Mahsulot haqida ma'lumot

Texnik xususiyatlari

  • Model: O2 Sensor Kit Mk9
  • Quvvat manbai: 24Vdc
  • Joriy iste'mol: 38mA
  • Kelib chiqqan mamlakati: Shvetsiya

AZOT GENERATORLARI
E'tibor bering, agar O2 sensori o'rnatilgan hududda azot generatori ishlatilsa, azot generatori tomonidan yaratilgan ortiqcha kislorod maydondan tashqariga chiqarilishi kerak. Kislorod tashqariga chiqarilmasa, hududda O2 sensoridan foydalanishga yo'l qo'yilmaydi.

Kalibrlash

LogiCO2 O2 sensori standart sifatida faollashtirilgan avtomatik kalibrlash funksiyasiga ega va normal sharoitda qo‘lda kalibrlash kerak bo‘lmaydi.

O'rnatish balandligi

O2 sensori nafas olish balandligida, poldan 150-180 sm / 5-6 fut oralig'ida o'rnatilishi kerak.
Try to find an installation position where the unit is least likely to be damaged. Mount the O2 sensor with supplied mounting screws. The horn/strobe/s must be installed on the wall above the O2 sensor, approximately 2-2.4 m/80-96 inches (as per NFPA 72) above the floor, clearly visible from any entrance of the area being monitored.

LogiCO2-O2-Mk9-Detector-Sensor- (1)

Yo'laklar
In areas where the Nitrogen or mixed gas are stored at the end of a corridor, it is paramount to place an extra Horn Strobe at the entrance of the corridor. This to give an early warning in case of a Oxygen depletion.

LogiCO2-O2-Mk9-Detector-Sensor- (2)

Lower floor/basement
In areas where the Nitrogen or mixed gas is stored or distributed in Below Grade locations such as Lower Floors and Basements, it is essential to have Horn Strobes before the entrance to the area.

LogiCO2-O2-Mk9-Detector-Sensor- (3)

Enclosed Spaces
In enclosed spaces Horn Strobes must be placed outside of each entrance.

LogiCO2-O2-Mk9-Detector-Sensor- (7)

Tizimni o'rnatish

LogiCO2-O2-Mk9-Detector-Sensor- (4)

Installing an O2-kit to an existing LogiCO2 Mk9 CO2 Safety System
Since you are adding an additional sensor to the system, you need to set the correct ID-settings for the sensors and the central unit. This is done using the dip switches.
The O2 sensor in the kit is set to ID2 as standard, if you only have one CO2 sensor connected in the sys-tem, you only need to change a dip switch in the central unit. Unscrew the screws and remove the lid of the central unit. Then put dip 1 in the ON position.
If you have 2 or more sensors already connected in the alarm system, please check the User´s manual.

LogiCO2-O2-Mk9-Detector-Sensor- (5)

O'rnatish sxemalari

LogiCO2-O2-Mk9-Detector-Sensor- (6)

LogiCO2 International • P.B. 9097 • 400 92 Gothenburg • Sweden www.logico2.cominfo@logico2.com

Tez-tez so'raladigan savollar (FAQ)

  • Q: Do I need to manually calibrate the O2 sensor?
    A: No, the O2 sensor has an automatic self-calibration function and does not require manual calibration under normal conditions.
  • Q: What is the recommended installation height for the O2 sensor?
    A: O2 sensori nafas olish balandligida, poldan 150-180 sm / 5-6 fut oralig'ida o'rnatilishi kerak.
  • Q: How do I add an O2 sensor to an existing LogiCO2 Mk9 CO2 Safety System?
    A: To add an O2 sensor, set the correct ID-settings for the sensors and central unit using dip switches. The O2 sensor in the kit is set to ID2 as standard.