Fiilex TOX End Feed Wiring Guide
STEP-BY-STEP INSTRUCTIONS
Please refer to the Video Links for detailed, step-by-step instructions for wiring the end feed. Contact Fiilex Customer Support (fiilex@fiilex.com) for any questions.
VIDEO LINKS
A QR code is provided as a link to video instructions. Scan the QR code with a mobile device to access the videos.
READ AND SAVE ALL INSTRUCTIONS
- Disconnect electrical power before adding to or changing the configuration of the track.
- Do not install this track in damp or wet locations (IP20, 45°C max).
- Do not install any part of a track system less than 5 ft. above the floor.
- Do not install track on any vertical surface.
- Check with a qualified electrician prior to any installation.
- Do not attempt to energize anything other than the Fiilex track lighting fixtures on the track.
- In order to reduce the risk of fire and electrical shock, do not attempt to connect power tools, extension cords, appliances and the like to the track.
- Do not slide light fixtures along track when relocating. Always remove fixtures and adapters from the track first.
- Before reinstalling in new location, make sure to properly secure the fixtures and adapters to the track.
Wire Power to End Feed
Each End Feed component has (3) circuits, with a total of 16A combined max load.
End Feed Component Overview
The End Feed component features a mechanical key/groove (labeled A) that ensures correct insertion into the track. Ensure this mechanical key is oriented properly during installation.
For wiring the end feed, use either 5x AWG12 or 7x AWG12 wire. To prepare, unscrew and remove the end-feed to expose the contacts. Knock out either hole B or C to create an entry point for the wires, then pass the wire through the chosen hole.
If passing the wire through hole C, a screw cord grip must be used. If using hole B, a plastic cord grip (not provided) is recommended.
Remove approximately 3-3.5 inches of protective covering from the wires, then strip about 1/2 inch of insulation from the ends of the wires.
End Feed Component Pin-outs
The End Feed component supports 3 circuits with a total capacity of 16 amps.
The connection terminals are labeled as follows:
- DATA(+)
- DATA(-)
- L3
- N (Neutral)
- L2
- L1
- GROUND
Wire DMX to End Feed
DMX signal requires 2 signal carriers. The polarity of the DMX conductors is labeled next to the corresponding screws. Visual representation showing the DMX polarity labels on the connection screws. Illustration indicating that the feeder has been connected to both Power and Data. Female connector diagram with pins 1, 2, 3 labeled. Diagram showing pins #1, #2, #7, #8. Diagram showing Tip, Ring 1, Ring 2, Sleeve.DMX Polarity Labeling
DMX Conductors Connected
Standard DMX Cabling and Polarity
Connector Description Connector Pin-out Signal XLR5 DMX lighting standard RJ45 Architectural, corporate, and fixed installations TRRS Fiilex RPU, P3 / Q3 / G3.