WINDOW MASTER WCC 103 Motor Controller
Application
- Comfort ventilation
- Operating voltage
- ±24V DC actuators
- for daily comfort ventilation
- for controlling ±24V DC standard window actuators 1 comfort ventilation group at max. 3Amaybee combined with external temperature and time-automated BMS
MotorController for controlling ±24V DC standard actuators for daily comfort ventilation. It can also control locking actuators. The number of actuators that may be connected to the motor line depends on the type of actuator – see the table, “Maximum number of actuators per MotorController” for type/number.
Description
- The motor controller controls (opens/closes) the
- window actuators based on a signal from the connected component(s) e.g. comfort keypad (operating keypad), room sensor,s, and weather sensors.
- We recommend connecting the comforkeypadsad when sensors and other operators are connected so that users always, via the comfort keypads, can override the signals and open or close windows themselves should there be a need for more or less fresh air.
- Up to motor controllers can be connected as part of a larger solution and may be connected to the same weather station. Several MotorControllers may be operated from the same comfort keypad.
- The MotorController is also supplied with 3A and 6A versions which can be controlled from a remote control or app.
Prioritised inputs
- The actuators may be overridden via three prioritized inputs.
- All switches must be potential-free.
- common CLOSE ALL/safety (rain) function (highest priority)
- hand operation of the motor line
- automated control of the motor line (lowest priority)
Power supply for external units
When connecting sensors the auxiliary power from the built-in 24V DC 500mA power supply can be used.
Configuration
Via a DIP switch, it can be configured if there should be maintained action on the connected comfort keypads.
Specifications
- 1 motor group with up to 3A in total
- Max output voltage 24VDC at 230VAC
- simple and quick installation
- up to 10 MotorControllers may be linked
- rain/wind sensors can be connected
- 3 prioritised inputs
Themotor controller may either be mounted horizontally or vertically on a wall.
Example 1: WCC 103 with timer control and wind/rain sensor
In the room 1 pcs. ±24V standard actuator is connected as well as comfort keypads fo the r individual operation of the window. A timer control is fitted that opens/closes the windows in the room at preset times, e.g. open and close at the start and end of a lunch break and “close all” at the end of the day. A wind/rain sensor is mounted on the roof.
Example 2: WCC 103 with NV Solo®
In the room 2 pcs. ±24V standard actuators are connected. An NV Solo® control panel with a built-in temperature sensor and a comfort keypad for the individual operation of the actuators is installed. An NV Solo® weather sensor is mounted on the roof which gives signals to the NV Solo® control panel in the room.
Technical specifications | ||
Output current | 3A incl. load on X7 (max 0.5A) | |
Motor lines | 1 x ±24V standard motor line | |
PrimaryVoltagee | 100-240 VAC 0.85A 50/60Hz | |
Actuator secondary voltage | Nominal voltage Open circuit voltage at 230V AC (no load) Ripple at max load | 24V DC (±15%) 24V DC @ 20°C 150mVp-p |
Power consumption | Idling < 0.5W Max load 77 W | |
Leakage current | max 0.75mA @240VAC | |
Inrush current on the primary side | 65A < 5ms v. 230V Max. 6 x WCC 103 per 10A power supply group. Circuit breaker “C” characteristic. | |
AUX | 24V DC, 500mA | |
Operating conditions | -5°C – +45°C, for indoor installation, the controller may not be covered | |
Switch-on duration | ED 40% (4 min. per 10 min.) | |
Connection cable | Actuators Flexible max 6mm² / solid max 10mm², max 2V voltage drop. Other components Min 0.2mm² / max 1.5mm² | |
Size | 215 x 206 x 37mm (W x H x D) | |
Material | Plastic | |
Color | White (RAL 9016) | |
Weight | 0.92kg | |
IP rating | IP20 | |
Safety class | I (with PE) | |
Delivery includes | MotorController with 1.2 m cable with Schuko plug UK version supplied with UK network adapter. | |
Note | We reserve the right to make technical changes |
Max number of actuators per MotorController
The following table shows the maximum number of actuators, based on actuator type (±24V standard ) that can be connected to the motor controller. Total power consumption for all connected actuators may not exceed 3A.
Actuator type | Max. number ±24V actuators that may be connected to WCC 103 |
WMD 820-1 | 3 |
WMD 820-2 | 2 |
WMD 820-3 | 3 |
WMS 306 / 309-1 | 3 |
WMS 306 / 309-2 | 2 |
WMS 306 / 309-3 | 3 |
WMS 409 xxxx 01 | 1 |
WMS 409-1 | 1 |
WMU 831 / 851-1 | 3 |
WMU 831 / 851-2 | 2 |
WMU 831 / 851-3 | 3 |
WMU 836-1 | 2 |
WMU 836-2 | 2 |
WMU 852-1 | 1 |
WMU 861-1 | 2 |
WMU 861-2 | 2 |
WMU 842 / 862 / 882-1 | 1 |
WMU 863 / 883-1 | 1 |
WMX 503 / 504 / 523 / 526-1 | 6 |
WMX 503 / 504 / 523 / 526-2 | 6 |
WMX 503 / 504 / 523 / 526-3 | 6 |
WMX 503 / 504 / 523 / 526-4 | 4 |
WMX 803 / 804 / 813 / 814 / 823 / 826-1 | 3 |
WMX 803 / 804 / 813 / 814 / 823 / 826-2 | 2 |
WMX 803 / 804 / 813 / 814 / 823 / 826-3 | 3 |
WML 820 / 825 | 3 |
WML 860-1 | 3 |
WML 860-2 | 2 |
WML 860-3 | 3 |
WMB 801 / 802 | 3 |
WMB 811 / 812 / 815/ 816 / 817 / 818 * | 2 |
* When having two locking actuators on one motor line use: 1 x WMB 811 and 1 x WMB 812, 1 x WMB 815 and 1 x WMB 81,6, or 1 x WMB 817 and 1 x WMB 818 |
motor controller
Variants | Item number |
MotorController 3A | WCC 103 010x |
MotorController 3A, UK version | WCC 103 040x
|
Accessories | Item number |
Comfort keypad, for fitting | WSK 100 1161 |
Comfort keypad, 1 window or 1 window group | WSK 110 0A0B |
Comfort keypad, for fitting (CH version) | WSK 300 |
Room thermostat: temperature | WLA 110 |
Wind/rain sensor | WLA 330 |
Rain sensor | WLA 331 |
- ©WindowMaster 2020, 2023 ®WindowMaster is a registered trademark used under license from WindowMaster International
- windowmaster.com
Documents / Resources