All PAD detectors’ and modules’ addresses are set by changing the dip switches located on each device. An address must be set prior to connection.
PAD Addresses
PAD addresses are comprised of a seven (7) position dip switch used to program each device with an address ranging from 1–127. Refer to the table below to set dip switches on any PAD detector or module.
Qaphela: Ngamunye “gray” box indicates that the dip switch is “Vula,” futhi ngamunye “white” box kubonisa "Valiwe."
I-exampOkuboniswe ngezansi kubonisa izilungiselelo zokushintshwa kwediphu yedivayisi ye-PAD: i-1st exampi-le ibonisa idivayisi engabhekiwe lapho zonke izilungiselelo ze-dip switch zisendaweni ezenzakalelayo ethi "Valiwe", eyesibili ibonisa idivayisi ye-PAD enekheli ngezilungiselelo ze-dip switch.
- All dip switches are set to the default “OFF” position. (Device Not Addressed)
- Dip switches set for address 42. Switches #2, 8, & 32 are “ON”. (2+8+32=42)
- Dip switches set for address 90. Switches #2, 8, 16 & 64 are “ON”. (2+8+16+64=90)