Product Information

The Duct Smoke Detector is a photoelectric plug-in device that detects smoke in HVAC ducts. It comes in two models: DUCTSD and D4120. The key differences between the two models are:

  1. Cover integrated smoke test port
  2. NO field selectable dip switches
  3. Opaque power board cover
  4. Interconnect number of devices 30

The DUCTSD model does not offer field selectable dip switches, while the D4120 model allows for the selection of instant or 7-minute delay cover tamper switch activation. Both models can interconnect up to 30 total devices.

Product Usage Instructions

Smoke Test Port Usage

  1. Put the detector into Speed-Up Test mode by pressing and holding the Test/Reset button for 2 to 7 seconds. When in Speed-Up Test mode, sensor LEDs will alternately flash Red and Green.
  2. Lift the tethered plug sealing the smoke test port via pull tab.
  3. Spray canned smoke into the test port.
  4. Replace the tethered test plug.

D4120 Cover Tamper Switch Activation

The D4120 model allows for the selection of instant or 7-minute delay cover tamper switch activation. To select the desired option:

  1. Remove the cover from the D4120 detector.
  2. Locate the dip switch on the power board labeled “Tamper Delay”.
  3. Toggle the dip switch to the desired setting: “ON” for instant activation, or “OFF” for 7-minute delay activation.
  4. Replace the cover on the D4120 detector.

Duct Smoke Detector Cross Reference

The DUCTSD 4-wire photoelectric duct smoke detector features a pivoting housing that fi ts both square and rectangular footprints and mounts to round or rectangular ductwork. This unit senses smoke in the most challenging conditions, operating in airfl ow speeds of 100 to 4,000 feet per minute, temperatures of –4°F to 158°F, and a humidity range of 0 to 95 percent (non-condensing). A plug-in sensor head offers simple installation and maintenance. The cover-integrated smoke test port enables easy testing and maintenance.SYSTEM-SENSOR-DUCTSD-Duct-Smoke-Detector-Cross-fig-1

Key Differences Between DUCTSD and D4120

  1. Cover integrated smoke test port
  2. NO fi eld selectable dip switches
  3. Opaque power board cover
  4. Interconnect number of devices 30

COVER INTEGRATED SMOKE TEST PORT How to Use the Smoke Test Port

  1. Put detector into Speed-Up Test mode
    • a. Press and hold Test/Reset button for 2 to 7 seconds
    • b. When in Speed-Up Test mode sensor LEDs will alternately fl ash Red and Green
  2. Lift tethered plug sealing the smoke test port via pull tab
  3. Spray canned smoke into the test port
  4. Replace tethered test plug

Simplified Options

  • DUCTSD does NOT offer fi eld selectable dip switches. The simplifi ed DUCTSD offers:
  1. One connected sensor
  2. Cover Tamper switch activates 7 minutes after sensor cover has been removed or improperly seated
  3. Aux Relay does not switch states on a Trouble condition

Opaque Power Board Cover

  • Quick reference information on the inside of the power board cover.
Device Interconnect
  • Interconnect any combination of DUCTSD and D4120 detectors, up to a maximum of 30 total devices.
SYSTEM-SENSOR-DUCTSD-Duct-Smoke-Detector-Cross-fig-2
 

Feature

  

D4120

Sensor TechnologyPhotoelectricPhotoelectric
Sensor MechanicsPlug-InPlug-In
Number of Sensors11 or 2 sensors
Airflow100 – 4000fpm100 – 4000fpm
Product Length14.38 inches14.38 inches
Product Width5 inches5 inches
Depth2.5 inches2.5 inches
Housing2 piece2 piece
Sampling Tubes EntryFront and rear entryFront and rear entry
Cover ColorBlack OpaqueTransparent
Cover Connectors4 captive screws on sensor

3 captive screws on power board

4 captive screws on sensor

3 captive screws on power board

Cover Tamper Delay7 minutesSelectable – Instant or 7 minutes
Conduit OpeningsTop: 2 x 1/2” Side 1 x 3/4”Top: 2 x 1/2” Side 1 x 3/4”
Wire Gauge12 gauge12 gauge
Connection Between Sensor and PowerBoardCo-Located – Pre-wiredCo-Located – Pre-wired
Wiring DiagramTerminal designator by each terminalTerminal designator by each terminal
Voltage Range20-29VDC

24VAC 50-60Hz

120VAC 50-60Hz (DUCTSD)

220/240VAC 50-60Hz (DUCTSD240)

20-29VDC

24VAC 50-60Hz

120VAC 50-60Hz (D4120)

220/240VAC 50-60Hz (D4240)

Standby Current Consumption21mA21mA
Power Up Time37 seconds (initialization complete)37 seconds (initialization complete)
Reset Time0.6 seconds0.6 seconds
Relays10A @ 30VDC/250VAC alarm 2 form C AUX 2A @ 30VDC/125VAC alarm

2A @ 30VDC/125VAC trouble

10A @ 30VDC/250VAC alarm 2 form C AUX 2A @ 30VDC/125VAC alarm

2A @ 30VDC/125VAC trouble

Sensor LED FunctionsStandby: 5 sec green blink Maintenance: 5 sec Red blink Trouble: No LED indication Alarm: Solid RedStandby: 5 sec green blink Maintenance: 5 sec Red blink Trouble: No LED indication Alarm: Solid Red
PowerBoard LED FunctionsStandby: 5 sec Red blink Maintenance: 5 sec Amber Blink Trouble: Solid Amber

Alarm: Solid red

Standby: 5 sec Red blink Maintenance: 5 sec Amber Blink Trouble: Solid Amber

Alarm: Solid red

Shutdown on TroubleAux Relay does not switch states on TroubleSelectable
Interconnection Quantity30 units50 units
InterconnectionNon-isolatedNon-isolated
Test FeaturesCover integrated smoke test port Magnet test at sensor

Pushbutton Test/Reset at PowerBoard

Magnet test at sensor

 

Pushbutton Test/Reset at PowerBoard

 Responds only if sensor is not in maintenanceResponds only if sensor is not in maintenance
Sensitivity MeasurementSENS-RDRSENS-RDR
AccessoriesCompatible with existing accessoriesCompatible with existing accessories
FiltersNoneNone
Temperature– 4ºF to 158ºF (-20ºC to +70ºC)– 4ºF to 158ºF (-20ºC to +70ºC)
Smoke Test PortCover integrated smoke test portNone