-fIG- 41 to log out.ActronAir-GW100K-BMS-Gateway-Controller-fIG- (26)

Input / Output Menu 

  • The Input/Output menu provides viewing and testing of pre-set variables for the purpose of verifying communication between the BMS gateway and the connected ActronAir system. Press the Up(ActronAir-GW100K-BMS-Gateway-Controller-fIG- (14) ) or Down(ActronAir-GW100K-BMS-Gateway-Controller-fIG- (15) ) arrow to select desired setting to change. Press  the Enter button(ActronAir-GW100K-BMS-Gateway-Controller-fIG- 41 ) to select the setting. Press the Up(ActronAir-GW100K-BMS-Gateway-Controller-fIG- (14) ) or Down( ActronAir-GW100K-BMS-Gateway-Controller-fIG- (15)) arrow to chage the parameter.ActronAir-GW100K-BMS-Gateway-Controller-fIG- (27)
  • There is a different input/output screen for each Device enabled.

NOTE

  • Unit On/Off – ICUNO-MOD register 1 – Read/Writable
  • Master Set Point – ICUNO-MOD register 102 – Read/Writable Indoor Coil Temperature – ICUNO-MOD register 1301 – Read only OD Firmware – ICUNO-MOD register 1001 – Read only

Information Menu

  • Provides information on the gateway hardware, firmware and network polling.
  • Software code and version will need to be provided when calling Actron Technical Service.ActronAir-GW100K-BMS-Gateway-Controller-fIG- (28)

Unit Configuration Menu

  • This menu allows for the configuration of the number of devices that the BMS gateway will be connected to.
  • If units are not to be configured and commissioned all at the same time, and was allocated a Device number in the BMS Gateway, these devices can be disabled to prevent alarm generation from the Gateway.
  • As an example, if three units (1, 2, and 3) are to be connected, but only units 1 and 3 will be commissioned at startup, set device 2 to ‘N.’ This will prevent the BMS Gateway from triggering an alarm when it cannot detect device 2.

ActronAir-GW100K-BMS-Gateway-Controller-fIG- (29)

Additional Variables

  • This allows the configuration of additional ICUNO-MOD variables that are not currently mapped in the gateway.
  • Each device connected to the BMS Gateway have the ability to configure an additional 5 Analog, 5 Integer, and 5 Digital variables, allowing for a maximum of 15 additional variables per device. The register entered will correspond to the holding register  provided by the ICUNO-MOD. The read/write status can be set for each variable.

ActronAir-GW100K-BMS-Gateway-Controller-fIG- (30)

NOTE

  • Ask for Actron Technical Support for further assistance on this.

Unit Configuration File This allows the export or import of configuration file.

ActronAir-GW100K-BMS-Gateway-Controller-fIG- (31)

Field Network Configuration

  • Fieldbus 1 is the communication from the BMS gateway to the ICUNO-MOD devices. Default parameters are:
  • Protocol: ActronAir Modbus (not changeable)
  • Baudrate: 19200
  • Stopbits: 1
  • Parity: Even

ActronAir-GW100K-BMS-Gateway-Controller-fIG- (32)

NOTE

  • These values must correspond with the configuration of all connected ICUNO-MOD cards.

BMS Network Connection

  • Ports available for this are Ethernet or RS485. However, only one port can be used and set as the network connection at a time.

ActronAir-GW100K-BMS-Gateway-Controller-fIG- (33)

Ethernet
Ethernet is the default setting. This is used for used for BACnet/IP and Modbus TCP/IP.

NOTE

  • If Ethernet is selected, J3 can be used to plug a CP05 or a CP10 terminal display.
  • Changing the Port selection requires the BMS gateway to be rebooted to take effect.

ActronAir-GW100K-BMS-Gateway-Controller-fIG- (34)

RS485
RS485 is selected for BACnet MS/TP (terminal J3). BACnet MS/TP configuration settings

ActronAir-GW100K-BMS-Gateway-Controller-fIG- (35)BACnet MS/TP port settings

ActronAir-GW100K-BMS-Gateway-Controller-fIG- (36)

NOTE

  • If RS485 is selected, J3 can only be used for BACnet MS/TP and a display terminal cannot be connected. Changing the Port selection requires the BMS gateway to be rebooted to take effect.

Network Configuration IP Settings This allows access and configuration of the Gateways IP settings.

ActronAir-GW100K-BMS-Gateway-Controller-fIG- (37)To save the network configuration, ‘Update Config’ must be set to Yes.

NOTE

  • The Net configuration menu is only visible when the BACnet port is set to Ethernet in menu Bc02

Troubleshooting

Restoring the Default values of the BMS Gateway 
This provides the ability to physically reset the gateways network address to default:

  • IP: 192.168.0.1
  • Subnet: 255.255.255.0
  • Step 1. Turn-Off power from mains supply by removing the fuse or switching the circuit breaker to the OFF position before performing the installation procedures. Follow sound LOCK-OUT/TAG-OUT (LOTO) procedures to ensure that power supply is not re-energized accidentally.
  • Step 2. Bridge U1-GND. Connect ends of the jumper wire to U1 and GND terminals to short. ActronAir-GW100K-BMS-Gateway-Controller-fIG- (38)
  • Step 3. Power system ON and wait to load.
  • Step 4. Remove the jumper wire (connected to the U1 and GND).
  • Step 5. Connect to the Gateway using default IP address settings.
  • Step 6. Configure desired IP address settings.

Link to the Register Table

There are two options to access the Registry Table.

Website
https://actronair.com.au/bmsgatewayregister/

QR

ActronAir-GW100K-BMS-Gateway-Controller-fIG- (39)

Once link is accessed, chose either View or Download the register table.

  • ©Copyright 2025 Actron Engineering Pty Limited ABN 34 002767240. ®Registered Trade Marks of Actron Engineering Pty Limited.
  • ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice.

FAQS

Q: What should I do if I encounter communication issues with the Gateway?
A: Check the cable connections, ensure proper addressing, and verify compatibility with the connected systems.

Q: Can I connect more than 10 Actron systems to a single Gateway unit?
A: No, the Gateway supports a maximum of 10 Actron systems per unit.

Q: How do I reset the Gateway to its default values?
A: Refer to section 09.01 in the manual for instructions on restoring default values.