Apr 3, 2025 — this or any other appliance. WHAT TO DO IF YOU SMELL GAS. • Do not try to light any appliance. • Do not touch any electrical switch; do not.


File Info : application/pdf, 12 Pages, 3.01MB

PDF preview unavailable. Download the PDF instead.

1511 Current
User's Manual

User's Manual for

Document 1511

Floor Standing, Modulating Gas, Condensing, Heating Only Boiler
Model FTHF199N
199,000 BTU/h

· · Propane Gas (LP) - Field-Convertible

FOR YOUR SAFETY: This product must be installed and serviced by a professional service technician,

death. Improper installation and/or operation will void the warranty.

, property damage, or

WARNING If the information in this manual is not
result causing property damage, personal injury or loss of life.
Do not store or use gasoline or other
this or any other appliance. WHAT TO DO IF YOU SMELL GAS
· Do not try to light any appliance. · Do not touch any electrical switch; do not
use any phone in your building. · Immediately call your gas supplier from a
nearby phone. Follow the gas supplier's instructions. · If you cannot reach your gas supplier, call
Installation and service must be performed
supplier.

AVERTISSEMENT Assurez-vous de bien suivres les instructions données dans cette notice pour réduire au minimum le risque d'incendie ou d'explosion ou pour éviter tout dommage matériel, toute blessure ou la mort.
Ne pas entreposer ni utiliser d'essence ou ni
le à proximité de cet appareil ou de tout autre appareil.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:
· Ne pas tenter d'allumer d'appareils. · Ne touchez à aucun interrupteur. Ne pas vous servir
des téléphones dans le bâtiment où vous vous trovez. · Appelez immédiatement votre fournisseur de gaz depuis un voisin. Suivez les instructions du fournisseur. · Si vous ne pouvez rejoindre le fournisseur de gaz, appelez le sservice des incendies. L'installation et l'entretien doivent être assurés par
ou par le fournisseur de gaz.

H2420000-

Page 2

CONTENTS

Pgs -

1. Familiarizing yourself with the FT ..........................2

2. Caring For Your FT ................................................ 4

3. Start Up and Shut Down. ...................................... 4

4. Control Display and Operation .........................5-10

1. Familiarizing yourself to
THE FT

The FT is a floor standing, condensing and fully modulating, residential boiler.

This Users Manual will guide you into the basics of operating your FT

Please reference the Installation and Operation

Manual for complete details

).

User's Manual - The FT Series Floor Standing, Heating Only Boiler

Page 3

1.1 Names of Components

7

65 4

8 9 10 11 12 13 14 15 16 17
18 19 20

# Name of Component

1 Pressure Relief Valve

2 Air Vent (air eliminator)

3 Boiler Return Connection

4 Boiler Supply Connection

5 Vent Pipe Collar

2

6 Boiler Pressure Gauge

7 Air Intake Collar 1
8 Gas Inlet Adapter

3

9 Air/ Gas Venturi

30

10 Gas Valve

29

11 BLDC Fan (Blower)

12 Low Water Cut Off 28
13 Burner High Limit Switch

27

14 Flame Detecting Sensor

26

15 Manual Power Switch (ON / OFF)

16 Heat Exchanger

25

17 Main PCB

24

18 Boiler Pump

19 Blocked Condensate Switch

20 Condensate Trap

23

21

Condensate neutralizer and Drain pump (optional equipment)

22 Drain Valve

23 Low Loss Header

24 Terminal Block

25 Overheat Temperature Sensor

26 Sight Glass

22

27 Igniter

21

28 Exhaust Pipe

29 Control Panel and Display

30 Air Pressure Sensor

Page 4

2. Caring For Your FT
Your FT will require very little maintenance. However, as with any fine appliance there are certain steps that should be taken to ensure continuing optimum performance.
2.1 General Care
Keep the area around the FT clean and free from combustible materials, gasoline and other flammable liquids and vapors.
The FT must be completely isolated and protected from any source of corrosive chemical fumes such as trichlorethylene, perchlorethylene, chlorine, etc.
Keep bottom and top openings on the boiler free for proper ventilation of interior components.
Do not obstruct or block a free flow of air to the boiler to ensure proper ventilation.
If desired, clean the jacket surfaces with a damp cloth and mild detergent. Do not use flammable cleaning materials.
If sidewall vented, keep the vent terminal clear of obstructions -- do not allow snow to cover the vent terminal. Clean the intake screen often, and then develop an appropriate maintenance schedule.

2.2 Annual Inspection of Flue and Vents
Visually inspect the vent pipe once a year. Should any deterioration exist, have the affected parts replaced by a qualified service person.
2.3 In the Event of a Power Failure
The FT can not be operated during an electrical power outage. If there is an extended power outage with danger from freezing, then the FT (and all other water systems) should be drained completely. When draining the boiler, turn off main electrical disconnect switch. When placing back in service, refer to Section 3 of this Manual for instruction. All draining and filling must only be done by a qualified service person.
2.4 Full Service Every Year
In addition to the annual visual inspections, a qualified service agency should conduct a detailed inspection of all flue product carrying areas of the boiler and its venting system.

3. Shut Down and Restart
3.1 To Start the FT
If drained, please refer to the Install and Operating Manual to ensure that the complete `Setup' procedure has been followed before starting this boiler. A complete `Setup' must be performed by a qualified service person.

3.2 Shutting Down the FT
1. Turn off the main electrical disconnect switch. 2. Close all manual gas valves. 3. If freezing is anticipated, drain the FT and be
sure to also protect building piping from freezing. All water must be removed from heat exchanger and condensate trap or else damage from
freezing may occur. Please refer to the Install and Operating Manual. This step to be performed by a qualified service person.

User's Manual - The FT Series Floor Standing, Heating Only Boiler
4. The ControlCDoisnptrloayl DainsdplOaypeanradtiOonperation
The Control Display

Page 5

B

C

E

Status Light

A

D

(constant green when operating

normally)

The Control Display has a Control Dial (E), 4 buttons (A, B, C, D), and a Liquid Crystal Display (with 72 back-lit segments). This section of this manual gives instruction on how to navigate into the many functions of the FT and to change temperature set points, set system variables and controller parameters.

Buttons

PRESS (Tap)

Functionality PRESS and HOLD (5 seconds)

A

Display Power Turns Control Display ON/OFF

B

Modes

Tap to return to menu

(If Display Power was On ) Status Display Mode (If Display Power was Off ) Installer Mode

C

Heating Water

CH set-point change mode (Maxium 82°C(180°F))

D

Time / Date Set

No Change

To SET: Year/Month/Week/Day/Time/Min

E

Scroll / Select

Menu select or value up(+)/down(-) or setting dial.

· Temperature Specifications Operating ambient Temperature Range : -10 to 60°C. Operating Relative Humidity up to: 90% at 40°C. Shipping & Storage Temperature Range of : -20 to 80°C.

water. Immediately call a qualified service technician been under water.

Page 6
4. The Control Display and Operation (continued) LCD Overview

Symbol

Name

Description

Service Reminder mode

Service Reminder mode indication

Outside Temperature Mode Anti-freeze mode Storage mode

Outside Temp setting indication Anti-freeze mode indication Storage mode indication

Information mode Communication state
Time setting mode

Information mode indication Communication state indication Time /Dispaly/Install mode indication

Fan operating mode

Fan operating mode indication

Flame signal CH pump mode Storage pump mode Internal boiler pump Celsius mode Fahrenheit mode Heat demand mode

Flame Signal indication CH pump mode indication Storage pump mode indication Internal Boiler pump mode indication Indicated as Celsius temperature Indicated as Fahrenheit temperature Heat demand mode indication

DAY mode Cascade System connecting
mode
Cascade System operating mode

Current day mode indication
Cascade System connecting mode indication
Cascade System operating mode indication

The LCD will illuminate when a user action is detected (a button is pressed) and will turn back off after 20 seconds.

User's Manual - The FT Series Floor Standing, Heating Only Boiler
5.3 Operating Mode
Operating Mode After the Power is turned on, and/or the Control Display is turned on , the Control Display will go through a `Start Up' checklist and briefly show a sequence of diagnostic codes before entering into the `Operating Mode. It will then display the following information.

Page 7

B

C

E

A

D

Indicate Current Operating Temperature Set-Point

Indicator

If the Fan is operating

If a flame is detected

Celsius or Fahrenheit

or

Date and Time indicator

If Outside Temperature Sensor is operating

If there is a Demand for Central Heat (CH)

If CH pump state is operating If Internal recirculation pump is operating If Communication state is activated

The Control Display can operate through user and service modes that have specific LCD output and dedicated controls: · Set-point change mode · Lock mode · Error mode · Status display mode · Outside Temperature mode · Installer mode
* Control Display will not allow changing of button in case of lock mode activated.

Page 8
5.4 Setting the Clock

B

C

E

A

D

The P-950EH Control Display does NOT have a daily timer or programmable thermostat.

Setting the Clock

a. Press and hold the

`Clock button' for about 5 seconds. Set the `Year' by turning the dial E. And

then, press the dial E to Save.

b. Set the `MON' (Month) by turning the dial E to the desired month number. Then press the dial E to Save.

c. Set the `DATE' (1-31, Day of the Month) by turning the dial E. Then press the dial E to Save.

d. Set the `HOUR' (1-24, Hour of the Day) by turning the dial E. Then press the dial E to Save.

e. Set the `MIN' (1-60, Minute of the Hour) by turning the dial E. Then press the dial E to Save.

f. Set the `Day' (Sun - Sat) by turning the dial E. Then press the dial E to Save.

To Exit at any time, tap the

button.

User's Manual - The FT Series Floor Standing, Heating Only Boiler
5.5 CH Set Point Change Mode CH Set point Change Mode

Page 9

B

C

E

A

D

To change CH Setpoint, press the C

button. The CH Icon and current

CH Setpoint will flash.

Turn the E dial clockwise to increase, and counterclockwise to decrease CH setpoint, until

desired temperature is reached.

Press E dial to save changes and to Exit.

Indicate Current CH Temperature Set-Point
Celsius or Fahrenheit If Communication state is activated If flame is detected Date and Time indicator If CH pump is operating If there currently a Demand for Central Heat (CH)

Indicator or

Default CH set-point is 140°F (60°C) CH set-point range is 130°F ~180°F (54°C ~ 82°C)

Page 10
5.6 Status Display Mode
To view any Status Parameter,
Press and Hold Button B to get into the Status Display Mode. Rotate Dial E until you find the Parameter that you wish to view. Tap Dial E to enter that Parameter as required. Dial E to save and to exit the Status Information Menu. To go back to the Operation Screen Press button B.

B

C

E

A

D

NOTE: For Cascading Installations, please refer to document 1349 `Cascading
the FT Series Boiler', available online.

Digital Display O: ot A: In

Status Display Parameter Outdoor temperature 0-10 V display

b: tt

CH target temperature in cascade system

C: It d: Fr

CH return water temperature FAN speed ( rpm)

Description Current outdoor sensor temperature Current voltage of (0-10V input) Current CH target temperature or Current System target temperature in a cascade system Current CH return water temperature Current FAN speed ( RPM)

E: oP F: Eh

CH supply temperature (Operating temperature) Current heating temperature

Exhaust gas temperature

Current exhaust gas temperature

H: dH

Indirect DHW tank temperature * If temperature sensor is not connected then it will display with 0°F (0°C).

Current DHW tank temperature

I: oH 1: PH 2: rh

L: rt

3: rH 4: It

5: IH

Overheat water temperature

Burner Operation Time

Time for supply power Time for burner operation Time for burner operation
Cycle for ignition

Cycle for ignition

Current Overheat water temperature Unit : 1000hour Unit : 1hour

L: rt on display on sub menu

Unit : 1,000hour
Cycle : 10 times the displayed unit
Cycle : 10,000 times the displayed unit

SELF Percentage of self units running. Percentage of self units running.

M: ALL CC

Capacity for all operating cascade units

Percentage of all cascade units running. This screen shows the overal cascade power output. The range of this value of boilers communicating with theMaster x 100. For example, if 8 boilers are connected and communicating, the maximum cascade power is 800%. Range: 0-100%

F1 ­ F 19
N: St

Capacity for individual boilers
System Temperature (cascade mode) * If system temperature sensor is not connected then it will display with 0°F (0°C).

Percentage of each cascade units running. Ex. F1, F2, ....
Current System Temperature (cascade mode)

User's Manual - The FT Series Floor Standing, Heating Only Boiler Notes:

Page 11

User's Manual - The FT Series Floor Standing, Heating Only Boiler Notes:

H2420000-

Dimensions and specifications subject to change without notice in accordance with our policy of continuous product improvement.

Customer Service and Product Support: 800.900.9276 · Fax 800.559.1583