Prevent water from entering on or in the iluminare at installation and during use of the luminaire.

INSTALLATIONPHILIPS-LL217X-BV-CoreLine-Trunking-Gen2-Leaner-FIG0-4 PHILIPS-LL217X-BV-CoreLine-Trunking-Gen2-Leaner-FIG0-5 PHILIPS-LL217X-BV-CoreLine-Trunking-Gen2-Leaner-FIG0-6 PHILIPS-LL217X-BV-CoreLine-Trunking-Gen2-Leaner-FIG0-7 PHILIPS-LL217X-BV-CoreLine-Trunking-Gen2-Leaner-FIG0-8 PHILIPS-LL217X-BV-CoreLine-Trunking-Gen2-Leaner-FIG0-9 PHILIPS-LL217X-BV-CoreLine-Trunking-Gen2-Leaner-FIG0-10 PHILIPS-LL217X-BV-CoreLine-Trunking-Gen2-Leaner-FIG0-11 PHILIPS-LL217X-BV-CoreLine-Trunking-Gen2-Leaner-FIG0-12 PHILIPS-LL217X-BV-CoreLine-Trunking-Gen2-Leaner-FIG0-13 PHILIPS-LL217X-BV-CoreLine-Trunking-Gen2-Leaner-FIG0-14 PHILIPS-LL217X-BV-CoreLine-Trunking-Gen2-Leaner-FIG0-15 PHILIPS-LL217X-BV-CoreLine-Trunking-Gen2-Leaner-FIG0-16 PHILIPS-LL217X-BV-CoreLine-Trunking-Gen2-Leaner-FIG0-17+

Inrush currentPHILIPS-LL217X-BV-CoreLine-Trunking-Gen2-Leaner-FIG0-18

 

 

 

 

TYPE

 

53S 1xPSU (36W)

 

30S/45S 1xSRD (35W)

 

90S 2x SRD (35W)

 

30S/45S 1xPSD (35W)

 

90S 2xPSD (35W)

 

30S/45S/53S/80S 1xPSD (60W)

 

90S/160S 2xPSD (60W)

 

53S/80S 1xSRD (60W)

 

160S 2xSRD (60W)

 

45S/80S 1xPSU (75W)

 

90S/160S 2xPSU (75W)

 

80S/120S 1xPSU (100W)

 

240S 2xPSU (100W)

 

80S/90S/120S 1xPSD (100W)

 

240S 2xPSD (100W)

 

80S/90S/120S 1xSRD (100W)

 

240S 2xSRD (100W)

 

80S/120S/160S 1xPSD (150W)

 

240S 2xPSD (150W)

 

160S 1xSRD (150W)

Imax [A] 14,0 21,0 42,0 23,1 46,2 25,1 50,2 21,0 42,0 19,0 38,0 22,5 45,0 10,0 20,0 4,5 9,0 5,1 10,2 5,1
Tref [μs] 250 280 280 221 221 214 214 280 280 280 280 30 30 35,9 35,9 1000 1000 760 760 760
cable Ø [mm²] 1.5 / 2.5*
MCB B-6A 13/13 8/8 4/4 8/8 4/4 8/8 4/4 8/8 4/4 9/9 4/4 9/9 4/4 7/7 3/3 7/7 3/3 6/6 3/3 4/4
MCB B-10A 20/20 13/13 6/6 13/13 6/6 13/13 6/6 13/13 6/6 15/15 7/7 14/14 7/7 11/11 5/5 11/11 5/5 10/10 5/5 7/7
MCB C-10A 34/34 21/21 10/10 22/22 11/11 21/21 10/10 21/21 10/10 24/24 12/12 23/23 11/11 18/18 9/9 18/18 9/9 16/16 8/8 12/12
MCB B-13A 26/26 17/17 8/8 17/17 8/8 17/17 8/8 17/17 8/8 19/19 9/9 18/18 9/9 14/14 7/7 14/14 7/7 12/12 6/6 9/9
MCB C-13A 40/44 28/28 14/14 29/29 14/14 28/28 14/14 28/28 14/14 32/32 16/16 30/31 15/15 24/24 12/12 24/24 12/12 20/21 10/10 16/16
MCB B-16A 33/33 21/21 10/10 22/22 11/11 21/21 10/10 21/21 10/10 24/24 12/12 23/23 11/11 18/18 9/9 18/18 9/9 16/16 8/8 12/12
MCB C-16A 40/56 35/35 17/17 37/37 18/18 35/35 17/17 35/35 17/17 40/40 20/20 30/39 15/19 30/30 15/15 30/30 15/15 20/27 10/13 20/20

Warning: The values on the left are for 1.5 mm thick cables, the values on the right are for 2.5 mm thick cables

Maintenance instructions

To asssure the lighting quality of this unique LED lighting concept there are a few instructions regading the maintenance of this LED luminaire:

  1. Do not touch electronic components!
    Electronic components are under high voltage.
    Electronic components are ESD sensitive.
  2. During installation or when maintaining the luminaire please use static free gloves to avoid marks on the luminaire.
  3. To remove dirt and spots use the following:
    Dust: only use micro fiber cloths
    Fingerprints, etc.: use a cleaner for
    synthetic materials with antistatic properties.
  4. Do not stare into the LED light beam.
  5. To avoid scratches and dirt on optical parts remove protective foil after installation.
  6. The luminaire shall be installed by a qualified electrician and wired in accordance with the lastest IEE electrical regulations or the nationak requirements.
  7. The light source of this luminarie is not replaceable: when the light source reaches its end of life whole luminare shall be replaced.
  8. Driver insulation: Basic according to IEC 61847-1.

Disconnectbeforeservicing: Luminaire has basic insulation between Low Voltage supply and control conductors.

Printed in Poland Data subject to change without notice
Keep for future reference: www.philips.com/lighting

Documents / Resources

PHILIPS LL217X BV CoreLine Trunking Gen2 Leaner Light [pdf] Instructions
LL217X BV, LL234X BV, LL217X BV CoreLine Trunking Gen2 Leaner Light, LL217X BV, CoreLine Trunking Gen2 Leaner Light, Trunking Gen2 Leaner Light, Gen2 Leaner Light, Leaner Light, Light

References

Leave a comment

Your email address will not be published. Required fields are marked *