Zennio ZPDEZTPV2 EyeZen TP v2 Motion Detector with Luminosity Sensor for Ceiling Mounting

INTRODUCTION

EYEZEN TP V2

EyeZen TP v2 from Zennio is a device that aims at, among other functions, the detection of motion, the measurement and control of the room luminosity and the detection of occupancy within the room where it has been installed. It has been designed for ceiling or false ceiling mounting by means of the bundled accessories.

The most outstanding features of EyeZen TP v2 are:

  • Sensor with configurable sensitivity.
  • LED to indicate motion.
  • Two colours of lenses: white and black.
  • Motion detection:
    ➢ 6 motion detection channels.
    ➢ Luminosity-dependent motion detection (optional).
    ➢ Periodic and delayed sendings (binary, scene, HVAC, percentage).
  • Occupancy detection:
    ➢ 1x occupancy detection channel.
    ➢ Master / slave configuration.
    ➢ Trigger upon door opening or closing.
    ➢ Periodic and delayed sendings (binary, scene, HVAC, percentage).
  • Luminosity measurement:
    ➢ Configurable correction factor and offset.
    ➢ Periodic sending or upon value change.
  • 2 constant light control channels with configurable setpoints.
  • Day / night configuration.
  • 10 customisable, multi-operation logic functions.
  • Heartbeat or periodical “still alive” notification
INSTALLATION

EyeZen TP v2 connects to the KNX bus through the on-board KNX connector.
Once the device is provided with power from the KNX bus, both the individual address and the associated application program may be downloaded.
This device does not need any additional external power since it is entirely powered through the KNX bus.

  1. Detection LED indicator.
  2. Retaining spring.
  3. Test/Prog. button.
  4. Test/Prog. LED.
  5. KNX connector.

The main elements of the device are described next.

  • Programming button (3): a short press on this button sets the device into the programming mode, making the associated LED (4) light in red.
    Note: if this button is held while plugging the device into the KNX bus, the device will enter the safe mode. In such case, the LED will blink in red every 0.5 seconds.
  • Detection notification LED (1): emits a red light flash when the sensor observes motion.

To get detailed information about the technical features of this device, as well as on the installation process and on security procedures, please refer to the corresponding Datasheet, bundled with the original packaging of the device and also available at www.zennio.com.

START-UP AND POWER LOSS

During the start-up of the device, the detection notification LED flashes red for one minute before the motion sensor is ready.
Depending on the configuration, some specific actions will also be performed during the start-up. For example, the integrator can set whether the detection channels should start up enabled or disabled.

CONFIGURATION

GENERAL

After importing the corresponding database in ETS and adding the device into the topology of the desired project, the configuration process begins by entering the parameters tab of the device.

ETS PARAMETERISATION

From General screen it is possible to activate/deactivate all the required functionality.

  • Lens Color [White / Black] 1: parameter to select the lens colour that EyeZen TP v2 has installed, for correct sensor luminosity measurement.
  • Motion Detection [enabled]: enables the “Motion Detector” tab in the tree on the left. For more information, see section 2.2.
  • Logic Functions [enabled/disabled] enables or disables the “Logic Functions” tab in the tree on the left. For more information, see section 2.3.
  • Heartbeat (Periodic Alive Notification) [enabled/disabled]: incorporates a one-bit object to the project (“[Heartbeat] Object to Send ‘1’”) that will be sent periodically with a value of “1” to notify that the device is still working (still alive).

1 The default values of each parameter will be highlighted in blue in this document, as follows: [default/rest of options].

Note: the first sending after download or bus failure takes place with a delay of up to 255 seconds, to prevent bus overload. The following sendings match the period set.

  • Device Recovery Objects (Send 0 and 1) [enabled/disabled]: this parameter lets the integrator activate two new communication objects (“[Heartbeat] Device Recovery”), which will be sent to the KNX bus with values “0” and “1” whenever the device begins operation (for example, after a bus power failure). It is possible to parameterise a certain delay [0…255][s] to this sending.

Note: after download or bus failure, the sending takes place with a delay of up to 6,35 seconds plus the parameterised delay, to prevent bus overload.

MOTION DETECTOR

EyeZen TP v2 incorporates six independent motion detection channels, two more for constant light control and one for occupancy detection.

  • Motion detection consists in sending objects to the bus whenever the device observes a moving body (or no longer observes it) in the environment of the room where it has been installed.
  • Constant light control consists in sending KNX orders to the dimmer device that controls the in-room luminaries so the ambient light level remains constant even if other light sources are present.
  • Occupancy detection is an algorithm that allows determining whether a particular space is under occupation no matter if the occupant moves or not (i.e., no matter if the device is detecting motion in the room or not).

It also allows setting different luminosity setpoints or object types for daytime and night time as well as activating or deactivating the motion indicator LEDs.
EyeZen TP v2 can also set custom sensitivity of the motion sensor and measure the luminosity of the room by making certain adjustments. This measurement will be made according to the color of lens selected.
Please refer to the specific manual “Presence Detector” available in EyeZen TP v2 product section at the Zennio website (www.zennio.com) for detailed information about the functionality and the configuration of the related parameters. Please note that references to presence detection in this manual in this case correspond to motion detection.

LOGIC FUNCTIONS

This module makes it possible to perform numeric and binary operations to incoming values received from the KNX bus, and to send the results through other communication objects specifically enabled for this purpose.
EyeZen TP v2 can implement up to 10 different and independent functions, each of them entirely customisable and consisting of up to 4 consecutive operations.

The execution of each function can depend on a configurable condition, which will be evaluated every time the function is triggered through specific, parameterisable communication objects. The result after executing the operations of the function can also be evaluated according to certain conditions and afterwards sent (or not) to the KNX bus, which can be done every time the function is executed, periodically or only when the result differs from the last one.

Please refer to the “Logic Functions” user manual available under the EyeZen TP v2 product section at the Zennio homepage (www.zennio.com) for detailed information about the functionality and the configuration of the related parameters.

ANNEX I. COMMUNICATION OBJECTS

Functional range” shows the values that, with independence of any other values permitted by the bus according to the object size, may be of any use or have a particular meaning because of the specifications or restrictions from both the KNX standard or the application program itself.

NumberSizeI/OFlagsData type (DPT)Functional RangeNameFunction
11 BitC – – T –DPT_Trigger0/1[Heartbeat] Object to Send ‘1’Sending of ‘1’ Periodically
21 BitC – – T –DPT_Trigger0/1[Heartbeat] Device RecoverySend 0
31 BitC – – T –DPT_Trigger0/1[Heartbeat] Device RecoverySend 1
41 ByteIC – W – –DPT_SceneNumber0 – 63Scene InputScene Value
51 ByteC – – T –DPT_SceneControl0-63; 128-191Scene OutputScene Value
62 BytesI/OC R W – –DPT_Coefficient0 – 100Correction Factor – Internal Sensor[0, 80] x0.1
72 BytesI/OC R W – –1.xxx0/1Offset – Internal Sensor[-200, 200] Luxes
82 BytesOC R – T –DPT_Value_LuxLuminosity – Internal SensorLuxes
121 BitIC – W – –DPT_DayNight0/1Day/Night0 = Day; 1 = Night
1 BitIC – W – –DPT_DayNight0/1Day/Night0 = Night; 1 = Day
131 BitIC – W – –DPT_Enable0/1Detection LED0 = Disable; 1 = Enable
1 BitIC – W – –DPT_Enable0/1Detection LED0 = Disable; 1 = Enable Only During the Day
141 BitOC R – T –DPT_Switch0/1Occupancy: Output (Binary)Binary Value
1 BitC – – T –DPT_Start0/1Occupancy: Slave Output1 = Motion Detected
151 ByteOC R – T –DPT_Scaling0% – 100%Occupancy: Output (Scaling)0-100%
161 ByteOC R – T –DPT_HVACMode1=Comfort 2=Standby 3=Economy 4=Building ProtectionOccupancy: Output (HVAC)Auto, Comfort, Standby, Economy, Building Protection
171 BitIC – W – –DPT_Window_Door0/1Occupancy: TriggerBinary Value to Trigger the Occupancy Detection
181 BitIC – W – –DPT_Start0/1Occupancy: Slave Input1 = Detection from slave device
192 BytesIC – W – –DPT_TimePeriodSec0 – 65535Occupancy: Waiting Time0-65535 s.
202 BytesIC – W – –DPT_TimePeriodSec0 – 65535Occupancy: Listening Time1-65535 s.
211 BitIC – W – –DPT_Enable0/1Occupancy: Lock0 = Unlock; 1 = Lock
1 BitIC – W – –DPT_Enable0/1Occupancy: Lock0 = Lock; 1 = Unlock
221 BitOC R – T –DPT_Occupancy0/1Occupancy: Occupancy State0 = Not Occupied; 1 = Occupied
231 ByteIC – W – –DPT_Scaling0% – 100%Sensor Sensitivity1-100%
27, 36, 45, 54, 63, 721 BitIC – W – –DPT_Start0/1[Cx] External Motion Detection1 = Motion detected by an external sensor
28, 37, 46, 55, 64, 731 BitOC R – T –DPT_Switch0/1[Cx] Output (Binary)Binary Value
29, 38, 47, 56, 65, 741 ByteOC R – T –DPT_Scaling0% – 100%[Cx] Output (Scaling)0-100%
30, 39, 48, 57, 66, 751 ByteOC R – T – 

 

DPT_HVACMode

1=Comfort 2=Standby 3=Economy 4=Building Protection[Cx] Output (HVAC)Auto, Comfort, Standby, Economy, Building Protection
31, 40, 49, 58, 67, 761 BitIC – W – –DPT_Enable0/1[Cx] Lock Status0 = Unlock; 1 = Lock
1 BitIC – W – –DPT_Enable0/1[Cx] Lock Status0 = Lock; 1 = Unlock
32, 41, 50, 59, 68, 771 BitIC – W – –DPT_Start0/1[Cx] Force State0 = No Detection; 1 = Detection
33, 42, 51, 60, 69, 781 BitIC – W – –DPT_Start0/1[Cx] External Switch0 = No Detection; 1 = Detection
34, 43, 52, 61, 70, 792 BytesI/OC R W – –DPT_TimePeriodSec0 – 65535[Cx] Length of Detection1-65535 s.
81, 971 BitIC – W – –DPT_Start0/1[CLCx] External Motion Detection1 = Motion detected by an external sensor
82, 981 BitIC – W – –DPT_Enable0/1[CLCx] Lock Status0 = Unlock; 1 = Lock
1 BitIC – W – –DPT_Enable0/1[CLCx] Lock Status0 = Lock; 1 = Unlock
83, 991 BitIC – W – –DPT_Start0/1[CLCx] Force State0 = No Detection; 1 = Detection
84, 1001 BitIC – W – –DPT_Start0/1[CLCx] External Switch0 = No Detection; 1 = Detection
 

85, 101

2 BytesIC – W – –DPT_Value_Lux[CLCx] SetpointSetpoint Value (1-2000)
2 BytesIC – W – –DPT_Value_Lux[CLCx] Setpoint During DaySetpoint Value (1-2000)
1 ByteIC – W – –DPT_Scaling0% – 100%[CLCx] SetpointSetpoint Value (1-100)%
1 ByteIC – W – –DPT_Scaling0% – 100%[CLCx] Setpoint During DaySetpoint Value (1-100)%
86, 1022 BytesIC – W – –DPT_Value_Lux[CLCx] Setpoint During NightSetpoint Value (1-2000)
1 ByteIC – W – –DPT_Scaling0% – 100%[CLCx] Setpoint During NightSetpoint Value (1-100)%
87, 1031 ByteOC R – T –DPT_Scaling0% – 100%[CLCx] Dimming ValueDimming Value (%)
88, 1042 BytesI/OC R W – –DPT_TimePeriodSec0 – 65535[CLCx] Length of Detection1-65535 s.
90, 1061 BitIC – W – –DPT_Switch0/1[CLCx] Manual Control: On/Off (Input)1-Bit Control
91, 1074 BitIC – W – –DPT_Control_Dimming0x0 (Stop)

0x1 (Dec. by 100%)

0x7 (Dec. by 1%) 0x8 (Stop)

0xD (Inc. by 100%)

0xF (Inc. by 1%)

[CLCx] Manual Control: Relative Dimming (Input)4-Bit Control
92, 1081 ByteIC – W – –DPT_Scaling0% – 100%[CLCx] Manual Control: Absolute Dimming (Input)1-Byte Control
93, 1091 BitOC R – T –DPT_Switch0/1[CLCx] Manual Control: On/Off (Output)1-Bit Control
94, 1104 BitOC R – T –DPT_Control_Dimming0x0 (Stop)

0x1 (Dec. by 100%)

0x7 (Dec. by 1%) 0x8 (Stop)

0xD (Inc. by 100%)

0xF (Inc. by 1%)

[CLCx] Manual Control: Relative Dimming (Output)4-Bit Control
95, 1111 BitIC – W – –DPT_Enable0/1[CLCx] Manual Control0 = Disable; 1 = Enable
96, 1121 BitOC R – T –DPT_Enable0/1[CLCx] Manual Control (Status)0 = Disabled; 1 = Enabled
113, 114, 115, 116, 117, 118,

119, 120, 121, 122, 123, 124,

125, 126, 127, 128, 129, 130,

131, 132, 133, 134, 135, 136,

137, 138, 139, 140, 141, 142,

143, 144

 

1 Bit

 

I

 

 C – W – –

 

DPT_Bool

 

0/1

  [LF] (1-Bit) Data Entry x 

Binary Data Entry (0/1)

145, 146, 147, 148, 149, 150,

151, 152, 153, 154, 155, 156,

157, 158, 159, 160

1 ByteI C – W – –DPT_Value_1_Ucount0 – 255[LF] (1-Byte) Data Entry x1-Byte Data Entry (0-255)
161, 162, 163, 164, 165, 166,

167, 168, 169, 170, 171, 172,

173, 174, 175, 176

2 BytesIC – W – –DPT_Value_2_Ucount0 – 65535[LF] (2-Byte) Data Entry x2-Byte Data Entry
177, 178, 179, 180, 181, 182,

183, 184

4 BytesIC – W – –DPT_Value_4_Count-2147483648 –

2147483647

[LF] (4-Byte) Data Entry x4-Byte Data Entry
185, 186, 187, 188, 189, 190, 191, 192, 193, 1941 BitOC R – T –DPT_Bool0/1[LF] Function x – Result(1-Bit) Boolean
1 ByteOC R – T –DPT_Value_1_Ucount0 – 255[LF] Function x – Result(1-Byte) Unsigned
2 BytesOC R – T –DPT_Value_2_Ucount0 – 65535[LF] Function x – Result(2-Byte) Unsigned
4 BytesOC R – T –DPT_Value_4_Count-2147483648 –

2147483647

[LF] Function x – Result(4-Byte) Signed
1 ByteOC R – T –DPT_Scaling0% – 100%[LF] Function x – Result(1-Byte) Percentage
2 BytesOC R – T –DPT_Value_2_Count-32768 – 32767[LF] Function x – Result(2-Byte) Signed
2 BytesOC R – T –9.xxx-671088.64 – 670433.28[LF] Function x – Result(2-Byte) Float

Join and send us your inquiries about Zennio devices:
https://support.zennio.com

Customer Support

Zennio Avance y Tecnología S.L.
C/ Río Jarama, 132. Nave P-8.11
45007 Toledo (Spain).
Tel. +34 925 232 002.
www.zennio.com