Protector Three Phase Adjustable V A

Overview
The Three Phase Adjustable V/A Protector provides individually adjustable protection functions, including a power-on delay plus overvoltage, undervoltage, and overcurrent protections. Protection action times and recovery times can be set independently, and each protection function can be turned on or off.
Specifications
| Rated supply voltage | L-N: AC 230V / L-L: 380V |
| Operating voltage range | L-N: AC 80V–300V |
| Rated frequency | 50/60 Hz |
| Rated insulation voltage | AC 450V |
| Output contact | 3NO (Normally Open) |
| Voltage measurement accuracy | ≤ 2% (across the entire spectrum) |
| Display / indicator | L1: Yellow, L2: Green, L3: Red |
| Voltage display example | 22.0V (as shown) |
| Current display example | 63.0A (as shown) |
| Warning indicators | >V (Overvoltage warning), >A (Overcurrent warning) |
| Controls | SET (Settings key), ▲ (Adjusting key Up), ▼ (Adjusting key Down), POWER (Output prompt) |
Quick Setup
- Use the SET key to enter settings.
- Use ▲ and ▼ to adjust protection-related values.
- Enable or disable each protection function individually (power-on delay, overvoltage, undervoltage, overcurrent).
- Independently set protection action times and recovery times for each enabled function.
- Use the indicator lights (L1/L2/L3) and the display/warnings (>V, >A) to monitor the device status.
Functions
- Adjustable power-on delay
- Adjustable overvoltage protection
- Adjustable undervoltage protection
- Adjustable overcurrent protection
- All protections can be individually turned on or off
- All protection action times and recovery times can be set independently
Technical Parameters
| Parameter | Value / Specification |
|---|---|
| Rated supply voltage | L – N: AC 230V / L – L: 380V |
| Operating voltage range | L – N: AC 80V – 300V |
| Rated frequency | 50/60Hz |
| Rated insulation voltage | AC 450V |
| Output contact | 3NO (Normally Open) |
| Voltage measurement accuracy | ≤2% (Across the entire spectrum) |
Display Panel
Indicator Light Status: L1: Yellow | L2: Green | L3: Red

Parameter Configuration
| Code | Option / Parameter Description | Set Range | Default Value |
|---|---|---|---|
| P1 | Power-on delay | 1 – 999 s | 5s |
| P2 | Overvoltage action value | 130 – 300V – OFF | 265V |
| P3 | Overvoltage action time | 0.1 – 30.0s | 5s |
| P4 | Overvoltage recovery value | 125 – 295V | 265V |
| P5 | Overvoltage recovery time | 1.0 – 500s | 30s |
| P6 | Undervoltage action value | 80 – 210V – OFF | 170V |
| P7 | Undervoltage action time | 0.1 – 60.0s | 0.5s |
| P8 | Undervoltage recovery value | 85 – 215V | 175V |
| P9 | Undervoltage recovery time | 1.0 – 500s | 30s |
| P10 | Overcurrent action value | 1.0 – 63A / 80A / 100A | 100A |
| P11 | Overcurrent action time | 0.1 – 30s | 1.0s |
| P12 | Overcurrent recovery time | 1.0 – 500s | 30s |
| P13 | Overcurrent automatic closing attempts | 1 – 20 – OFF | 5 |
| P14 | Voltage sampling calibration coefficient | -9.9% to +9.9% | 0 |
| P15 | Current sampling calibration coefficient | -9.9% to +9.9% | 0 |
| P16 | Password settings | 1 – 999 | 112 |
Product Dimensions
Wiring Diagram
Troubleshooting
- Overvoltage warning (>V) appears: Review and adjust the overvoltage protection settings (including whether overvoltage protection is enabled).
- Overcurrent warning (>A) appears: Review and adjust the overcurrent protection settings (including whether overcurrent protection is enabled).
- Unexpected protection behavior: Confirm that each protection function is set to the intended on/off state, and verify that the protection action time and recovery time values are set independently as required.