SUNSYNK logoL051100-A Power Lite Lithium Battery System
Owner’s Manual

SUNSYNK L051100-A Power Lite Lithium Battery System - Fig14

Introduction

Thank you for choosing Sunsilk’s energy storage system.
The energy storage module comprises of lithium ion rechargeable batteries with 5.12 kWh capacity, and the controller enables a central of multiple modules.
This manual provides information regarding safety precautions to prevent possible accidents and how to use the product.
Please read this manual carefully before use for safety and keep this manual handy for reference.
1.1. Main Features
Some main features of this product are:

  • Long Life Span
    The battery can be expected to remain serviceable for more than 10 years, considering that it is charged and discharged once in a day at room temperature (25 deg. C).
  • Long Life Span
    Olivine-type lithium iron phosphate batteries with excellent thermal stability and storage characteristics are used in this product. The module also incorporates a self-monitoring function for the detection of any abnormalities in energy storage.
  • Compact Design
    The height is nicely designed in 3U, in favor of standard industrial applications.
  • High Scalability
    Multiple energy storage modules can be connected in parallel, and the capacity can be customized according to the intended use.

1.2. Safety Precautions
Sunsilk products are designed with full consideration of safety. However, all electrical appliances can be dangerous if used inappropriately; it can cause a fire or electric shock that leads to severe injury or death. For your protection, please read these safety precautions thoroughly.
Definitions of Symbols:
Below are symbols used in this manual and the unit.
Please read through the following definitions before reading the manual.
DANGER Warning
If you ignore these instructions, it can lead to a fire or electric shock causing serious injury or death.
WARNING Caution
If you ignore these instructions, it can lead to electric shock or other accidents causing injury or harm to nearby products.
DANGER Warning
If you do not follow the instructions below, it can lead to a f ire or electric shock causing serious injury or death.
Instruction
Use designated cable. A non-designated cable use can cause electric shock. Be sure to use the cable designated in this manual.
 Prohibited
Do not damage cables. If you damage a cable, it can cause a fire or electric shock.

  1. Do not work over or damage a cable.
  2. Do not place heavy objects on a cable or pull the cable.
  3. Do not place a heater near the cable, which may result in the cable overheating.
  4. Do not tuck down a cable when installing in a rack.
  5. When you unplug a communication cable, be sure to hold the plug and pull it.

Instruction
Connect a power cable and communication cable properly.

  1. If you connect a power cable improperly, contact resistance will increase and it may damage the parts or cause a fire.
  2. Insert the connector of the communication cable all the way in. If it is connected improperly, the system may be deactivated.

Prohibited
Do not install in a closed area. If the module/controller is installed in a closed area with no air-conditioning, heat may build up inside the set and cause a fire.
Prohibited
Do not place the set in direct sunlight or near a heater. Doing so can cause deformation, a breakdown, or a fire. Pay extra attention when you place the set near windows.
Prohibited
Do not install the set where excessive oil smoke, steam, moisture or dust is contained in the air. If the set is installed in such a place, it may cause a fire or electric shock.
Instruction

  1. Wear insulating gloves and protection glasses during installation and connection
  2. Wear insulating gloves and protection glasses during installation and connection of the set to prevent electric shock or other injuries.

No Wet

  1. Do not allow water and/or foreign objects inside the module
  2. Water or foreign objects inside the module can cause a fire or electric shock.
  3. Should this occur, however, turn off the “POWER ON/OFF” switch on the controller to shut down, and remove the power connector from the POWER CONNECTOR terminal of the module.

Do not disassemble
Do not open the set unnecessarily. Opening and modifying the set can cause a fire or electric shock.
WARNING Caution
If you ignore any of the following instructions, it can cause injury or damage to nearby products.
Prohibited
Do not cover the vent. If the vent is covered, heat may build up inside the set and cause a fire.

  1. Do not put the set in a poorly ventilated and narrow space.
  2. Remove any dust buildup in the vent.
  3. Do not place the set upside down or sideways.
  4. Do not place on a shag carpet or bed.
  5. Do not cover the vent with a cloth, etc.

Instruction
Install in a stable place.

  1. If you install the set in an unstable place, such as an unstable rack, it may fall and cause injury.
  2. Do not install upside down or sideways. The set may drop and cause injury.

Instruction
Use the designated packaging materials for transportation. If you do not use the designated packaging materials, the packaging material may be damaged by vibration during transportation and it may cause injury.
Instruction
Install based on the designated way of installation. If you do not follow the designated way of installation, the set may drop due to the strength poverty and can cause injury.
Instruction
Fix a rack to the floor. If a rack falls by the weight of the set, it may cause serious injury or death.
No Wet
Do not touch with wet hands If you touch the set with wet hands, it may cause electric shock.
Instruction
Install other equipment or accessories properly. If you inadequately install other equipment or accessories sold separately, they may fall and cause injury. When you install any of the following accessories, install it properly based on this manual.
Bracket
Power connector
Instruction
Set up cables properly If your foot is caught by a cable, the set may fall and cause injury. Connect and
install cables carefully.
Instruction
Power off at a malfunction In case any malfunction happens, please turn off the POWER ON/OFF switch in order to shut down, and remove the power connector from the POWER CONNECTOR terminal of the module.
Prohibited
Do not put anything, stand or sit on the set If you put anything on the set, it may fall and cause injury.
Also, if it is used as a stool, for example, it may topple and cause injury.
Instruction
Follow related laws or ordinances for disposal. When you dispose of this product, do not dispose as general or household waste.
Instruction
Disposal with specified method Contact technical vendor when you discard. Do not disassemble, destroy, or disposal in the fire.
WARNING Danger
If liquid is leaking from the module, observe the following measures.

  • Do not allow the liquid to come in contact with skin or clothing.
  • If the liquid comes in contact with skin or clothing, wash thoroughly with plenty of water.
  • If the liquid gets into the eyes or mouth, flush immediately with clean water, and immediately seek medical treatment.
  • Contact customer service.

1.3. Precautions for Use

  • In the case of a failure, or any of the abnormalities shown below, turn off the set and contact Sunsynk customer services.
    1. Abnormal sound, smell or smoke.
    2. Water or particles inside the product.
    3. The product is dropped, or the cabinet is damaged.
  • Charge and discharge the product according to the control signals of the controller. Do not hammer a nail or punch a hole in the product.
  • Replace the module with a new one if discharge time at room temperature is noticeably short, even from fully charged.

DO NOT:

  • Disassemble.
  • Modify the product (Modification may destroy the protection function inside, or cause abnormal charge/ discharge, heat generation, gas eruption, or fire.).
  • Touch the rear output terminal except for installation.
  • Throw the product into fire or heat, or otherwise expose the set to heat or naked flame.
  • Submerge the product in liquid or allow it to become wet.
  • Apply strong shock, crush, or drop.
  • Use for medical purposes.
  • Place any foreign objects inside.
  • Connect any devices that exceed the operating voltage and current range.
  • Do not unplug the power connector from the POWER CONNECTOR terminal while power is turned on.

Specification and Functions

2.1. System Introduction
L051100-A Energy Storage System is consisted of 2 sets of M025100-A modules manufactured by Sunsynk. In each M025100-A, there are 8 pcs of 100 Ah LFP cell originated from CATL. The overall system also provides standard communication port, i.e. CAN and RS485, to monitor the working status and communicate with upper machine as well as the Power Conversion System (PCS) in front. The system schematic drawing is presented in Figure 1.

SUNSYNK L051100-A Power Lite Lithium Battery System - Fig1

2.2. Dimensions
L051100-A dimensions are presented in Figure 2. It is well designed for 19 inch cabinet.

SUNSYNK L051100-A Power Lite Lithium Battery System - Fig2

2.3. Specifications 

pacifications of L051100-A 
Cell TypeLiFePO4 (LFP)
Rated Voltage51.2 V
Rated Capacity100Ah
Rated Energy5.12kwh
Packing1P16S
Working Voltage Range44.8~57.6V
Standard Charging Current50A
Max. Continuous Charging Current50A
Standard Discharging Current50A
Max. Continuous Discharging Current100A(1C, 25  ±2°C)
Max. Pulse Discharging Current200A(2C, 30S, 25°C ±2°C SOC≥40%)
Standard Charging Method0.5C CC to 57.6V, CV at 57.6V till current is 0.05C
Working Temp.Charging: 0° ~50 Discharging: -20°C~55°C
Working ROH20%~80%
Storage Temp.-20~50°C
Self-discharging rate≤5%(25 , 50% SoC)
SoC @ end of product line40%
Insulation Resistance>100MΩ
Voltage Difference in each module≤20mV
Inner Resistance of single Cell0.34±0.05mΩ(fresh cell 30~40% SoC)
WeightApprox. 48kg
Dimension440mm*530mm*132mm(not include connector MSD and other parts)

2.4. Installing Instructions
Some instructions for installing the equipment must be followed.
2.4.1. Definition of Voltage Sampling Connector

PINWire No.SignalWire size (mm²Remarks
1B0Signal0.3Cell #1-
2B2+Signal0.3Cell #2+
3B4+Signal0.3Cell #4+
4B6+Signal0.3Cell #6+
5B8+Signal0.3Cell #8+
6B10+Signal0.3Cell #10+
7B12+Signal0.3Cell #12+
8B14+Signal0.3Cell #14+
9B16+Signal0.3Cell #16+
10NCNCNCNC
11B1+Signal0.3Cell #1+
12B3+Signal0.3Cell #3+
13B5+Signal0.3Cell #5+
14B7+Signal0.3Cell #7+
15B9+Signal0.3Cell #9+
16B11+Signal0.3Cell #11+
17B13+Signal0.3Cell #13+
18B15+Signal0.3Cell #15+

2.4.2. Definition of Temp. Sampling Connector 

PINWire No.SignalWire size (mm²)Remarks
1T1+Signal0.3Temp. #1+
2T2+Signal0.3Temp. #2+
3T3+Signal0.3Temp. #3+
4T4+Signal0.3Temp. #4+
5T1-Signal0.3Temp. #1-
6T2-Signal0.3Temp. #2-
7T3-Signal0.3Temp. #3-
8T4-Signal0.3Temp. #4-

2.4.3. Front View 

SUNSYNK L051100-A Power Lite Lithium Battery System - Fig3

ItemNameModelRemarks
1SOC LED x4
2Alarm LED
3RUN LED
4Dialer
5Communication portRJ11RS232 To upper machine
6Communication port *2RJ45CAN To PCS RS485 Internal Connection
7ResetWaken system from malfunction status
8Dry Contact
9Power On/Off Switch
10Port Negative x2PSR6XABBlack 5.7, 25mm2
11Port Positive x2PSR6XBBOrange 5.7, 25mm2
12GNDM6Yellow-Green, 10AWG

2.4.4 Port RS485 and RS232 

SUNSYNK L051100-A Power Lite Lithium Battery System - Fig4

Description
CANPin 1: CAN-H Pin 5: CAN-L
Pin 2, 3, 4, 6, 7: NC
Pin 8: GND
RS485Pin 1, 4, 5: NC Pin 2, 7: RS485-A Pin 3, 6: RS485-B Pin 8: GND
RS232Pin 1, 2, 6: NC
Pin 3: BMS transmit; Computer receiver Pin 4: BMS receiver; Computer transmit Pin 5: GND

Installation

3.1. DC Cable Requirements 

SizeOuter DiameterMax. VoltageMax. Current
21-33 mm²10-12 mm1000 V120 A

WARNING Caution
DC cable must be a multicore wire.
3.2. DC Cable
WARNING Danger

  • Turn off system before doing electrical connection
  • Ensure all the cables are in electrical safe condition

3.2.1 Material List

SUNSYNK L051100-A Power Lite Lithium Battery System - Fig5

3.2.2 Steps 

  1. Put wire through isolation cap and TailSUNSYNK L051100-A Power Lite Lithium Battery System - Fig6Hood.
  2. Swipe outer isolation layer of DC cableSUNSYNK L051100-A Power Lite Lithium Battery System - Fig7.
  3. The is used for the positive, and the negative for tieback contact. The end of the cable is bunched at the terminal using a wire clamp.SUNSYNK L051100-A Power Lite Lithium Battery System - Fig8
  4. Tighten the isolation cap and plug contact.SUNSYNK L051100-A Power Lite Lithium Battery System - Fig9
  5. Put the positive and negative plug on to the system and tighten it.
  6. Use isolation cap for unused DC plug.

3.3. DC Cable Connection
3.3.1 Single Unit 

SUNSYNK L051100-A Power Lite Lithium Battery System - Fig10

3.3.2 Multi-Units in Parallel (4 sets as an example)

SUNSYNK L051100-A Power Lite Lithium Battery System - Fig11

Master Pack and Slave Pack L051100-A can be used as single unit as well as multi-units (inparallel) mode. The customer must inform supplier if multi-units mode is required. The MasterPack can be used individually, but Slave Pack cannot be used individually.
3.3.3. Method to set up Master Pack and Slave Pack

SUNSYNK L051100-A Power Lite Lithium Battery System - Fig12

Master/slave machine dial code diagram:

SUNSYNK L051100-A Power Lite Lithium Battery System - Fig13

 Power ON and OFF

4.1. Instruction
Please double check the Precautions for use in section 1.3.
4.1.1 System Power ON

  • Installation (including DC cable, communication wire connection and dialer switch) is properly down.
  • Press Power Switch button, green LED should be twinkling and then turn into function mode. (system status can be red from LED signal, as shown below)

4.1.2. System Power OFF
Attention: It must be confirmed that the system is off before taking off DC cables. Press Power Switch button
Green LED should be twinkling and then turn into stop mode
4.1.3. Sleep and wake up function

NumberSleep ConditionWake up ConditionMark
1Forced sleep by upper computerReset button
 2 Forced sleep by soft switch Soft switch,Only those equipped with soft switch can pass the call Wake up
 3Total Voltage is lower than 48V or monomer is lower than 2.8V, and continuous No charge and discharge current for 4 hours, no communication goes to sleepReset button, Soft switch, Communicatio n, Charging Only those equipped with soft switch can pass the call Wake up

4.1.4. Buzzer function

  • 0.25s per 1s in case of fault
  • 0.25s per 2S during protection

4.1.5. System Status Instruction
There are 6 LED indicator, 4 green LED gives status of SoC, 1 red Alarm LED and 1 green Running Status LED (indicating charging, discharging etc.)

SUNSYNK L051100-A Power Lite Lithium Battery System - Fig15

StatusNormal/Warning/ProtectionRUNALMSoCRemarks
MOTOsafety MPAAS1P1 Plug-In OBD Vehicle Tracker - GreenMOTOsafety MPAAS1P1 Plug-In OBD Vehicle Tracker - GreenMOTOsafety MPAAS1P1 Plug-In OBD Vehicle Tracker - GreenMOTOsafety MPAAS1P1 Plug-In OBD Vehicle Tracker - GreenMOTOsafety MPAAS1P1 Plug-In OBD Vehicle Tracker - Green
Power OffHibernatenonononononoALL No
StandbyNormalTwinkle 1noReal SoCStandby
WarningTwinkle 1no
ChargingNormal 1Twinkle2no
WarningTwinkle 2no
OverchargingTwinkle 1noOvercharing ALM no
Overheat, Over-current, Low Temp.Twinkle 1Twinkle 2
DischargingNormalContinuousno
WarningContinuousnoOver-current, ALM no
Over dischargingTwinkle Ino
Overheat, Low Temp., Over-cun ent ShortcutTwinkle ITwinkle 2
Charging/
Discharging/
Standby
AbnormalTwinkle at current
state
Twinkle 3If the slave is disconnected or disconnected, the slave ALM light Twinkle;
FaultnoContinuousnonononoFault refers to the hardware fault of BMS voltage car yang device, charging MOS damage, temperature sensor disconnection. etc

4.1.6 LED Twinkle Status

StatusOnOff
Twinkle 10.25S3.75S
Twinkle 20.5S0.5S
Twinkle 30.5S1.5S

4.1.7. SoC indicator

SoCLED
MOTOsafety MPAAS1P1 Plug-In OBD Vehicle Tracker - GreenMOTOsafety MPAAS1P1 Plug-In OBD Vehicle Tracker - GreenMOTOsafety MPAAS1P1 Plug-In OBD Vehicle Tracker - GreenMOTOsafety MPAAS1P1 Plug-In OBD Vehicle Tracker - Green
LED1LED2LED3LED4
0-25%OnOFFOFFOFF
25%-50%OnOnOFFOFF
50%,-75%OnOnOnOFF
75%,w100%OnOnOnOn

Transportation and Storage

5.1. Transportation
It is forbidden to encounter serious vibration and shock during transportation.
5.2. Storage
If the system is not placed to use, the system must be properly stored. Otherwise, if any issues, Sunsynk

  • It should be stored in 60% SoC status.
  • It should be stored at ventilation environment, Temp. < 35 deg C, RoH <65%.
  • It should be stored avoiding humid condition.
  • It should be stored in place where they can be monitored by professionals.

Disclaimer

It should be noted that Sunsynk shall not be liable if any necessary materials are added to this user’s manual without further inform of customers.

SUNSYNK logoGlobal Tech China Ltd, 3 Floor, Wai Yip Industrial Building.171 Wai Yip Street,
Kwun Tong, Kowloon, Hong Kong. Tel: +852 2884 4318 Fax:
+8522884 4816
www.sunsynk.com
sales@globaltech-china.com
www.globaltechhk.com

Documents / Resources

SUNSYNK L051100-A Power Lite Lithium Battery System [pdf] Owner's Manual
L051100-A, Power Lite Lithium Battery System, L051100-A Power Lite Lithium Battery System, Lite Lithium Battery System, Lithium Battery System, Battery System

References

Leave a comment

Your email address will not be published. Required fields are marked *