ABB DI562 Digital Input Module

Dimensions

The dimensions are in mm and in brackets in inch.
Ordering data
| Part no. | Description | Product life cycle phase *) |
| 1TNE 968 902 R2101 | DI561, digital input module, 8 DI, 24 V DC / 24 V AC | Active |
| 1TNE 968 901 R3101 | Terminal block TA563-9, 9 pins, screw front, cable side, 6 pieces per unit | Active |
| 1TNE 968 901 R3103 | Terminal block TA564-9, 9 pins, screw front, cable front, 6 pieces per unit | Active |
| 1TNE 968 901 R3105 | Terminal block TA565-9, 9 pins, spring front, cable front, 6 pieces per unit | Active |
*) Modules in lifecycle Classic are available from stock but not recommended for planning and commissioning of new installations.
DI562 – Digital input module
- 16 digital inputs 24 V DC / 24 V AC (I0 … I15) in 2 groups
- Group-wise galvanically isolated
- I/O bus
- 16 yellow LEDs to display the signal states of the inputs I0 … I15
- Terminal number
- Allocation of signal name
- Terminal block for input signals (9-pin)
- Terminal block for input signals (11-pin)
- 2 holes for wall-mounting with screws
- DIN rail
- QR code for datasheet

Intended purpose
The device can be used as a decentralized I/O extension module for S500 communication interface modules (e.g. CI592-CS31, CI50x-PNIO, CI51x-ETHCAT, CI52x-MODTCP, CI54x-DP, CI58x-CN) or as a centralized extension module for AC500 CPUs.
The inputs are group-wise galvanically isolated from each other.
The other electronic circuitry of the module is galvanically isolated from the inputs.
The I/O module must not be used as a decentralized I/O module with CI590- CS31-HA communication interface modules.
Functionality
| Parameter | Value |
| LED displays | For signal states |
| Internal power supply | Via I/O bus |
| External power supply | Not necessary |
Connections
For a detailed description of the mounting, disassembly and connection of the module, please refer to the installation instructions.
The connection is carried out by using removable 9-pin and 11-pin terminal blocks. These terminal blocks differ in their connection system (spring terminals or screw-type terminals, cable mounting from the front or from the side). The terminal blocks are not included in the module’s scope of delivery and must be ordered separately.
Chapter 1.9.2.1 “TA563-TA565 – Terminal blocks” on page 1136

Fig. 16: Internal construction of the digital inputs
- Logic – I/O bus interface
- Digital inputs
Table 41: Assignments of the terminal
| Terminal | Signal | Description |
| 1 | C0 … C7 | Input common for signals I0 to I7 |
| 2 | I0 | Input signal I0 |
| 3 | I1 | Input signal I1 |
| 4 | I2 | Input signal I2 |
| 5 | I3 | Input signal I3 |
| 6 | I4 | Input signal I4 |
| 7 | I5 | Input signal I5 |
| 8 | I6 | Input signal I6 |
| 9 | I7 | Input signal I7 |
| 10 | C8 … C15 | Input common for signals I8 … I15 |
| 11 | I8 | Input signal I8 |
| 12 | I9 | Input signal I9 |
| 13 | I10 | Input signal I10 |
| 14 | I11 | Input signal I11 |
| 15 | I12 | Input signal I12 |
| 16 | I13 | Input signal I13 |
| 17 | I14 | Input signal I14 |
| 18 | I15 | Input signal I15 |
| 19 | — | Reserved |
| 20 | — | Reserved |
The internal power supply voltage for the module’s circuitry is carried out via the I/O bus (provided by a communication interface module or a CPU). Thus, the current consumption from 24 V DC power supply at the terminals L+/UP and M/ZP of the CPU/communication interface module increases by 5mA per DI562.
An external power supply connection is not needed.
WARNING!
Removal/Insertion under power
The devices are not designed for removal or insertion under power. Because of unforeseeable consequences, it is not allowed to plug or unplug devices with the power being ON.
Make sure that all voltage sources (supply and process voltage) are switched off before doing the following:
- Connect or disconnect any signal or terminal block.
- Remove, mount or replace a module.
Disconnecting any powered devices while energized in a hazardous location could result in an electric arc, which could create a flammable ignition resulting in fire or explosion.
Make sure that power is removed and that the area has been thoroughly checked to ensure that flammable materials are not present prior to proceeding.
The devices must not be opened when in operation. The same applies to the network interfaces.
NOTICE!
Risk of damaging the PLC modules!
Overvoltages and short circuits might damage the PLC modules.
- Make sure that all voltage sources (supply voltage and process supply voltage) are switched off before you begin with operations on the system.
- Never connect any voltages or signals to reserved terminals (marked with —). Reserved terminals may carry internal voltages.
The module provides several diagnosis functions Ä Chapter 1.6.1.1.3.6 “Diagnosis” on page 170.
The digital inputs can be used as source inputs or as sink inputs.
NOTICE!
Risk of malfunctions in the plant!
A ground fault, e. g. caused by a damaged cable insulation, can bridge switches accidentally.
Use sink inputs when possible or make sure that, in case of error, there will be no risks to persons or plant.
Table 42: Connection of the digital input module DI562

The meaning of the LEDs is described in section State LEDs Ä Chapter 1.6.1.1.3.7 “State LEDs” on page 170.
I/O configuration
The module itself does not store configuration data. It receives its parameterization data from the master device of the I/O bus (CPU or communication interface module) during power-up of the system.
Hence, replacing I/O modules is possible without any re-parameterization via software.
If the external power supply voltage via UP/ZP terminals fails, the I/O module loses its configuration data. The whole station has to be switched off and on again to re-configure the module.
Parameterization
The arrangement of the parameter data is performed with Automation Builder software.
The parameter data directly influences the functionality of modules.
For non-standard applications, it is necessary to adapt the parameters to your system configuration.
| Name | Value | Internal Value | Internal Value, Type | Default | Min. | Max. | EDS Slot Index |
| Module ID | Internal | 6110 1) | WORD | 6110
0x17DE |
0 | 65535 | xx01 |
| Ignore module | No Yes |
0 1 |
BYTE | No (0x00) | |||
| Parameter length 2) | Internal | 1 – CPU | BYTE | 0 | 0 | 255 | xx02 3) |
Remarks:
| 1) | With CS31 and addresses less than 70, the value is increased by 1 |
| 2) | The module has no additional user-configurable parameters |
| 3) | Value is hexadecimal: HighByte is slot (xx: 0 … 7), LowByte is index (1 … n) |
GSD file:
| Ext_User_Prm_Data_Len = Ext_User_Prm_Data_Const(0) = |
0x03 0xDF, 0x17, 0x00; |
Diagnosis
| E1 … E4 | d1 | d2 | d3 | d4 | Identifier 000 … 063 | AC500-
Display |
<− Display in | |
| Class | Comp | Dev | Mod | Ch | Err | AB SW | ||
| Byte 6
Bit 6 … 7 |
– | Byte 3 | Byte 4 | Byte 5 | Byte 6
Bit 0 … 5 |
PNIO
diagnosis block |
||
| Class | Interface | Device | Module | Channel | Error Identifier | Error message | Remedy | |
| 1) | 2) | 3) | 4) | |||||
| Module error DI562 | ||||||||
| 3 | 14 | 1 … 10 | 31 | 31 | 19 | Checksum error in the I/O module | Replace I/O module | |
| 11 / 12 | ADR | 1 … 10 | ||||||
| 3 | 14 | 1 … 10 | 31 | 31 | 43 | Internal error in the module | Replace I/O module | |
| 11 / 12 | ADR | 1 … 10 | ||||||
| 3 | 14 | 1 … 10 | 31 | 31 | 9 | Overflow diagnosis buffer | Restart | |
| 11 / 12 | ADR | 1 … 10 | ||||||
| 3 | 14 | 1 … 10 | 31 | 31 | 26 | Parameter error | Check master | |
| 11 / 12 | ADR | 1 … 10 | ||||||
Remarks:
| 1) | In AC500 the following interface identifier applies: 14 = I/O bus, 11 = COM1 (e.g. CS31 bus), 12 = COM2. The PNIO diagnosis block does not contain this identifier. |
| 2) | With “Device” the following allocation applies: 31 = module itself, 1 … 10 = decentralized communication interface module 1 … 10, ADR = hardware address (e. g. of the DC551-CS31) |
| 3) | With “Module” the following allocation applies depending on the master: Module error: I/O bus or PNIO: 31 = module itself; COM1/COM2: 1 … 10 = expansion 1 … 10 |
| 4) | In case of module errors, with channel “31 = module itself” is output. |
State LEDs
| LED | State | Color | LED = OFF | LED = ON | |
![]() |
Inputs I0 … I15 | Digital input | Yellow | Input is OFF | Input is ON |
In the undefined signal range, the state LED for the inputs can be ON although the input state detected by the module is OFF.
Technical data
Technical data of the module
The system data of AC500-eCo apply.
Chapter 2.5.1 “System data AC500-eCo” on page 1165
Only additional details are therefore documented below.
| Parameter | Value | |
| Galvanic isolation | Yes, between the input groups and the rest of the module | |
| Isolated groups | 2 (8 channels per group) | |
| Current consumption from 24 V DC power supply at the L+/UP and M/ZP terminals of the CPU/communication interface module | Ca. 5 mA | |
| Max. power dissipation within the module | 3.2 W | |
| Weight | Ca. 115 g | |
| Mounting position | Horizontal or vertical | |
| Cooling | The natural convection cooling must not be hindered by cable ducts or other parts in the control cabinet. | |
Technical data of the digital inputs
| Parameter | Value | |||
| Number of channels per module | 16 inputs (24 V DC / 24 V AC) | |||
| Distribution of the channels into groups | 2 (8 channels per group) | |||
| Connections of the channels I0 to I7 | Terminals 2 … 9 | |||
| Connections of the channels I8 to I15 | Terminals 11 … 18 | |||
| Reference potential for the channels I0 to I7 | Terminal 1 (positive or negative pole of the process supply voltage, signal name I0 … I7) | |||
| Reference potential for the channels I8 to I15 | Terminal 10 (positive or negative pole of the process supply voltage, signal name I8 … I15) | |||
| Indication of the input signals | 1 yellow LED per channel; the LED is ON when the input signal is high (signal 1). The module is pow-ered through the I/O bus. | |||
| Monitoring point of input indicator | LED is part of the input circuitry | |||
| Input type according to EN 61131-2 | Type 1 source | Type 1 sink | Type 1 AC 1) | |
| Input signal range | -24 V DC | +24 V DC | 24 V AC 50/60 Hz | |
| Signal 0 | -5 V … +3 V | -3 V … +5 V | 0 V AC … 5 V AC | |
| Parameter | Value | |||
| Undefined signal | -15 V … -5 V | +5 V … +15 V | 5 V AC … 14 V AC | |
| Signal 1 | -30 V … -15 V | +15 V … +30 V | 14 V AC … 27 V AC | |
| Input current per channel | ||||
| Input voltage 24 V | Typ. 5 mA | Typ. 5 mA r.m.s. | ||
| Input voltage 5 V | Typ. 1 mA | Typ. 1 mA r.m.s. | ||
| Input voltage 14 V | Typ. 2.7 mA r.m.s. | |||
| Input voltage 15 V | > 2.5 mA | |||
| Input voltage 27 V | Typ. 5.5 mA r.m.s. | |||
| Input voltage 30 V | < 8 mA | |||
| Max. permissible leakage current (at 2-wire proximity switches) | 1 mA | Typ. 1 mA r.m.s. | ||
| Input delay (0->1 or 1->0) | Typ. 8 ms | |||
| Input data length | 2 bytes | |||
| Max. cable length | ||||
| Shielded | 500 m | |||
| Unshielded | 300 m | |||
- For version before E0, when inputs are used with 24 V AC, external surge limiting filters are required.
Refer to ‘System data AC500-eCo’ for details Ä Chapter 2.5.1 “System data AC500-eCo” on page 1165.
Dimensions

The dimensions are in mm and in brackets in inch.
Ordering data
| Part no. | Description | Product life cycle phase *) |
| 1TNE 968 902 R2102 | DI562, digital input module, 16 DI, 24 V DC / 24 V AC | Active |
| 1TNE 968 901 R3101 | Terminal block TA563-9, 9 pins, screw front, cable side, 6 pieces per unit | Active |
| 1TNE 968 901 R3102 | Terminal block TA563-11, 11 pins, screw front, cable side, 6 pieces per unit | Active |
| 1TNE 968 901 R3103 | Terminal block TA564-9, 9 pins, screw front, cable front, 6 pieces per unit | Active |
| 1TNE 968 901 R3104 | Terminal block TA564-11, 11 pins, screw front, cable front, 6 pieces per unit | Active |
| 1TNE 968 901 R3105 | Terminal block TA565-9, 9 pins, spring front, cable front, 6 pieces per unit | Active |
| 1TNE 968 901 R3106 | Terminal block TA565-11, 11 pins, spring front, cable front, 6 pieces per unit | Active |