User Manual
40A MPPT Solar Charge Controller

Input: DC 100V Maximum Output: DC 12V / 24V 40A

MODEL: RS-MPPT40FM

THIS MANUAL CONTAINS IMPORTANT SAFETY AND OPERATING INSTRUCTIONS FOR MPPT SOLAR CHARGE CONTROLLER. YOU READ THIS MANUAL AND FOLLOW THE INSTRUCTIONS EXACTLY.

02 WARNING ­ IMPORTANT PLEASE READ 02 MOUNTING AND INSTALLATION 05 WIRING CONNECTIONS 06 OPERATING ­ LCD DISPLAY 10 CHARGING STAGE 11 LED INDICATIONS 12 SAFETY PROTECTIONS 12 MAINTENANCE 13 SPECIFICATIONS 15 FEATURE AND ADVANTAGE
-01-

WARNING ­ IMPORTANT PLEASE READ
RISK OF EXPLOSIVE GASES WORKING IN VICINITY OF A LEAD-ACID BATTERY IS DANGEROUS. EXPLOSIVE GASES DEVELOP DURING NORMAL BATTERY OPERATION. IT IS IMPORTANT THAT EACH TIME BEFORE USING OR CONNECTING YOUR SOLAR CONTROLLER:
This charger is designed for indoor use only and should never be exposed to rain. Do not disassemble the controller. Take to a qualified person if the unit requires repairing. Lead acid, LCO, LiFePO4, LTO batteries can be dangerous. Ensure no sparks or flames are present when working near batteries. Eye protection should always be used. Never short circuit the battery. Given sufficient light solar panels always generate energy even when they are disconnected. Accidental `shorting' of the terminals or wiring can result in sparks causing personal injury or a fire hazard. We recommend that you cover up the panel(s) with some sort of soft cloth so you can block all incoming light during the installation. This will ensure that no damage is caused to the Solar Panel or Battery if the wires are accidentally short-circuited. Always install a battery fuse on each circuit including the solar controller. Do not reverse connect the wires to the solar panel or battery.
MOUNTING AND INSTALLATION
This solar controller is designed to be mounted against a wall, especially for caravan use, out of the way but easily visible, please note, mounted on a vertical surface to optimize cable placement and cooling of the unit, indoor use, protected from the weather.
-02-

1. The mounting dimensions
Refer to the Fig.1 to know the panel size and depth. Refer to Fig. 2 to get a cavity for flush mounting, make sure there is sufficient depth behind the controller or in the cavity.

Fig.1

Fig.2

2. The installation preparation
Insert a slotted screwdriver into the slots at the below location of  and , turn the screwdriver to separate the surface panel from the basement. Take off the surface panel from the basement, you can see four screw holes on the top face.

Fig.3 -03-

3. The installation procedures
Please see below steps from 1 ~ 6 Insert the input and output cables and firmly secure the cables to the solar controller via the screws, fit the controller to the cutout and wall, secure the controller to the wall, reinstall the surface panel back to the solar controller.
Fig.4
-04-

WIRING CONNECTIONS
To protect the Battery and the Solar Panel, we strongly recommend that you place an inline fuse on the positive wire on both the "Solar" and "Battery" Circuits. 50A fuse for 40A controller; 40A fuse for 30A controller, (As close to the Battery /Panel as possible). Refer to the below drawing, please cover the solar panel before connecting cables.

50AMP

Fig.5

Correct Wire Size
Please refer to the wire size chart below to determine the minimum size wire needed for each connection. This will also ensure you get the best performance out of your solar controller.

Rated Current

The cable total length One-way distance

Solar panel -> Controller -> Battery

< 3M

3-6M

6-9M

Rated Current

The cable total length One-way distance

Solar panel -> Controller -> Battery(meter)

< 3M

3-6M

6-9M

30/40Amp

The cable size (AWG)

10AWG

8AWG

6AWG

Rated Current

The cable total length One-way distance

Solar panel -> Controller -> Battery

< 10ft

10-20ft

20-30ft

Rated Current

The cable total length One-way distance

Solar panel -> Controller -> Battery(feet)

< 10ft

10-20ft

20-30ft

30/40Amp

The cable size (AWG)

10AWG

8AWG

6AWG

The solar controller is installed to close to the battery as near as possible. Please do not reverse the connections with the solar panel and battery when installed the cables Once the connections are completed, the Solar Controller will start working automatically.

-05-

OPERATING ­ LCD DISPLAY
When the controller powers on, the unit will run self-qualify mode and automatically show below items on LCD before going into charging process.
Self-test starts, digital meter segments test Software version test System battery voltage and current test External battery temperature sensor test (if connected) Absorption voltage test Float voltage test Self-test completed
System battery voltage setting
Press and hold the SET UP button for 3 seconds to go into the system battery voltage setting mode, press PV / + or BATT / - button to select your desired system battery voltage 12V, 24V or AUTO, press the SET UP button again to confirm the battery voltage setting.
The display in sequence,
The controller will automatically memorize your previous battery voltage setting, If AUTO mode selected, the controller will automatically detect 12V or 24V battery connected.
System Battery type setting
Please check your battery manufacturer's specifications to select correct battery type. The unit provides 8+1 battery types for selections: LCO, LTO, LFP, Crystal (Lead crystal), Gel, AGM, WET (Conventional lead acid) and Calcium (Calcium contented) battery plus Custom setting. Follow up the Battery voltage setting, Press the SET UP button to go into your battery type setting mode, the battery type you select will be flashed on the LCD meter, the default setting is AGM Battery; the controller will automatically memorize your battery type setting. Remarks: LCO battery type setting is only recommended working with 3-SERIES Lithium Cobalt Oxide LiCoO2 battery.
-06-

LFP battery shown in LCD indicates Lithium Iron Phosphate battery, LiFePO4 battery. LTO battery shown in LCD indicates Lithium titanate oxidized, Li4Ti5O12 battery. Caution: Incorrect battery type setting may damage your battery. Press PV / + or BATT / - button to navigate your desired battery type as below:
Press the SET UP button again, the selected battery type will be solid On and confirmed.
Custom setting
This solar controller provides a CUSTOM mode to meet your special battery charging demand, the users can preset the Absorption voltage level and duration, Equalization voltage level, duration and periodical cycle, Float voltage level and Reset voltage level for your targeted battery charging parameters. Alternatively display Absorption Voltage character AbS.U and voltage data when going into CUSTOM mode:
Absorption voltage setting range from 13.20V ~ 15.50V, press PV / + or BATT / - button for once +/- 0.05V variation, press the SET UP button again to confirm the absorption voltage level you preset, then move to next Absorption duration setting.
Alternatively display Absorption Time character AbS.T and duration data; Absorption duration setting lasted from 5 ­ 500 minutes, press PV / + or BATT / - button for once +/- 5 minutes variation, press the SET UP button again to confirm the absorption duration setting, then move to next Equalization voltage setting.
-07-

Alternatively display Equalization voltage character EqL.U and voltage data; Equalization voltage setting range from 13.20V ~ 16.2V, press PV / + or BATT / - button for once +/- 0.05V variation, press the SET UP button again to confirm the Equalization voltage and then move to next Equalization duration setting.
Alternatively display Equalization Time character EqL.T and duration data; Equalization duration setting lasted from 5 ­ 500 minutes, press PV / + or BATT / - button for once +/- 5 minutes variation, press the SET UP button again to confirm the Equalization duration setting and then move to next Equalization periodical cycle setting.
Alternatively display Equalization periodical cycle character EqL.P and cycle day; Equalization periodical cycle day setting from 0 ­ 100 days, press PV / + or BATT / - button for once +/- 1 day variation, 0 indicates no Equalization setting; press the SET UP button again to confirm the Equalization periodical cycle setting and move to next Float voltage setting.
Alternatively display Float voltage character FLT.U and voltage data; Float voltage setting range from 13.00V ~ 14.00V, press PV / + or BATT / - button for once +/- 0.05V variation, press the SET UP button again to confirm the Float voltage and then move to next Reset/Restart setting.
Alternatively display Reset/ Restart voltage character rST.U and voltage data; Reset voltage setting range from 12.50V ~ 13.50V, press PV / + or BATT / - button for once +/- 0.05V variation, press the SET UP button again to confirm the Reset / Restart voltage and all settings will be automatically stored.
-08-

Solar input parameter display
Once the settings are completed, the solar controller will automatically go into charging process, the LCD displays the parameters of solar input as below: Press PV / + button in sequence, the LCD will display in turn with solar input voltage, current, power and kWh.
Press BATT / - button in sequence, the LCD will display in turn with battery voltage, charging current, charged capacity (Amp-hour) and battery temperature (if external temperature sensor connected).
The users also can read the battery voltage as degree centigrade or Fahrenheit degree by pressing SET UP button for converting.
Alternatively display voltage and FUL when battery is fully charged.
You also can visually monitor your battery charging condition for each battery; there is an LCD bar to show the percentage of charge, you can easily see the battery is charged to 25%, 50%, 75% or 100%, and also roughly match each charging stage of Soft-start, Bulk, Absorption and Float.
The LCD also can be treated as an independent voltage meter or thermometer at night.
-09-

CHARGING STAGE
This solar controller provides multiple charging stages with smart charging algorithm. For Lead acid battery (Crystal, Gel, AGM, WET and Calcium battery): Soft Charge ­ Bulk Charge - Absorption charge - Equalizing Charge* - Float charge
For Lithium battery (LCO, LFP, LTO battery) Soft Charge ­ Bulk Charge - Absorption charge ­ Stop and Restart charge*
Soft start - When batteries suffer an over-discharge, the controller will softly ramp the battery voltage up to 10V.
Bulk Charge - Maximum current charging until batteries rise to Absorption level. For Lead crystal battery type, the charge controller will deliver two step level of Bulk charge, when the first level rises the battery voltage up to14.4V, then switch into the second level of the 10% of the first bulk charge rate, until the Lead crystal battery voltage up to 14.7V.
Absorption - Constant voltage charging and battery is over 85% for lead acid battery; the Lithium battery (LCO, LFP and LTO battery) will close fully charged after absorption stage. -10-

Equalization * - Only for WET or Calcium battery type, when the battery is deeply drained below 10V or every 28 days cycle, it will automatically run this stage to bring the internal cells as an equal state and fully complement the loss of capacity. (Lead crystal, Gel, AGM battery or Lithium batteries do not run Equalization charge).
Float Charge or Re-Start charge* Battery is fully charged and maintained at a safe level. A fully charged Lead acid battery (Crystal, GEL, AGM, WET or Calcium battery) has a voltage of more than 13.6 Volts; if the lead acid battery voltage drops to 12.7V at float mode, it will return to Bulk charge, Lithium battery will stop charge after Absorption stage, it will restart to bulk charge if the voltage discharge less than 12.0V for LCO battery, 13.0V for LTO battery, 13.3V for LFP.
Remarks: This controller provides an override function (force output delivery) for some heavily discharged Lead acid batteries (Low to 0V), or for some LiFePO4 batteries which are protected by BMS due to over-discharged. Press BATT / - button for 3 seconds to wake up the Lithium battery (activate the BMS against protection) or override the Lead acid battery.

LED INDICATIONS

Normal charge

LED indications LED Color Soft-Start Bulk charge Absorption / Equalization Float charge

GREEN ON ON ON ON

BLUE FLASH
ON ON OFF

WHITE FLASH
ON ON ON

WHITE OFF
FLASH ON ON

WHITE OFF OFF ON ON

WHITE OFF OFF
FLASH ON

-11-

Abnormal charge
Solar panel abnormal mode Solar panel weak <15V Solar panel reverse connection Solar panel over voltage (> 95V)
Battery abnormal mode Solar panel is connected, battery disconnected Battery reverse connection
Battery over voltage than > 17V
Battery temperature over 65 The controller over temperature protection

LCD display /
LCD display

LED indication LCD backlight

Flash ON Flash Flash Flash Flash

ON Flash Flash

LED indication LCD backlight

Flash Flash Flash Flash Flash Flash Flash Flash Flash Flash
ON

Flash Flash Flash Flash Flash

SAFETY PROTECTIONS
-- Reverse polarity solar and battery connection. -- Against reverse current from battery to solar panel at night. -- Over temperature protection with charging current de-rate. -- Transient overvoltage protection, a varistor or transient voltage suppressor (TVS) at the solar input and battery output against surge voltage.
MAINTENANCE
Occasionally, clean the case using a damp cloth and mild cleaning agent. Check with terminals without loose, rusty; If connecting cable is damaged, replace the cable by qualified person.

-12-

SPECIFICATIONS

ELECTRICAL PARAMETERS Maximum PV open circuit voltage at -20 Normal input PV voltage at 25 Max. PV input current Max. PV short circuit current Rated charging current Conversion efficiency Tracking efficiency Nominal PV power Self-consumption from battery when PV is disconnected Output open circuit voltage when battery is disconnected MPP voltage range CHARGING CHARACTERISTICS Minimum battery start charging voltage Soft start charging voltage Soft start charging current Bulk charge Absorption charging voltage at 25 --LCO battery --LTO battery --LFP battery --Gel type battery --AGM type battery (default setting) --WET type battery --Lead Crystal battery --Calcium battery --Custom setting range Absorption transits to Equalizing or Float /Stop condition --Charging current drops to --or Absorption charging timer timed out Equalization charging activation -- Only for WET or Calcium battery -- Battery voltage discharged less than -- Automatic equalizing charging periodical

100

Max. VDC

92

Max. VDC

40

Max. AMP

45

Max. AMP

40

Max. AMP

98

Max. %

99.5

Min %

600@12V/1200@24V

Watt

10

±0.5 mA

0.5

Max. VDC

15-72

±0.5 VDC

5 5-10 20 40

Min VDC ±0.2 VDC
AMP Max. AMP

12.6 14.0 14.2 14.1 14.4 14.7 14.7 14.9 13.2-15.5

±0.2 ±0.2 ±0.2 ±0.2 ±0.2 ±0.2 ±0.2 ±0.2 ±0.2

VDC VDC VDC VDC VDC VDC VDC VDC VDC

2.0

+0.1 AMP

4

Huor

10

±0.2 VDC

28

Day

-13-

Equalization charging voltage at 25 Equalization charging timer timed out Equalization charging voltage for CUSTOM setting Float voltage (for Crystal, GEL, WET, AGM and Calcium battery) at 25 Restart voltage -- for Crystal, GEL, WET, AGM and Calcium battery) -- for LCO battery -- LTO battery -- LFP -- for CUSTOM setting range Voltage control accuracy Battery temperature compensation coefficient Temperature compensation range ELECTRICAL PARTS Input output terminal PHYSICAL PARAMETERS Controller material Mounting IP grade Net weight ENVIRONMENTAL CHARACTERISTICS Operating temperature Storage temperature Operating Humidity range

15.5 2 13.2-16.2 13.6

±0.2
±0.2 ±0.2

VDC Hour VDC VDC

12.7 12.0 13.0 13.3 12.5-13.5 ± 1% -24 -20~+50

±0.2 ±0.2 ±0.2 ±0.2 ±0.2

VDC VDC VDC VDC VDC

mV/ 

Rated 50A connector

Plastic, PC Surface mounting IP43, Approx. 0.8KG

-25 ~ 50 / -13 ~ 122  -40 ~ 85 / -40 ~ 185  0-85% RH

Remarks: Battery Voltage settings for 12V mode, x2 for 24V mode.

-14-

FEATURE AND ADVANTAGE
PV open circuit voltage up to 100V. The latest Maximum Power Point Tracking (MPPT) algorithm. Unique multiple peaks detected technology for maximum power point tracking. MPPT tracking efficiency above 99.5%. Wider MPP operating voltage range. Common negative grounding connection. Suit for most rechargeable batteries, up to 9 battery types preset plus custom setting. Extensive internal electronics in-circuit protection. Reliable operating safety protection: overcharging or undercharging protection, short circuit protection, reverse polarity protection, thermal protection. Automatically detect 12V or 24V DC system voltages. Unique and concise LED bar to indicate the solar statues and battery charging condition. Large and informative display interface to show Solar parameter, battery charging parameter, battery type, battery temperature, custom presetting and faulty codes, etc. Provides plug-in remote digital display meter (Optional). Provides external battery temperature sensor (Optional). Splash proof IP43. Rubber mask for connecting terminals protection. Conformal coating for internal boards. Designed according to UL1741, EN/IEC 62109-1; EMI standard: EN61000-6-1/EN61000-6-3 and FCC standard: 47 CFR Part 15, Subpart B.
-15-

