FRIGA-BOHN MOSC Compressor Rack Installation Guide

FRIGA-BOHN-logo

FRIGA-BOHN MOSC Compressor Rack

FRIGA-BOHN-MOSC-Compressor-Rack-product

Overview

This manual provides dimensional characteristics, handling guidance, technical data for MOSC positive/negative compressor rack models, and installation/technical details for oil level and liquid level monitoring components used with compressor systems.

Specifications

Specification Details
Dimensional characteristics (MOSC models) — H / P / A / L’ / P’ / H’ Positive: MOSC 64/5P: 1400 / 800 / 655 / 650 / 620 / 1700; MOSC 90/5P: 1400 / 800 / 655 / 650 / 620 / 1950; MOSC 108/6P: 1400 / 1000 / 755 / 650 / 620 / 1950; MOSC 110/5P: 1400 / 1000 / 755 / 650 / 620 / 1950; MOSC 129/5P: 1400 / 1000 / 755 / 650 / 620 / 1750; MOSC 132/6P: 1400 / 1000 / 755 / 650 / 620 / 1750; MOSC 154/6P: 1400 / 1000 / 755 / 650 / 620 / 1750. Negative: 20/5N: 1400 / 800 / 655 / 650 / 620 / 1700; 23/5N: 1400 / 800 / 655 / 650 / 620 / 1700; 28/6N: 1400 / 1000 / 755 / 650 / 620 / 1950; 35/5N: 1400 / 1000 / 755 / 650 / 620 / 1750; 38/5N: 1400 / 1000 / 755 / 650 / 620 / 1750; 42/6N: 1400 / 1000 / 755 / 650 / 620 / 1750; 45/6N: 1400 / 1000 / 755 / 650 / 620 / 1750.
Weight — liquid station Positive: MOSC 64/5P: 140 kg; 90/5P: 190 kg; 108/6P: 190 kg; 110/5P: 190 kg; 129/5P: 230 kg; 132/6P: 230 kg; 154/6P: 230 kg. Negative: 20/5N: 140 kg; 23/5N: 140 kg; 28/6N: 190 kg; 35/5N: 230 kg; 38/5N: 230 kg; 42/6N: 230 kg; 45/6N: 230 kg.
Compressor weights (positive/negative) Positive: 64/5P (5 x ZB56) 820 kg; 30/5P (5 x ZB75) 820 kg; 110/5P (5 x ZB92) 890 kg; 129/5P (5 x ZB11) 930 kg; 108/6P (6 x ZB75) 980 kg; 132/6P (6 x ZB92) 1040 kg; 154/6P (6 x ZB11) 1100 kg. Negative: 20/5N (5 x ZF24) 820 kg; 23/5N (5 x ZF33) 820 kg; 35/5N (5 x ZF40) 890 kg; 38/5N (5 x ZF48) 930 kg; 28/6N (6 x ZF33) 980 kg; 42/6N (6 x ZF40) 1040 kg; 45/6N (6 x ZF48) 1100 kg.
Technical data — Positive models (I max / I dem / P max) 64/5P: 80 A / 163 A / 40 kW; 90/5P: 110 A / 222 A / 61 kW; 110/5P: 125 A / 269 A / 68 kW; 129/5P: 150 A / 307 A / 83 kW; 108/6P: 132 A / 244 A / 73 kW; 132/6P: 150 A / 294 A / 82 kW; 154/6P: 180 A / 337 A / 99 kW.
Technical data — Negative models (I max / I dem / P max) 20/5N: 81 A / 163 A / 43 kW; 23/5N: 112 A / 223 A / 65 kW; 35/5N: 126 A / 259 A / 73 kW; 38/5N: 155 A / 311 A / 85 kW; 28/6N: 97 A / 180 A / 52 kW; 42/6N: 134 A / 246 A / 77 kW; 45/6N: 151 A / 285 A / 87 kW.
Oil level regulator — INT280 Supply voltage: AC 24V 50/60Hz ±10%, 15VA; AC 115V 50/60Hz ±10%, 15VA; AC 230V 50/60Hz ±10%, 15VA. Permitted ambient temperature: -30…+60°C. Medium temperature: -30…+100°C. Operating pressure: -1…46 bar. Differential pressure: 1…25 bar (across valve). Relay: AC 240V, 2.5A, C300. Protection class: IP65 (per EN 60529). Connecting cable: 6xAWG18 (0.75 mm²), length 1 m. Housing material: Aluminium and PA66/PA6 (glass-fibre-reinforced). Flange connection: 3- / 4-hole flange. Oil connection: 7/16-20 UNF. Permitted oils: standard mineral and ester oil, without additives. Permitted refrigerants: all non-corrosive standard refrigerants. Weight: approx. 950 g. Mechanical service life: approx. 10^6 switching cycles (stated as approx. 106). Mechanical service life also stated as approx. 106 switching cycles.
Liquid level monitoring — INT275 L Optical, contactless level monitoring. Relay on delay after supply voltage: about 3 s (3s±1s). Relay off (low level) after: 5 s±2 s; relay off (fault) after: 5 s±2 s; relay on (level high again) after: 5 s±2 s; relay on (fault disappears) after: 5 s±2 s. Relay rating: AC250V, 2.5A, C300. Mechanical service life: approx. 106 switching cycles. Protection class: IP54 when mounted (per EN60529). Supply voltages listed: 230V version: INT275 L Level Monitoring, electrical part 52S475S60; 115V version: electrical part 41S475S60. Screw-in part: ambient temperature range -30…+60°C; max. temperature at prism +80°C; test pressure 32 bar; mounting M20x1.5mm (wrench size 24) or NPT1/2 (wrench size 24); weight approx. 75 g. Electrical part: ambient temperature range -30…+60°C; connecting cable 4xAWG18 (0.75mm²), L=1 m, colour-coded; weight approx. 80 g.

Quick Guide

  1. Handling: Use a pallet truck or forklift truck and handle the unit from the front (compressor side).
  2. Oil level regulator INT280: Ensure the flange is properly tightened. Carry out the electrical connection according to the provided wiring diagram.
  3. Liquid level sensor INT275 L: Ensure seal tightness for the specific application. Clean the inside of the screw-in part and the prism. Fit the electrical part into the screw-in part and tighten the coupling ring (torque approx. 10 Nm). Position the lead so the cable exit is downwards. Complete the electrical wiring according to circuit suggestions. After filling the tank, check the tightness of all joints.

Dimensional characteristics

FRIGA-BOHN-MOSC-Compressor-Rack-fig- (1) FRIGA-BOHN-MOSC-Compressor-Rack-fig- (2)MOSC Positive

0oGHO + [PP] 3 [PP] $ [PP] / [PP] 3 [PP] + [PP] :HigKt  OiTXiG

station [kg]

MOSC 64/SP 1400 800 655 650 620 1700 140
MOSC 90/SP 1400 800 655 650 620 1950 190
MOSC 108/6P 1400 1000 755 650 620 1950 190
MOSC 110/SP 1400 1000 755 650 620 1950 190
MOSC 129/SP 1400 1000 755 650 620 1750 230
MOSC 132/6P 1400 1000 755 650 620 1750 230
MOSC 1S4/6P 1400 1000 755 650 620 1750 230

MOSC Negative

0oGHO + [PP] 3 [PP] $ [PP] / [PP] 3 [PP] + [PP] :HigKt OiTXiG station [kg]
20/SN 1400 800 655 650 620 1700 140
23/SN 1400 800 655 650 620 1700 140
28/6N 1400 1000 755 650 620 1950 190
3S/SN 1400 1000 755 650 620 1750 230
38/SN 1400 1000 755 650 620 1750 230
42/6N 1400 1000 755 650 620 1750 230
4S/6N 1400 1000 755 650 620 1750 230

Weight positive / Weight négative

Model Compressor Weight (Kg) model Compresseur Weight (Kg)
64/SP 5 x ZB56 820 20/SN 5 x ZF24 820
30/SP 5 x ZB75 820 23/SN 5 x ZF33 820
110/SP 5 x ZB92 890 3S/SN 5 x ZF40 890
129/SP 5 x ZB11 930 38/SN 5 x ZF48 930
108/6P 6 x ZB75 980 28/6N 6 x ZF33 980
132/6P 6 x ZB92 1040 42/6N 6 x ZF40 1040
1S4/6P 6 x ZB11 1100 4S/6N 6 x ZF48 1100

Technical data

Positive / Négative

MODEL Compressors I max

(A]

I dem

[A]

P max

[kW]

MODEL Compressors I max

(A]

I dem

[A]

P max

[kW]

64/5P 5 x ZB56 80 163 40 20/5N 5 x ZF24 81 163 43
90/5P 5 x ZB75 110 222 61 23/5N 5 x ZF33 112 223 65
110/5P 5 x ZB92 125 269 68 35/5N 5 x ZF40 126 259 73
129/5P 5 x ZB11 150 307 83 38/5N 5 x ZF48 155 311 85
108/6P 6 x ZB75 132 244 73 28/6N 6 x ZF33 97 180 52
132/6P 6 x ZB92 150 294 82 42/6N 6 x ZF40 134 246 77
154/6P 6 x ZB11 180 337 99 45/6N 6 x ZF48 151 285 87

Attention: Idem = maximum start current with timer for cascade start-up of compressors. (The compressors do not all start at the same time).

Handling
When using a pallet truck or forklift tuck, the unit must be handled from the front (compressor side). Please refer to the associated commercial and/or software documentation for further details.

Appendix 1: Installation log sheet

Company:

Technician:

Date
Unit Suction pressure bar
Suction temperature oc
Delivery pressure bar
Power supply voltage (u, uv, uw) V
Cut-out value HP pressure switch bar
Cut-out value LP pressure switch bar
 

Compressor 1

Input amperage (u, v, w) A
Delivery temperature oc
Crankcase heater in good working order YIN
Oil level (full ¾ ½ ¼)
Compressor 2 Input amperage (u, v, w) A
Delivery temperature oc
Crankcase heater in good working order YIN
Oil level (full ¾ ½ ¼)
Compressor 3 Input amperage (u, v, w) A
Delivery temperature oc
Crankcase heater in good working order YIN
Oil level (full ¾ ½ ¼)
Compressor

4

Input amperage (u, v, w) A
Delivery temperature oc
Crankcase heater in good working order YIN
Oil level (full ¾ ½ ¼)
Compressor 5 Input amperage (u, v, w) A
Delivery temperature oC
Crankcase heater in good working order YIN
Oil level (full ¾ ½ ¼)
Compressor 6 Input amperage (u, v, w) A
Delivery temperature oC
Crankcase heater in good working order YIN
Oil level (full ¾ ½ ¼)
Refrigerant Circuit Presence of humidity YIN
Pump down working correctly YIN
Refrigerant safety devices working correctly YIN
Hoses in good state YIN
Circuit sealing YIN
Electrical

Cabinet

Connections properly tightened YIN
Electrical safety devices working correctly YIN

Appendix 2: Operating instructions for oil management system series “INT 280 -230V”

INT280 in the two mounting positionsFRIGA-BOHN-MOSC-Compressor-Rack-fig- (3) Dimensions in mmFRIGA-BOHN-MOSC-Compressor-Rack-fig- (4) Wiring diagram (suggestion)FRIGA-BOHN-MOSC-Compressor-Rack-fig- (5)

Application
The INT280 monitors and controls the oil level in the refrigerant compressors. In particular, the problem of poor oil distribution in multi-compressor packs is solved, thanks to active oil supply from a shared oil reservoir. The oil level regulator keeps the oil level at half the height of the sight glass.

Functional description
If the optical monitoring unit detects that the oil level is low, the integrated oil supply solenoid valve is activated by the electronics. Via the solenoid valve, oil is cyclically injected into the compressor crankcase. The INT280 generates an alarm signal and activates the relay output ifthe oil level is still too low after a defined period of time. During the “oil deficiency” alarm status, the electronics of the INT280 continue to operate the solenoid valve to inject oil into the crankcase. The alarm status is automatically reset if the oil level is at half the height ofthe sight glass.

LED status display

  • Level OK: Green is continuously lit
  • Filling: Green flashes
  • Oil level too low: Red is continuously lit
  • Internal error: Red flashes

Installation instructions

The user hæ to ensure that the image is properly tight. The eleariæl connætion to be carried out according to the wiring diagram. The unit must be connæted by traæd elEtrEal. All valid European and national standards for connæting dectri(Zlequipme-t must be observed.

Technical Specifications

Specification Details
Supply Voltage AC 24V 50/60Hz ±10%, 15VA
Supply Voltage AC 115V 50/60Hz ±10%, 15VA
Supply Voltage AC 230V 50/60Hz ±10%, 15VA
Permitted Ambient Temperature -30 to +60°C
Medium Temperature -30 to +100°C
Operating Pressure -1 to 46 bar
Differential Pressure 1 to 25 bar (across valve)
Relay AC 240V, 2.5A, C300
Mechanical Service Life Approx. 10⁶ switching cycles
Protection Class According to EN 60529 IP65
Connecting Cable 6 × AWG18 (0.75 mm²), Length 1 m
Housing Material Aluminium, PA66/PA6, Glass-Fibre-Reinforced
Flange Connection 3-/4-hole flange
Oil Connection 7/16″-20 UNF
Permitted Oils Standard mineral and ester oil, without additives
Permitted Refrigerants All non-corrosive standard refrigerants
Dimensions Refer to dimensions
Weight Approx. 950 g

Order Data

Supply Voltage Order Number
AC 24V 31 S 381
AC 115V 41 S 381
AC 230V 52 S 381

Appendix 3 : Operating instructions for level monitoring ” INT27SL ”

INT275 LFRIGA-BOHN-MOSC-Compressor-Rack-fig- (6) Connection diagramFRIGA-BOHN-MOSC-Compressor-Rack-fig- (7) Dimensions in mmFRIGA-BOHN-MOSC-Compressor-Rack-fig- (8)

Application
The optical sensor INT275 L is developed for contactless level monitoring of liquids. A screw-in part mounted at the required location and a removable electrical part perform this function. The electrical part can be fitted or removed without opening the liquid tank.  When the supply voltage is applied, the relay switches on after about 3s. In the absence of liquid or When a fault occurs, the relay trips after a delay. When liquid is present, or the fault disappears, the relay pulls in after a delay. The potential-free normally open contact can be directly wired in a control circuit without an additional auxiliary relay. An integrated self-monitoring circuit ensures high reliability. A mounting check eliminates wrong installation or manipulation.

Installation instruction

Mounting
The installer must ensure seal tightness for the application. The maximum tightening torque is approx. 75Nm. Clean the inside of the screw-in part as well as the prism. Fit the electrical part in the screw-in part and tighten the coupling ring (torque approx. I Nm), Pay attention to the position of the lead (cable exit downwards). Complete the electrical wiring in accordance with the attached circuit suggætions. After filling the tank, check the tightness of all joints.

Technical Data: Screw-In Part
Specification Details
Ambient Temperature Range -30 to +60°C
Max. Temperature at Prism +80°C
Test Pressure 32 bar
Housing VA 1.4510 or 1.4305
Mounting M20 × 1.5 mm, Wrench Size 24
Mounting NPT 1/2″, Wrench Size 24
Weight Approx. 75 g

Technical Data: Electrical Part

Specification Details
Supply Voltage (52S…) AC 230V, 50/60Hz ±10%
Supply Voltage (41S…) AC 115V, 50/60Hz ±10%
Ambient Temperature Range -30 to +60°C
Relay On After Supply Voltage On 3s ±1s
Relay Off (Low Level) After 5s ±2s
Relay Off (Fault) After 5s ±2s
Relay On (Level High Again) After 5s ±2s
Relay On (Fault Disappears) After 5s ±2s
Relay AC 250V, 2.5A, C300
Mechanical Service Life Approx. 10⁵ Switching Cycles
Housing Ultramid A3XZG5
Protection Class According to EN 60529 IP54 When Mounted
Mounting Coupling Ring on Screw-In Part
Connecting Cable 4 × AWG18 (0.75 mm²), Length 1 m, Colour-Coded
Weight Approx. 80 g

Ordering Information

Product / Version Order Number
230V Version: INT275 L Level Monitoring Electrical Part 52S475S60
115V Version: INT275 L Level Monitoring Electrical Part 41S475S60
Screw-In Part M20 × 1.5 mm 02K465
Screw-In Part NPT 1/2″ 02K460S22

The unit must be connected by trained electrical personnel. All valid standards for connecting electrical equipment must be observed. Limit values for the supply voltage of the unit may not be exceeded

  • LFB France
  • 42 rue Roger Salengro – 205
  • 69741 GENAS CEDEX – FRANCE
  • Tél. : +33 4 72 47 13 00 – Fax : +33 4 72 47 13 96
  • www.frigabohn.com
    FRIGA-BOHN-MOSC-Compressor-Rack-fig- (9)

Troubleshooting

  • INT280 (oil level regulator) — oil level still too low: The INT280 generates an alarm signal and activates the relay output if the oil level remains too low after a defined period of time. During the oil deficiency alarm status, the electronics continue operating the solenoid valve to inject oil into the crankcase. The alarm status automatically resets when the oil level reaches half the height of the sight glass.
  • INT280 LED status: Green continuously lit = Level OK. Green flashes = Filling. Red continuously lit = Oil level too low. Red flashes = Internal error.
  • INT275 L (level monitoring) — relay behavior: When there is absence of liquid or a fault occurs, the relay trips after a delay (relay off after 5 s±2 s). When liquid is present, or the fault disappears, the relay pulls in after a delay (relay on after 5 s±2 s). After supply voltage is applied, the relay switches on after about 3 s (3s±1s).

Documents / Resources

PDF thumbnailMOSC Compressor Rack
Installation Guide · Friga-Bohn, IN0008300-F, MOSC, Compressor rack, Installation instructions, MOSC Compressor Rack, Compressor Rack, Rack

References

Ask a Question

Use this section to ask about setup, compatibility, troubleshooting, or anything missing from this manual.

Ask a Question

Ask about setup, compatibility, troubleshooting, or anything missing from this manual. Name and email are optional.