SUPRA-TDS-2 Supra TDS Filter
“
Specifications
- Handle: Semi-automatic
- Filter Valve: Self-sealing
- Flush Valve: Manual
Product Usage Instructions
Assembly Instructions
- Connect the flush valve to the bottom of the filter cup.
(Teflon tape not required)
Installation Guidelines
- Verify the flow direction according to markings on the filter
body. - Ensure both flush valves are fully closed.
- Install a shut-off valve upstream for easy maintenance.
Initial Operation
- Gradually open the water source and check for leaks.
- The filter is now operational.
Automatic Flushing Procedure
- Pressure can be measured manually or with a pressure
indicator. - Flushing Steps:
- Open the flush valve slowly.
- Turn the scanning handle counterclockwise until it stops.
- Close the flush valve slowly and check the pressure.
Manual Cleaning Procedure
- Close the inlet valve to the filter.
- Open the flush valve gradually to drain water.
- Remove components for cleaning and reassemble in reverse
order.
FAQ
Q: Can I open the filter cup while the system is under
pressure?
A: No, do not open the filter cup while the
system is under pressure to avoid accidents or damage.
“`
SUPRA-TDSTM
Semi-Automatic Disc Filter
Assembly, Installation, and Maintenance Instructions For 2″ and 3″ Filters
A S S E M B LY I N S T R U CT I O N S
1. Connect the 1″ flush valve to the bottom of the filter cup. Note: Teflon tape is not required; the valve is self-sealing.
I N S TA L LAT I O N G U I D E L I N E S
1. Install the filter either vertically or at a 90° angle to the pipe. Ensure the flush valve is oriented downward or to the side.
2. Verify the flow direction according to the markings on the filter body.
3. Ensure both flush valves are fully closed. 4. It is recommended to install a shut-off valve upstream of the
filter to allow for easy maintenance. 5. The filter is now ready for initial operation.
INITIAL OPERATION
1. Gradually open the water source and check all connections for leaks.
2. Perform 23 flushing cycles following the instructions in the next section.
3. The filter is now operational.
AUTOMATIC FLUSHING PROCEDURE
Flush the filter when the head loss reaches 0.50.7 bar (710 PSI).
Pressure Monitoring 1. Pressure can be measured manually by inserting a gauge into
the pressure ports on the filter body. 2. For easier monitoring, a pressure indicator is recommended:
· The indicator features a red button that pops up when pressure loss exceeds 0.5 bar, signaling the need for flushing.
· After flushing, the red button retracts, indicating normal operation.
· The indicator is connected directly to the built-in pressure testing ports.
· When installed, the pressure indicator eliminates the need for manual pressure checks.
FLUSHING STEPS
1. Open the flush valve slowly. 2. Turn the scanning handle counterclockwise until it stops
(the handle will rise upward). 3. Close the flush valve slowly and check the pressure:
If a pressure indicator is installed, verify that the red pin has retracted. 4. If pressure remains high or the red pin stays raised, repeat the flushing cycle. 5. If the filter is still not clean after repeated flushing, proceed with the manual cleaning procedure.
Note: Water flow to the irrigation system remains uninterrupted during automatic flushing.
26-045 ©2025 DIG Corp
MANUAL CLEANING PROCEDURE
1. Close the inlet valve to the filter. 2. Open the flush valve gradually to drain water from the filter. 3. Loosen the locking nut and remove the filter cup. 4. Remove the pin that connects the handle and detach the
handle. 5. Unscrew and remove the scanner bar. 6. Carefully remove the screen and rinse it thoroughly with
clean water. Do not use a wire brush. 7. Reassemble the filter:
a. Reinsert all components in reverse order. b. Gradually open the inlet valve. c. The filter is ready for use.
i Warning
Do not open the filter cup while the system is under pressure. S P E C I F I CAT I O N S
· Pressure: Max 145 PSI (10 bar) · Flow Rate: 2″ 110 GPM | 3″ 220 GPM · Discs: 40 / 80 / 120 / 150 mesh · Area: 158 in² | Volume: 81 in³ · Sizes: 2″ & 3″ NPT · Temp: Max 140°F (60°C) · Flush Time: 1530s (handle), 10s (port) · Flush Pressure: Min 29 PSI · Flush Flow: 2 bar 40 GPM | 3 bar 52 GPM · Materials: RPA, PP, RPP, EPDM
Handle
Filter Valve
Flush Valve