BCM-0000-B Battery Controller Module
Installation Guide
BCM-0000-B Battery Controller Module
Safety Notes
NOTICE!
- Installation must only be carried out by authorized personnel.
- The BCM-0000-B can only be used with panel controllers FPA-1200-MPC and MPC-xx00-B with software versions from 2.1 onwards.
- The total current for all connected components, including the battery charge current, must not exceed 6 A.
- The 24 V switch outputs must not be connected in parallel.
- The batteries connected to BCM-0000-B must all be the same type and have the same electrical features.
- The length of the cable on the fault switch outputs must not exceed 3 meters (approx. 9.8 feet).
- The cables on the fault switch outputs must only be installed within the housing.
Functions
The module monitors the power supply for the complete panel and regulates battery charging as a function of time and temperature. The button has three functions, which are dependent on the status of the battery controller module:
- The four module LEDs light up as a confirmation and LED test each time the button is pressed.
- If the batteries have a voltage of between 18 V and 21 V, the battery loading procedure can be started manually. Please note that a power supply must be available.
- The 24 V switch outputs can be reset. The switch output is deactivated if a fault occurs.
Terminal assignment
See drawing on page 4.
Labeling | Connection |
Upper connections, from left to right | |
24 V +/- | Switch output +24 V max. 2.8 A (battery buffered, optional) |
24 V +/- | Switch output +24 V max. 2.8 A (battery buffered, optional) |
Lower connections, from left to right | |
MAIN +/- | Power supply unit connection |
MAIN FAULT | Signal input, power supply fault |
BAT1 +/- | Battery pair 1 connection |
BAT2 +/- | Battery pair 2 connection |
FAULT AC – | Switch output, mains fault |
FAULT BAT – | Switch output, battery fault |
FAULT 1 – | Switch output, collective fault |
FAULT +24 V | Switch output + |
Standby current calculation in accordance with EN 54-4Formula (1) gives the maximum panel current required to provide a specific buffering time (Imax, Standby).
Formula (2) gives the maximum panel current with simultaneous consideration of the battery charge (Imax, A ).
According to formula (3), the required standby current of the panel (Ibom) is based on the smaller value of the two maximum current values of the panel.
Parameter:
- standby = buffering time in hour
- I Alarm = maximum alarm current (Imax)
- Catt = battery capacity in Ah
The following capacities are feasible:
- 24–26 Ah and 36–45 Ah for 2 batteries
- 48–52 Ah and 72–90 Ah for 4 batteries
Technical Specifications
Input voltage | 20.4 V to 30 V |
Current consumption at 24 V DC – Standby operation – Fault |
25 mA 40 mA |
Approved battery capacities – with 2 batteries – with 4 batteries |
24 – 26 Ah 36 – 45 Ah 48 – 52 Ah 72 – 90 Ah |
Maximum current – of the module – to the panel rails (PRS 0002 A/PRS 0004 A) – of the switch outputs |
Max. 6 A Max. 6 A Max. 5.6 A (2 x 2.8 A cannot be connected in parallel) |
Fault threshold | Max. 430 ma battery resistance |
Outputs 2 switch outputs +24 V / 0 to 2.8 A, battery buffered 1 switch output battery fault, 0 V / 0 to 20 mA 1 switch output mains fault, 0 V / 0 to 20 mA 1 switch output Collective fault in accordance with EN 54-4, 0 V / 0 to 20 mA |
|
Display and operating elements 1 green LED Mains power on 3 yellow LEDs Mains fault, battery 1 fault, battery 2 fault 1 button Charge battery, start panel without mains current, reset fault | |
Permissible operating temperature | -5°C to 50°C |
Permissible storage temperature | -25°C to 85°C |
Permissible relative humidity | max. 95% non-condensing |
Housing material and color | ABS plastic, satin finish, anthracite, RAL 7016 |
Dimensions (H x W x D) | approx. 127 x 96 x 60 mm (5 x 3.8 x 2.4 inches) |
Weight | 193 g (0.43 Ibs) |
Bosch Sicherheitssysteme GmbH
Robert-Koch-Straße 100
D-85521 Ottobrunn
Germany
Telefon +49 89 6290-0
Fax +49 89 6290-1020
www.boschsecurity.com
© Bosch Sicherheitssysteme GmbH, 2009