SUMSUNG VCTRL02P-1 BACnet Gateway
Specifications
- Product Model: VCTRL02P-1 BACnet Gateway
Product Information
The VCTRL02P-1 BACnet Gateway is designed to provide seamless integration for BACnet systems. It allows for efficient communication between different building automation devices and systems, enabling centralized control and monitoring.
BACnet Gateway
FEATURES AND FUNCTIONS
- Control gateway that allows control and monitoring of Lennox Powered by Samsung HVAC systems via BACnet /IP
- Individual/Group control of up to 256 indoor units
- Operation mode, temperature setting, airflow direction, fan speed, temperature restriction settings, unoccupied mode setting, and discharge air temperature setting (for applicable duct unit models).
- Restrict use of wireless/wired remote controllers, mode, temperature, and set point.
- Outdoor and indoor unit cycle monitoring
- Convenient digital display allows for easy initial set up
- SD memory card slot for data storage and software updating (daily automatic backup, SD card purchased separately)
- LAN connection for upper level control options
- Available sophisticated control logic allows programming outputs based on various system inputs
- Dynamic security management
- Operation and error history management
- Maximum current control of outdoor unit(s) to limit current (50% – 100% of design current) adjustable at outdoor unit or VCTRL02P-1 (does not apply to all system models)
- Supports multiple user access (different usernames and access levels)
- Various user management level settings (HVAC system access, gateway permission access)
- Unoccupied room control settings adjustment capability (for compatible units) Web Server Function
- Remote control with a public IP address via internet connection
- No management software required – PC-independent management through web browser (optimized for Internet Explorer)
- Multiple user accounts can be setup with the ability to specify what unit(s) each individual can monitor and control and what level of control permission is allowed.
- 2D Floorplan layout option for simplified project viewing.
Schedule Control Function Through Web Browser
- Up to 256 schedule settings
- Weekly and daily schedule setting
- Wireless/wired remote controller restriction setting
- Digital outputs can be incorporated into scheduling
Advanced Programmable Control Logic Setting
- Specify various system control point inputs (indoor units, outdoor units, DI, DO) and operators (=, >, <, ≤, ≥, ≠) to manipulate system operation (indoor units, outdoor units, DI, DO) based on the status of the specified variables.
Advanced Heat Pump Auto Changeover Logic
- Optional “weighted averaging” or “representative” setting for heat pump systems to provide optimal auto changeover while in Auto mode.
External Contact Interface
- Full indoor unit control with simple contact input (emergency/lock)
- 8 additional digital input terminals for monitoring options
- State output (operation/error) for synchronous control
- 6 general purpose outputs to control other components (on: 12VDC out; off: no voltage)
- Digital inputs and digital outputs can be incorporated into control logic
- Digital outputs can be incorporated into control logic and daily schedules to control other devices
Energy Management / Power Distribution Function
- Ability to monitor, track, and query energy use from indoor unit(s) and systems with 37Y68 VCTRL08P-1 electricity meter interface module (purchased separately, requires 3rd party watt-hour meters with pulse output).
- When used with SNET 3 software, detailed PDF report generation is possible
- User defined daily time periods for energy use reports to accommodate on/off peak energy billing.
- Export energy usage and other data to Excel file
NOTE − Due to Lennox’ ongoing commitment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability. Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury. Installation and service must be performed by a qualified installer and servicing agency.
History Management
- Storage of all operation commands from gateway and other system controls (saves to SD card purchased separately).
- Storage of all error events for review (saves to SD card purchased separately).
- Storage of all operation logic control events (saves to SD card purchased separately).
- Error alerts via email that contain: error code, error explanation, units affected, time and date of error occurrence, and error status.
Specifications
- Fixed port number: 47808 (can be changed from 0 – 65535)
- Network ID can be assigned 1-16 (this number will determine device ID of gateway and all equipment)
- The gateway shall support BACnet/IP and provide functions to monitor status and control Lennox Powered by Samsung VRF, Mini-Splits, and Chillers.
- The gateway shall monitor status and control Lennox Powered by Samsung systems only via web client, BMS, and/or Samsung SNET 3 software.
- DC 12V, 3A power provided by AC/DC adapter (input 110-240VAC 50/60Hz, provided with gateway)
- Direct connection to VRF and Mini-Split MMLD and MMPD single zone outdoor units
- 16 AWG X 2 copper stranded, shielded cable between Samsung equipment and controls is recommended for proper operation
- Maximum number of RS485 connections:
- Maximum 75 Touch Central Controllers (37Y72 VCTRL01P-1) to 1 gateway
- Maximum 15 Touch Central Controllers (37Y72 VCTRL01P-1) to a single gateway channel
- Maximum 16 systems to a single channel (5 total)
- Maximum 16 Chiller FCU Interface Modules (37Y81 VCTRL05P-1) to a single channel (5 total, each 37Y81 VCTRL05P-1 supports up to 16 37Y80 VCTRL04P-1 FCU Kits)
- Maximum 80 Chiller FCU Interface Modules (37Y81 VCTRL05P-1) connected direct (5 ports, 16 X 37Y81 VCTRL05P-1 per port)
- Maximum 128 indoor units on a single gateway channel (MSB, air handlers)
- Maximum 256 indoor units (MSB, air handlers to one gateway
- Maximum 8 37Y68 VCTRL08P-1 Energy Meter Interface Modules per gateway (must connect to CH4 (COM5) on gateway)
- Maximum 8 37Y68 VCTRL08P-1 Energy Meter Interface Modules per gateway (can connect to same channel as VRF outdoor units on gateway)
- Digital inputs and outputs:
- DI terminals (X 10): Dry input (0V)
- DO terminals (X 8): 12VDC, maximum 200 mA
- Segment capability
- Segment requests supported window size: 1476
- Segment responses supported window size: 1476
- BTL Certification to BACnet standard ISO 16484-5 protocol revision 1.12
- BACnet IP Data Link Layer (Annex J)
- BACnet Stanardized Device Profile (Annex L): BACnet Application Specific Controller (B-ASC)
- Refer to controls technical engineering handbook for more information
Installation with Direct Connection to VRF Outdoor Units
Installation with 37Y68 VCTRL08P-1 – Energy Management
Indoor unit
Instance Number |
Object |
Object Type |
Object Name | Unit | Status value | |||
Inactive | Active | |||||||
Text-1 | Text-2 | Text-3 | Text-4 | Text-5 | ||||
1 | Indoor temperature | AI | AC_RoomTemp_xx_xxxxxx | °C(°F) | ||||
2 | Set temperature | AV | AC_Temp_Set_xx_xxxxxx | °C(°F) | ||||
3 | Setting lower temperature limit | AV | AC_Cool_LimitTemp_xx_xxxxxx | °C(°F) | ||||
4 | Setting upper temperature limit | AV | AC_Heat_LimitTemp_xx_xxxxxx | °C(°F) | ||||
5 | The power value of an indoor unit after the basic date | AI | AC_Baseline_kWh_xx_xxxxxx | kWh | ||||
6 | The number of hours usage of an indoor unit after the basic date | AI | AC_Baseline_Minute_xx_xxxxxx | Minute | ||||
7 | Power value within period | AI | AC_Period_kWh_xx_xxxxxx | kWh | ||||
8 | The number of hours usage of an indoor unit within period | AI | AC_Period_Minute_xx_xxxxxx | Minute | ||||
9(**) | Power On/Off | BV | AC_Power_xx_xxxxxx | Off | On | |||
10 | Applying lower temperature limit setting | BV | AC_Cool_Limit_set_xx_xxxxxx | False | True | |||
11 | Applying upper temperature limit setting | BV | AC_Heat_Limit_set_xx_xxxxxx | False | True | |||
12(**) | Filter sign status | BI | AC_FilterSign_xx_xxxxxx | False | True | |||
13(**) | Filter sign reset | BO | AC_FilterSign_Reset_xx_xxxxxx | False | True | |||
14(**) | Operation mode status | MV | AC_Operation_Mode_xx_xxxxxx | Auto | Cool | Heat | Fan | Dry |
15 | Fan speed status | MV | AC_FanSpeed_xx_xxxxxx | Auto | Low | Mid | High | |
16 | Air flow direction status | MV | AC_FanFlow_xx_xxxxxx | None | Vertical | Horizontal | All | |
17(**) | Operation mode limit status | MV | AC_Mode_Limit_xx_xxxxxx | No Limit | Cool Only | Heat Only | ||
18(**) | Remote controller limit status | MV | AC_Remocon_Limit_xx_xxxxxx | Enable RC | Disable RC | Conditional RC | ||
19(**) | Integrated error code of both indoor unit and outdoor unit | AI | AC_Error_Code_xx_xxxxxx | Refer to Samsung integrated error code list | ||||
20(*) | SPI setting | BV | AC_SPI_xx_xxxxxx | False | True | |||
21(*) | Human sensor setting | BV | AC_MDS_xx_xxxxxx | False | True | |||
22(**) | AC indoor notify | NC | AC_Notify_xx_xxxxxx | When the error occurred, send event to list of destination in the recipient_list. (Max : 8) | ||||
23(**) | Discharge cooling set temperature | AV | AC_DisCoolTemp_Set_xx_xxxxxx | °C(°F) | ||||
24(**) | Discharge heating set temperature | AV | AC_DisHeatTemp_Set_xx_xxxxxx | °C(°F) | ||||
25(**) | Discharge current temperature | AI | AC_DisCurrentTemp_xx_xxxxxx | °C(°F) |
Temperature setting range can be different depending on model. The standard range is noted below:
- Auto: 18~30°C (64~86°F)
- Cool: 18~30°C (64~86°F)
- Heat: 16~30°C (60~86°F)
- Fan: Temperature cannot be adjusted
- Dry: 18~30°C (64~86°F)
(*) Mark is optionally supported. For OAP Duct unit (**) mark is supported.
VRF Multi-position AHU and AHU kit
Instance Number |
Object |
Object Type |
Object Name | Unit | Status value | |||
Inactive | Active | |||||||
Text-1 | Text-2 | Text-3 | Text-4 | Text-5 | ||||
1 | Indoor temperature | AI | AHU_RoomTemp_xx_xxxxxx | °C(°F) | ||||
2 | Set temperature | AV | AHU_Temp_Set_xx_xxxxxx | °C(°F) | ||||
3 | Setting lower temperature limit | AV | AHU_Cool_LimitTemp_xx_xxxxxx | °C(°F) | ||||
4 | Setting upper temperature limit | AV | AHU_Heat_LimitTemp_xx_xxxxxx | °C(°F) | ||||
5 | The power value of an indoor unit after the basic date | AI | AHU_Baseline_kWh_xx_xxxxxx | kWh | ||||
6 | The number of hours usage of an indoor unit after the basic date | AI | AHU_Baseline_Minute_xx_xxxxxx | Minute | ||||
7 | Power value within period | AI | AHU_Period_kWh_xx_xxxxxx | kWh | ||||
8 | The number of hours usage of an indoor unit within period | AI | AHU_Period_Minute_xx_xxxxxx | Minute | ||||
9 | Power On/Off | BV | AHU_Power_xx_xxxxxx | Off | On | |||
10 | Applying lower temperature limit setting | BV | AHU_Cool_Limit_set_xx_xxxxxx | False | True | |||
11 | Applying upper temperature limit setting | BV | AHU_Heat_Limit_set_xx_xxxxxx | False | True | |||
12 | Filter sign status | BI | AHU_FilterSign_xx_xxxxxx | False | True | |||
13 | Filter sign reset | BO | AHU_FilterSign_Reset_xx_xxxxxx | False | True | |||
14 | Operation mode status | MV | AHU_Operation_Mode_xx_xxxxxx | Auto | Cool | Heat | Fan | Dry |
15 | Operation mode limit status | MV | AHU_Mode_Limit_xx_xxxxxx | No Limit | Cool Only | Heat Only | ||
16 | Remote controller limit status | MV | AHU_Remocon_Limit_xx_xxxxxx | Enable RC | Disable RC | Conditional RC | ||
17 | Integrated error code of both indoor unit and outdoor unit | AI | AHU_Error_Code_xx_xxxxxx | Refer to Samsung integrated error code list | ||||
18(*) | Discharge cooling set temperature | AV | AHU_DisCoolSetTemp_xx_xxxxxx | °C(°F) | ||||
19(*) | Discharge heating set temperature | AV | AHU_DisHeatSetTemp_xx_xxxxxx | °C(°F) | ||||
20(*) | Discharge current temperature | AI | AHU_Dis_CurrentTemp_xx_xxxxxx | °C(°F) | ||||
21(**) | Humidification setting | BV | AHU_Humidification_xx_xxxxxx | Off | On | |||
22(**) | Outdoor air intake setting | BV | AHU_OAIntake_xx_xxxxxx | Off | On | |||
23(**) | Outdoor cooling setting | BV | AHU_OutdoorCool_xx_xxxxxx | Off | On | |||
24 | Fan speed status | MV | AHU_FanSpeed_xx_xxxxxx | Low | Mid | High | ||
25(**) | Set humidity status | MV | AHU_SetHumidity_xx_xxxxxx | Low | Mid | High | ||
26(**) | Current humidity status | MI | AHU_CurrentHumidity_xx_xxxxxx | Low | Mid | High | ||
27 | AHU Notify | NC | AHU_Notify_xx_xxxxxx | When the error occurred, send event to list of destination in the recipient_list. (Max : 8) |
* Not supported as standard, additional sensors and unit configuration required. ** Not supported for North American AHU models.
VRF Chiller
Instance Number |
Object |
Object Type |
Object Name | Unit | Status value | |||
Inactive | Active | |||||||
Text-1 | Text-2 | Text-3 | Text-4 | Text-5 | ||||
1 | Chilled Water Temperature | AI | MC_WaterTemp_xx_xxxxxx | °C(°F) | ||||
2 | Set temperature | AV | MC_WaterTemp_Set_xx_xxxxxx | °C(°F) | ||||
3 | Demand limit setting | AV | MC_Demand_Set_xx_xxxxxx | % | ||||
4 | The number of hours usage of an indoor unit after the basic date | AI | MC_Baseline_Minute_xx_xxxxxx | Minute | ||||
5 | The number of hours usage of an indoor unit within period | AI | MC_Period_Minute_xx_xxxxxx | Minute | ||||
6 | Power On/Off operation | BV | MC_Power_xx_xxxxxx | Off | On | |||
7 | Water Law | BO | MC_Water_Law_xx_xxxxxx | False | True | |||
8 | Quiet | BV | MC_Quiet_xx_xxxxxx | Off | On | |||
9 | Forced Fan | BV | MC_Forced_Fan_xx_xxxxxx | Off | On | |||
10 | Operation mode status | MV | MC_Operation_Mode_xx_xxxxxx | Cool | Heat | Cool Storage | Hot Water | |
11 | Remote controller limit status | MV | MC_Remocon_Limit_xx_xxxxxx | Enable RC | Disable RC | Conditional RC | ||
12 | Integrated error code | AI | MC_Error_Code_xx_xxxxxx | |||||
13 | VRF CHILLER Notify | NC | MC_Notify_xx_xxxxxx | When the error occurred, send event to list of destination in the recipient_list. (Max : 8) |
BACnet Device Object does not support master function of VRF CHILLER.
Digital input / output
Instance Number |
Object |
Object Type |
Object Name | Unit | Status value | |||
Inactive | Active | |||||||
Text-1 | Text-2 | Text-3 | Text-4 | Text-5 | ||||
1 | Digital Input 1 | BI | DI_01_xx_xx (BACnet Gateway Reserved) | Off | On | |||
2 | Digital Input 2 | BI | DI_02_xx_xx (BACnet Gateway Reserved) | Off | On | |||
3 | Digital Input 3 | BI | DI_03_xx_xx | Off | On | |||
4 | Digital Input 4 | BI | DI_04_xx_xx | Off | On | |||
5 | Digital Input 5 | BI | DI_05_xx_xx | Off | On | |||
6 | Digital Input 6 | BI | DI_06_xx_xx | Off | On | |||
7 | Digital Input 7 | BI | DI_07_xx_xx | Off | On | |||
8 | Digital Input 8 | BI | DI_08_xx_xx | Off | On | |||
9 | Digital Input 9 | BI | DI_09_xx_xx | Off | On | |||
10 | Digital Input 10 | BI | DI_10_xx_xx | Off | On | |||
11 | Digital Output 1 | BO | DO_01_xx_xx (BACnet Gateway Reserved) | Off | On | |||
12 | Digital Output 2 | BO | DO_02_xx_xx (BACnet Gateway Reserved) | Off | On | |||
13 | Digital Output 3 | BO | DO_03_xx_xx | Off | On | |||
14 | Digital Output 4 | BO | DO_04_xx_xx | Off | On | |||
15 | Digital Output 5 | BO | DO_05_xx_xx | Off | On | |||
16 | Digital Output 6 | BO | DO_06_xx_xx | Off | On | |||
17 | Digital Output 7 | BO | DO_07_xx_xx | Off | On | |||
18 | Digital Output 8 | BO | DO_08_xx_xx | Off | On |
Caution
- You may use ALL_OFF command to turn on all the indoor units but it is not recommended.
- If communication error occurs on devices such as SIM, On/Off Controller, Interface Module etc., other functions such as power distribution may also create a problem. You must have BMS system to check the errors and you must take action immediately.
Interface module (outdoor unit)
Instance Number | Object | Object Type | Object Name | Unit | Status value | |||
Inactive | Active | |||||||
Text-1 | Text-2 | Text-3 | Text-4 | Text-5 | ||||
1 | Outside temperature | AI | ODU_Outside_Temp_xx_xxxx | °C(°F) | ||||
2(*) | Cool capacity compensation | AV | ODU_Cool_Compensation_xx_ xxxx | 0 : 5~7°C(41~45°F) 1 : 7~9°C(41~48°F) 2 : 9~11°C(48~52°F) 3 : 10~12°C(50~54°F) 4 : 11~13°C(52~55°F) 5 : 12~14°C(54~57°F) 6 : 13~15°C(55~59°F) 14 : Auto control (from ODU) | ||||
3(*) | Heat capacity compensation | AV | ODU_Heat_Compensation_xx_ xxxx | 0 : 25kg/cm² 1 : 26kg/cm² 2 : 27kg/cm² 3 : 28kg/cm² 4 : 29kg/cm² 5 : 30kg/cm² 6 : 31kg/cm² 7 : 32kg/cm² 8 : 33kg/cm² 14 : Auto control (from ODU) | ||||
4 | Compressor status | BI | ODU_Comp_Status_xx_xxxx | False | True | |||
5 | Interface module error code | AI | Repeater_Error_Code_xx_xxxx | Refer to the list of the integrated error code | ||||
6 | Interface module notify | NC | IM_Notify_xx_xxxx | When the error occurred, send event to list of destination in the recipient list. (Max : 8) |
* Only available for supported models
SIM (PIM)
Instance Number | Object | Object Type | Object Name | Status value |
1 | SIM (PIM) error code | AI | SIM_Error_Code_xx_xx | Refer to list of error code |
2 | SIM (PIM) Notify | NC | SIM_Notify_xx_xx | When the error occurred, send event to list of destination in the recipient list. (Max : 8) |
BACnet Gateway)
Instance Number | Control and Monitoring | Object Type | Object Name | Status value |
1 | All device OFF | BO | ALL_OFF_xx | Inactive : All devices Off |
1 | DMS2.5 Status | AI | DMS2_Status_xx | 0: Normal 8: Emergency stop 105: Tracking in progress 108: Tracking failed 10 : DMS2.5 / BACnet communication failed |
1 | BACnet error code | AI | BACnetApp_Error_ Code_xx | BACnet error code |
2 | Gateway Notify | NC | GW_Notify_xx | When the error occurred, send event to list of destination in the recipient_list. (Max : 8) |
FAQ
Q: How do I reset the BACnet Gateway to factory settings?
A: To reset the gateway to factory settings, locate the reset button on the device and hold it down for 10 seconds until the indicator lights flash. Release the button, and the gateway will reboot with default settings.