User Guide for Cyber Power models including: RMCARD205 Smart App Sinewave Ups Series, RMCARD205, Smart App Sinewave Ups Series, Sinewave Ups Series, Ups Series
PR3000RTXL2UXXAN | User Manual | CyberPower
Smart App Sinewave UPS Firmware v1.1786 - Firmware - Product Details, Specs, | CyberPower
File Info : application/pdf, 7 Pages, 250.61KB
DocumentDocumentYOUR ULTIMATE ALLY IN POWER SMART APP SINEWAVE UPS SERIES RMCARD205Firmware FIRMWARE UPGRADE PROCEDURES Thisistheprocedureforupdatingthefirmwareofthe PR3000RTXL2UACNandPR3000RTXL2UHVACNUPS. TheUPSwillbeupdatedtofirmwareversion1.1786. Cyber Power Systems (USA), Inc. 424112thAvenueEast,Suite400|Shakopee,MN55379|CyberPowerSystems.com UPDATING FIRMWARE Step 1: DownloadthePRV36_US_2UA-101786-240814-0903.binfilefromthecyberpower.comwebsite. https://www.cyberpowersystems.com/products/software/firmware/ NOTE:Beforeapplyingthisfirmwareupdate,pleasescheduleatimewhentheconnected equipmentcanbeturnedoff.ThisupdaterequirespoweringdowntheUPSforafewminutes. ThisprocedurerequiresanetworkconnectiontotheRMCARD205(networkcard)installed inyourUPS.Anynetworkequipmentlikeswitchesorrouters,thatarepluggedintotheUPS, shouldbetransferredtemporarilytoanalternatesourceofpowersotheconnectiontothe RMCARDisnotlostwhentheUPSisturnedoff. Step 2: VerifyRMCARD205hasaf/wversionofv1.14orhighertosupporttheUPSfirmwareupgrade function.Tochecktheversion,opentheRMCARD205interfaceandclickonthe"System"tab locatedatthetopandselect"About"ontheside. IfyourRMCARD205Firmwareversionis1.14orlower,pleaseupdatetothelatestRMCARD205 firmwarebeforeupdatingtheUPS.ThefirmwarecanbefoundatCyberPower'swebsite. Ref: https://www.cyberpowersystems.com/products/software/firmware/ UPDATING FIRMWARE Step 3: Select"TurnUPSoff"radialbuttonforInstantshutdownontheUPSMasterSwitchpage andthenclick"Next"buttontoinitiateUPSshutdownprocedure. Step 3.1: Click"Apply"buttononUPSMasterSwitchpagetoconfirm. UPDATING FIRMWARE Step 3.2: Underthe"Next"buttonitwillsayUPSRemainOff.YourUPSisnolongersupplying powertotheACoutlets. Step 4: Click"Update"iconontheUPSInformationpagetobeginthefirmwareupdateprocess. UPDATING FIRMWARE Step 4.1: Clickonthe"ChooseFile"buttonandselectthePRV36_US_2UA-101786-240814-0903.binfile fromthefolderyoudownloadeditinto. Step 4.2: Clickonthe"Submit"buttontobegintheupdate. UPDATING FIRMWARE Step 5: Aprogressindicatorwillbeshownonyourscreen.Processingthefirmwareupdate willtake5-10minutes. Step 5.1: Oncetheupdatehasbeenappliedarebootwarningwillappear. Step 5.2: YourUPSwillturnonautomaticallyandyourscreenwilldisplaytheloginprompt. UPDATING FIRMWARE Step 5.3: Loginandclickonthe"UPS"tabandselect"Information"toconfirmtheversion numberhaschangedto1.1786. Theupgradeiscomplete,andyoucanreturntousingyourUPSasnormal. Ifyouneedadditionalassistance,pleasecall1-877-297-6937,press1forTechnicalSupport orsubmitasupportticketonlineatwww.cyberpower.com/support. Pleasebereadytoprovidethe12-characterserialnumberoftheUPSwhencontactingus. ©2024CyberPowerSystems(USA),Inc.CyberPowerisaregisteredtrademarkandbrandof CyberPowerSystems(USA),Inc.Allrightsreserved.Allothertrademarksarethepropertyoftheirrespectiveowners.