Specifications

  • Product Model: VCTRL02P-1 BACnet Gateway

Product Information

The VCTRL02P-1 BACnet Gateway is designed to provide seamless integration for BACnet systems. It allows for efficient communication between different building automation devices and systems, enabling centralized control and monitoring.

BACnet Gateway

FEATURES AND FUNCTIONS

  • Control gateway that allows control and monitoring of Lennox Powered by Samsung HVAC systems via BACnet /IP
  • Individual/Group control of up to 256 indoor units
  • Operation mode, temperature setting, airflow direction, fan speed, temperature restriction settings, unoccupied mode setting, and discharge air temperature setting (for applicable duct unit models).
  • Restrict use of wireless/wired remote controllers, mode, temperature, and set point.
  • Outdoor and indoor unit cycle monitoring
  • Convenient digital display allows for easy initial set up
  • SD memory card slot for data storage and software updating (daily automatic backup, SD card purchased separately)
  • LAN connection for upper level control options
  • Available sophisticated control logic allows programming outputs based on various system inputs
  • Dynamic security management
  • Operation and error history management
  • Maximum current control of outdoor unit(s) to limit current (50% – 100% of design current) adjustable at outdoor unit or VCTRL02P-1 (does not apply to all system models)
  • Supports multiple user access (different usernames and access levels)
  • Various user management level settings (HVAC system access, gateway permission access)
  • Unoccupied room control settings adjustment capability (for compatible units) Web Server Function
  • Remote control with a public IP address via internet connection
  • No management software required – PC-independent management through web browser (optimized for Internet Explorer)
  • Multiple user accounts can be setup with the ability to specify what unit(s) each individual can monitor and control and what level of control permission is allowed.
  • 2D Floorplan layout option for simplified project viewing.

Schedule Control Function Through Web Browser

  • Up to 256 schedule settings
  • Weekly and daily schedule setting
  • Wireless/wired remote controller restriction setting
  • Digital outputs can be incorporated into scheduling

Advanced Programmable Control Logic Setting

  • Specify various system control point inputs (indoor units, outdoor units, DI, DO) and operators (=, >, <, ≤, ≥, ≠) to manipulate system operation (indoor units, outdoor units, DI, DO) based on the status of the specified variables.

Advanced Heat Pump Auto Changeover Logic

  • Optional “weighted averaging” or “representative” setting for heat pump systems to provide optimal auto changeover while in Auto mode.

External Contact Interface

  • Full indoor unit control with simple contact input (emergency/lock)
  • 8 additional digital input terminals for monitoring options
  • State output (operation/error) for synchronous control
  • 6 general purpose outputs to control other components (on: 12VDC out; off: no voltage)
  • Digital inputs and digital outputs can be incorporated into control logic
  • Digital outputs can be incorporated into control logic and daily schedules to control other devices

Energy Management / Power Distribution Function

  • Ability to monitor, track, and query energy use from indoor unit(s) and systems with 37Y68 VCTRL08P-1 electricity meter interface module (purchased separately, requires 3rd party watt-hour meters with pulse output).
  • When used with SNET 3 software, detailed PDF report generation is possible
  • User defined daily time periods for energy use reports to accommodate on/off peak energy billing.
  • Export energy usage and other data to Excel file

NOTE − Due to Lennox’ ongoing commitment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability. Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury. Installation and service must be performed by a qualified installer and servicing agency.

History Management

  • Storage of all operation commands from gateway and other system controls (saves to SD card purchased separately).
  • Storage of all error events for review (saves to SD card purchased separately).
  • Storage of all operation logic control events (saves to SD card purchased separately).
  • Error alerts via email that contain: error code, error explanation, units affected, time and date of error occurrence, and error status.

Specifications

  • Fixed port number: 47808 (can be changed from 0 – 65535)
  • Network ID can be assigned 1-16 (this number will determine device ID of gateway and all equipment)
  • The gateway shall support BACnet/IP and provide functions to monitor status and control Lennox Powered by Samsung VRF, Mini-Splits, and Chillers.
  • The gateway shall monitor status and control Lennox Powered by Samsung systems only via web client, BMS, and/or Samsung SNET 3 software.
  • DC 12V, 3A power provided by AC/DC adapter (input 110-240VAC 50/60Hz, provided with gateway)
  • Direct connection to VRF and Mini-Split MMLD and MMPD single zone outdoor units
  • 16 AWG X 2 copper stranded, shielded cable between Samsung equipment and controls is recommended for proper operation
  • Maximum number of RS485 connections:
    • Maximum 75 Touch Central Controllers (37Y72 VCTRL01P-1) to 1 gateway
    • Maximum 15 Touch Central Controllers (37Y72 VCTRL01P-1) to a single gateway channel
    • Maximum 16 systems to a single channel (5 total)
    • Maximum 16 Chiller FCU Interface Modules (37Y81 VCTRL05P-1) to a single channel (5 total, each 37Y81 VCTRL05P-1 supports up to 16 37Y80 VCTRL04P-1 FCU Kits)
    • Maximum 80 Chiller FCU Interface Modules (37Y81 VCTRL05P-1) connected direct (5 ports, 16 X 37Y81 VCTRL05P-1 per port)
    • Maximum 128 indoor units on a single gateway channel (MSB, air handlers)
    • Maximum 256 indoor units (MSB, air handlers to one gateway
    • Maximum 8 37Y68 VCTRL08P-1 Energy Meter Interface Modules per gateway (must connect to CH4 (COM5) on gateway)
    • Maximum 8 37Y68 VCTRL08P-1 Energy Meter Interface Modules per gateway (can connect to same channel as VRF outdoor units on gateway)
  • Digital inputs and outputs:
    • DI terminals (X 10): Dry input (0V)
    • DO terminals (X 8): 12VDC, maximum 200 mA
  • Segment capability
    • Segment requests supported window size: 1476
    • Segment responses supported window size: 1476
  • BTL Certification to BACnet standard ISO 16484-5 protocol revision 1.12
  • BACnet IP Data Link Layer (Annex J)
  • BACnet Stanardized Device Profile (Annex L): BACnet Application Specific Controller (B-ASC)
  • Refer to controls technical engineering handbook for more information

SUMSUNG-VCTRL02P-1-BACnet-Gateway- (1)

Installation with Direct Connection to VRF Outdoor Units

SUMSUNG-VCTRL02P-1-BACnet-Gateway- (2)

Installation with 37Y68 VCTRL08P-1 – Energy Management

SUMSUNG-VCTRL02P-1-BACnet-Gateway- (3)

Indoor unit

 

Instance Number

 

 

Object

 

 

Object Type

 

 

Object Name

UnitStatus value
InactiveActive
Text-1Text-2Text-3Text-4Text-5
1Indoor temperatureAIAC_RoomTemp_xx_xxxxxx°C(°F)
2Set temperatureAVAC_Temp_Set_xx_xxxxxx°C(°F)
3Setting lower temperature limitAVAC_Cool_LimitTemp_xx_xxxxxx°C(°F)
4Setting upper temperature limitAVAC_Heat_LimitTemp_xx_xxxxxx°C(°F)
 

5

The power value of an indoor unit after the basic date 

AI

 

AC_Baseline_kWh_xx_xxxxxx

 

kWh

 

6

The number of hours usage of an indoor unit after the basic date 

AI

 

AC_Baseline_Minute_xx_xxxxxx

 

Minute

7Power value within periodAIAC_Period_kWh_xx_xxxxxxkWh
8The number of hours usage of an

indoor unit within period

AIAC_Period_Minute_xx_xxxxxxMinute
9(**)Power On/OffBVAC_Power_xx_xxxxxxOffOn
10Applying lower temperature limit

setting

BVAC_Cool_Limit_set_xx_xxxxxxFalseTrue
11Applying upper temperature limit

setting

BVAC_Heat_Limit_set_xx_xxxxxxFalseTrue
12(**)Filter sign statusBIAC_FilterSign_xx_xxxxxxFalseTrue
13(**)Filter sign resetBOAC_FilterSign_Reset_xx_xxxxxxFalseTrue
14(**)Operation mode statusMVAC_Operation_Mode_xx_xxxxxxAutoCoolHeatFanDry
15Fan speed statusMVAC_FanSpeed_xx_xxxxxxAutoLowMidHigh
16Air flow direction statusMVAC_FanFlow_xx_xxxxxxNoneVerticalHorizontalAll
17(**)Operation mode limit statusMVAC_Mode_Limit_xx_xxxxxxNo LimitCool OnlyHeat Only
18(**)Remote controller limit statusMVAC_Remocon_Limit_xx_xxxxxxEnable RCDisable RCConditional RC
 

19(**)

Integrated error code of both indoor unit and outdoor unit 

AI

 

AC_Error_Code_xx_xxxxxx

 

Refer to Samsung integrated error code list

20(*)SPI settingBVAC_SPI_xx_xxxxxxFalseTrue
21(*)Human sensor settingBVAC_MDS_xx_xxxxxxFalseTrue
22(**)AC indoor notifyNCAC_Notify_xx_xxxxxxWhen the error occurred, send event to list of destination in the recipient_list. (Max : 8)
23(**)Discharge cooling set temperatureAVAC_DisCoolTemp_Set_xx_xxxxxx°C(°F)
24(**)Discharge heating set temperatureAVAC_DisHeatTemp_Set_xx_xxxxxx°C(°F)
25(**)Discharge current temperatureAIAC_DisCurrentTemp_xx_xxxxxx°C(°F)

Temperature setting range can be different depending on model. The standard range is noted below:

  • Auto: 18~30°C (64~86°F)
  • Cool: 18~30°C (64~86°F)
  • Heat: 16~30°C (60~86°F)
  • Fan: Temperature cannot be adjusted
  • Dry: 18~30°C (64~86°F)

(*) Mark is optionally supported. For OAP Duct unit (**) mark is supported.

VRF Multi-position AHU and AHU kit

 

Instance Number

 

 

Object

 

 

Object Type

 

 

Object Name

UnitStatus value
InactiveActive
Text-1Text-2Text-3Text-4Text-5
1Indoor temperatureAIAHU_RoomTemp_xx_xxxxxx°C(°F)
2Set temperatureAVAHU_Temp_Set_xx_xxxxxx°C(°F)
3Setting lower temperature limitAVAHU_Cool_LimitTemp_xx_xxxxxx°C(°F)
4Setting upper temperature limitAVAHU_Heat_LimitTemp_xx_xxxxxx°C(°F)
5The power value of an indoor unit

after the basic date

AIAHU_Baseline_kWh_xx_xxxxxxkWh
 

6

The number of hours usage of an indoor unit after the basic date 

AI

 

AHU_Baseline_Minute_xx_xxxxxx

 

Minute

7Power value within periodAIAHU_Period_kWh_xx_xxxxxxkWh
8The number of hours usage of an

indoor unit within period

AIAHU_Period_Minute_xx_xxxxxxMinute
9Power On/OffBVAHU_Power_xx_xxxxxxOffOn
10Applying lower temperature limit

setting

BVAHU_Cool_Limit_set_xx_xxxxxxFalseTrue
11Applying upper temperature limit

setting

BVAHU_Heat_Limit_set_xx_xxxxxxFalseTrue
12Filter sign statusBIAHU_FilterSign_xx_xxxxxxFalseTrue
13Filter sign resetBOAHU_FilterSign_Reset_xx_xxxxxxFalseTrue
14Operation mode statusMVAHU_Operation_Mode_xx_xxxxxxAutoCoolHeatFanDry
15Operation mode limit statusMVAHU_Mode_Limit_xx_xxxxxxNo LimitCool OnlyHeat Only
16Remote controller limit statusMVAHU_Remocon_Limit_xx_xxxxxxEnable RCDisable RCConditional RC
 

17

Integrated error code of both indoor unit and outdoor unit 

AI

 

AHU_Error_Code_xx_xxxxxx

 

Refer to Samsung integrated error code list

18(*)Discharge cooling set temperatureAVAHU_DisCoolSetTemp_xx_xxxxxx°C(°F)
19(*)Discharge heating set temperatureAVAHU_DisHeatSetTemp_xx_xxxxxx°C(°F)
20(*)Discharge current temperatureAIAHU_Dis_CurrentTemp_xx_xxxxxx°C(°F)
21(**)Humidification settingBVAHU_Humidification_xx_xxxxxxOffOn
22(**)Outdoor air intake settingBVAHU_OAIntake_xx_xxxxxxOffOn
23(**)Outdoor cooling settingBVAHU_OutdoorCool_xx_xxxxxxOffOn
24Fan speed statusMVAHU_FanSpeed_xx_xxxxxxLowMidHigh
25(**)Set humidity statusMVAHU_SetHumidity_xx_xxxxxxLowMidHigh
26(**)Current humidity statusMIAHU_CurrentHumidity_xx_xxxxxxLowMidHigh
27AHU NotifyNCAHU_Notify_xx_xxxxxxWhen the error occurred, send event to list of destination in the recipient_list. (Max : 8)

* Not supported as standard, additional sensors and unit configuration required. ** Not supported for North American AHU models.

VRF Chiller

 

Instance Number

 

 

Object

 

 

Object Type

 

 

Object Name

UnitStatus value
InactiveActive
Text-1Text-2Text-3Text-4Text-5
1Chilled Water TemperatureAIMC_WaterTemp_xx_xxxxxx°C(°F)
2Set temperatureAVMC_WaterTemp_Set_xx_xxxxxx°C(°F)
3Demand limit settingAVMC_Demand_Set_xx_xxxxxx%
 

4

The number of hours usage of an indoor unit after the basic date 

AI

 

MC_Baseline_Minute_xx_xxxxxx

 

Minute

5The number of hours usage of an

indoor unit within period

AIMC_Period_Minute_xx_xxxxxxMinute
6Power On/Off operationBVMC_Power_xx_xxxxxxOffOn
7Water LawBOMC_Water_Law_xx_xxxxxxFalseTrue
8QuietBVMC_Quiet_xx_xxxxxxOffOn
9Forced FanBVMC_Forced_Fan_xx_xxxxxxOffOn
10Operation mode statusMVMC_Operation_Mode_xx_xxxxxxCoolHeatCool StorageHot Water
11Remote controller limit statusMVMC_Remocon_Limit_xx_xxxxxxEnable RCDisable RCConditional RC
12Integrated error codeAIMC_Error_Code_xx_xxxxxx
13VRF CHILLER NotifyNCMC_Notify_xx_xxxxxxWhen the error occurred, send event to list of destination in the recipient_list. (Max : 8)

BACnet Device Object does not support master function of VRF CHILLER.

Digital input / output

 

Instance Number

 

 

Object

 

 

Object Type

 

 

Object Name

UnitStatus value
InactiveActive
Text-1Text-2Text-3Text-4Text-5
1Digital Input 1BIDI_01_xx_xx (BACnet Gateway Reserved)OffOn
2Digital Input 2BIDI_02_xx_xx (BACnet Gateway Reserved)OffOn
3Digital Input 3BIDI_03_xx_xxOffOn
4Digital Input 4BIDI_04_xx_xxOffOn
5Digital Input 5BIDI_05_xx_xxOffOn
6Digital Input 6BIDI_06_xx_xxOffOn
7Digital Input 7BIDI_07_xx_xxOffOn
8Digital Input 8BIDI_08_xx_xxOffOn
9Digital Input 9BIDI_09_xx_xxOffOn
10Digital Input 10BIDI_10_xx_xxOffOn
11Digital Output 1BODO_01_xx_xx (BACnet Gateway Reserved)OffOn
12Digital Output 2BODO_02_xx_xx (BACnet Gateway Reserved)OffOn
13Digital Output 3BODO_03_xx_xxOffOn
14Digital Output 4BODO_04_xx_xxOffOn
15Digital Output 5BODO_05_xx_xxOffOn
16Digital Output 6BODO_06_xx_xxOffOn
17Digital Output 7BODO_07_xx_xxOffOn
18Digital Output 8BODO_08_xx_xxOffOn

Caution

  • You may use ALL_OFF command to turn on all the indoor units but it is not recommended.
  • If communication error occurs on devices such as SIM, On/Off Controller, Interface Module etc., other functions such as power distribution may also create a problem. You must have BMS system to check the errors and you must take action immediately.

Interface module (outdoor unit)

Instance NumberObjectObject TypeObject NameUnitStatus value
InactiveActive
Text-1Text-2Text-3Text-4Text-5
1Outside temperatureAIODU_Outside_Temp_xx_xxxx°C(°F)
 

2(*)

 

Cool capacity compensation

 

AV

 

ODU_Cool_Compensation_xx_ xxxx

0 : 5~7°C(41~45°F)

1 : 7~9°C(41~48°F)

2 : 9~11°C(48~52°F)

3 : 10~12°C(50~54°F)

4 : 11~13°C(52~55°F)

5 : 12~14°C(54~57°F)

6 : 13~15°C(55~59°F)

14 : Auto control (from ODU)

3(*) 

Heat capacity compensation

 

AV

 

ODU_Heat_Compensation_xx_ xxxx

0 : 25kg/cm²

1 : 26kg/cm²

2 : 27kg/cm²

3 : 28kg/cm²

4 : 29kg/cm²

5 : 30kg/cm²

6 : 31kg/cm²

7 : 32kg/cm²

8 : 33kg/cm²

14 : Auto control (from ODU)

4Compressor statusBIODU_Comp_Status_xx_xxxxFalseTrue
5Interface module error codeAIRepeater_Error_Code_xx_xxxxRefer to the list of the integrated error code
6Interface module notifyNCIM_Notify_xx_xxxxWhen the error occurred, send event to list of destination in the recipient list. (Max : 8)

* Only available for supported models

SIM (PIM)

Instance

Number

ObjectObject TypeObject NameStatus value
1SIM (PIM) error codeAISIM_Error_Code_xx_xxRefer to list of error code
2SIM (PIM) NotifyNCSIM_Notify_xx_xxWhen the error occurred, send event to list of destination in the recipient list. (Max : 8)

BACnet Gateway)

Instance

Number

Control and MonitoringObject TypeObject NameStatus value
1All device OFFBOALL_OFF_xxInactive : All devices Off
1DMS2.5 StatusAI 

DMS2_Status_xx

0: Normal

8: Emergency stop 105: Tracking in progress

108: Tracking failed

10 : DMS2.5 / BACnet communication failed

1BACnet error codeAIBACnetApp_Error_ Code_xxBACnet error code
2Gateway NotifyNCGW_Notify_xxWhen the error occurred, send event to list of destination in the recipient_list. (Max : 8)

FAQ

Q: How do I reset the BACnet Gateway to factory settings?
A: To reset the gateway to factory settings, locate the reset button on the device and hold it down for 10 seconds until the indicator lights flash. Release the button, and the gateway will reboot with default settings.