TRANE LogoInstallation Guide
Split System Air Conditioners
Odyssey™
MERV 13 Filter Accessory Kits for Odyssey Air
Handler – 5 to 25 Tons
BAYFILT006*: Used with Odyssey D Cabinet – TWE051, TWE060
BAYFILT007*: Used with Odyssey E Cabinet – TWE072, TWE076, TWE090
BAYFILT008*: Used with Odyssey F Cabinet – TWE101, TWE120
BAYFILT009*: Used with Odyssey G Cabinet – TWE126, TWE150, TWE156, TWE180
BAYFILT010*: Used with Odyssey H Cabinet – TWE201, TWE240, TWE251, TWE300

ACC-SVN218C Split System Air Conditioners

SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.

Introduction

Read this manual thoroughly before operating or servicing this unit.
Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as required. Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.
The three types of advisories are defined as follows:

Warning icon WARNINGIndicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
Warning icon CAUTIONIndicates a potentially hazardous situation which, if not avoided, could result in minor or moderate
injury. It could also be used to alert against unsafe practices.
Warning icon NOTICEIndicates a situation that could result in equipment or property-damage only accidents.

Important Environmental Concerns

Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants
that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants.

Important Responsible Refrigerant Practices

Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified according to local rules. For the USA, the Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.

 Warning iconWARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury.
All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state/national electrical codes.

Warning icon WARNING
Personal Protective Equipment (PPE) Required!
Failure to wear proper PPE for the job being undertaken could result in death or serious injury.
Technicians, in order to protect themselves from potential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the instructions below:

  • Before installing/servicing this unit, technicians MUST put on all PPE required for the work being undertaken (Examples; cut resistant gloves/ sleeves, butyl gloves, safety glasses, hard hat/ bump cap, fall protection, electrical PPE and arc flash clothing). ALWAYS refer to appropriate Safety Data Sheets (SDS) and OSHA guidelines for proper PPE.
  • When working with or around hazardous chemicals, ALWAYS refer to the appropriate SDS and OSHA/GHS (Global Harmonized System of Classification and Labelling of Chemicals) guidelines for information on allowable personal exposure levels, proper
    respiratory protection and handling instructions.
  • If there is a risk of energized electrical contact, arc, or flash, technicians MUST put on all PPE in accordance with OSHA, NFPA 70E, or other country-specific requirements for arc flash protection, PRIOR to servicing the unit. NEVER PERFORM ANY  SWITCHING, DISCONNECTING, OR VOLTAGE TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASH CLOTHING. ENSURE ELECTRICAL METERS AND EQUIPMENT ARE PROPERLY RATED FOR INTENDED VOLTAGE.

Warning icon WARNING
Follow EHS Policies!
Failure to follow instructions below could result in death or serious injury.

  • All Trane personnel must follow the company’s Environmental, Health and Safety (EHS) policies when performing work such as hot work, electrical, fall protection, lockout/tagout, refrigerant handling, etc. Where local regulations are more stringent than these policies, those regulations supersede these policies.
  • Non-Trane personnel should always follow local regulations.

Warning icon WARNING
R-454B Flammable A2L Refrigerant!
Failure to use proper equipment or components as described below could result in equipment failure, and possibly fire, which could result in death, serious injury, or equipment damage.
The equipment described in this manual uses R-454B refrigerant which is flammable (A2L). Use ONLY R454B rated service equipment and components. For specific handling concerns with R-454B, contact your local representative.

Copyright
This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.
Trademarks
All trademarks referenced in this document are the trademarks of their respective owners.
Parts List
X21130286120 – gasket

CabinetModelUsed withFilter Part #Nominal SizeQty.LocationReplace Direction of FilterKit Label Part #
LHD
DTWE051, 060BAYFILT006*X09011832040162021SAME LEVELLEFT SIDE436733948600
X09011832050202021
ETWE072, 076, 090BAYFILT007*X09011832010162523LEFT OR RIGHT SIDE436733948700
FTWE101, 120BAYFILT008*X09011832010162524LEFT OR RIGHT SIDE436733948800
GTWE126, 150, 156,180BAYFILT009*X09011832140201524UPPER LEVELLEFT OR RIGHT SIDE436733948900
X09011832140201524LOWER LEVEL
HTWE201, 240, 251, 300BAYFILT010*X09011832010251622UPPER LEVELRIGHT SIDE436733949000
X09011832040201622
X09011832010251622LOWER LEVEL
X09011832040201622

Installation

Table 2. Static pressure drop through accessories (inch W.G.) — standard air handler

TonsUnit Model NumberCFM2″ MERV 13 FILTER
5TWE060**A/B16000.22
20000.29
24000.36
6TWE072**B19200.15
24000.19
28800.24
7.5TWE090**A/B24000.19
30000.25
36000.31
10TWE120**A/B32000.19
40000.25
48000.31
12.5TWE150**B40000.15
50000.20
60000.25
15TWE180**B48000.19
60000.25
72000.31
20TWE240**B64000.22
80000.29
96000.36
25TWE300**B80000.29
1000-00.37
1200-00.47

Installation for 5-10 Ton Air Handlers

  1. Refer to parts list for corresponding unit model and correct part number/quantity.
  2. Locate kit label and place next to an open spot near the nameplate. See Figure 1, p. 4.
  3. From Figure 1, p. 4, loosen the two screws on panel. Set panel aside.TRANE ACC SVN218C Split System Air Conditioners - label location
  4. Remove original air filters. See Figure 2, p. 4.TRANE ACC SVN218C Split System Air Conditioners - Remove filter
  5. Locate two filter racks and loosen four screws on filter rack. Figure 3, p. 5.TRANE ACC SVN218C Split System Air Conditioners - Remove filter rack screws
  6. Move filter rack to position shown in Figure 4, p. 5, tighten the four screws.TRANE ACC SVN218C Split System Air Conditioners - filter rack
  7. Install the new air filter per parts list. Pay attention to length direction of filter and filter rack. See Figure 5, p. 5.TRANE ACC SVN218C Split System Air Conditioners - filter
  8. Cut the provided gasket to size and paste on the side panel insulation so that it aligns with the location of the filter (for installation in Title 24 compliant regions).TRANE ACC SVN218C Split System Air Conditioners - Add gasket
  9. Push the filters to the end. Check for gap between filter and newly installed gasket. If there is gap, repeat Step 7 on the side panel on opposite side (for installation in Title 24 compliant regions). See Figure 7, p. 6TRANE ACC SVN218C Split System Air Conditioners - Add gasket on the other side
  10. Install panel and tighten screws to close the unit. See Figure 8, p. 6.TRANE ACC SVN218C Split System Air Conditioners - Panel replacement
  11. Dispose of filter and package.

Installation for 12.5-25 Ton Air Handlers

  1. Refer to parts list for corresponding unit model and correct part number/quantity.
  2. Locate kit label and place next to an open spot near the nameplate. See Figure 9, p. 6. Figure 9. Panel removal and label locationTRANE ACC SVN218C Split System Air Conditioners - label location 1
  3. From pic shown direction, loosen the four screws on panel. Set panel aside.
  4. Remove original air filters. See Figure 10, p. 7.TRANE ACC SVN218C Split System Air Conditioners - Filter rack removal
  5. Install the new air filter per parts list table.
    Notes:
    • Pay attention to the difference between upper and lower level. See Figure 11, p. 7TRANE ACC SVN218C Split System Air Conditioners - Install new filters• Pay attention to length direction of filter and filter rack.
  6. Install panel and tighten screws to close the unit. See Figure 12, p. 7.TRANE ACC SVN218C Split System Air Conditioners - Install panel
  7. Dispose of filter and package.
  8. Cut the provided gasket to size and paste on the side panel insulation so that it aligns with the location of the filter (for installation in Title 24 compliant regions). See Figure 13, p. 8.TRANE ACC SVN218C Split System Air Conditioners - Add gasket 1
  9. Push the filters to the end. Check for gap between filter and newly installed gasket. If there is gap, repeat Step 8 on the side panel on opposite side (for installation in Title 24 compliant regions). See Figure 14, p. 8.TRANE ACC SVN218C Split System Air Conditioners - other side

Trane and American Standard create comfortable, energy efficient indoor environments for commercial and residential applications. For more information, please visit trane.com or americanstandardair.com.
Trane and American Standard have a policy of continuous product and product data improvement and reserve the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.
ACC-SVN218C-EN 11 Aug 2024
Supersedes ACC-SVN218B-EN (April 2020)
©2024

TRANE Logo

Documents / Resources

TRANE ACC-SVN218C Split System Air Conditioners [pdf] Installation Guide
ACC-SVN218C Split System Air Conditioners, ACC-SVN218C, Split System Air Conditioners, Air Conditioners, Conditioners

References

Leave a comment

Your email address will not be published. Required fields are marked *